Separation Method - Fujitsu ARYG72LHTA Service Instruction

Duct type inverter
Hide thumbs Also See for ARYG72LHTA:
Table of Contents

3-5. SEPARATION METHOD

It is possible to install the indoor unit through narrow openings by separating the heat exchanger unit
and fan unit.
The separation method is as follows;
1. Remove parts (1) and (2).
(1) Control box cover
(2) Connection plates
2. Disconnect the wiers(3).
- Pipe thermistor wire
-Drain pump wire
-Float SW wire
3. Remove the screws (4).
4. Separate the heat exchanger unit and fan unit.
To attach the units again, reverse the instructions above.
Do not damage the wires.
(2)
Heat exchanger
unit
Slit
(4)
03-22
Wire(s)
Fan unit
(3)
(1)
(2)