Fault Recall - Daikin DX17VSS B Series Service Instructions Manual

Inverter outdoor units with r-410a refrigerant
Table of Contents
SERVICING

FAULT RECALL

WARNING
HIGH VOLTAGE!
T
O AVOID PERSONAL INJURY OR DEATH DUE TO
,
ELECTRICAL SHOCK
DISCONNECT ELECTRICAL POWER
BEFORE PERFORMING ANY SERVICE OR MAINTENANCE
the integrated control module is equipped with a momen-
tary push-button switch that can be used to display the last
six faults on the 7 segment LEd display. to display the
faults, follow the steps below.
NOTE: the integrated control module must be in Standby
Mode (no thermostat inputs).
1. Press fAULt RECALL button (for 2 to 5 seconds).
the 7 segment LEd display will show solid "--".
NOTE: if fAULt RECALL button is not pressed long enough
(for 2 to 5 seconds), the control goes back to Standby
Mode.
2. Release the fAULt RECALL button. the 7 segment
LEd display will show the most recent fault.
3. Subsequent pressing of the fAULt RECALL button
will recall a previous fault. At the end of the faults, the
7 segment LEd display will show "--" and go back to
Standby Mode.
NOTE: Consecutively repeated faults are displayed a
maximum of three times. if the fAULt RECALL button is left
untouched longer than 3 minutes, the control goes back to
Standby Mode.
to clear the error code history:
1. Press fAULt RECALL button until the 7 segment LEd
display blinks "--".
2. Release the fAULt RECALL button. the 7 segment LEd
display will show "88" and clear the faults.
NOTE: if fAULt RECALL button is pressed for longer than
15 seconds, control goes back to Standby Mode.
34
.
NOTE: for the cased coil application, the active fault codes
displayed on this control board are information related only
to CAPE(A)* / CHPE*.
the active fault codes of gas furnaces and modular blowers
are displayed on the control board installed in each unit.
When trouble of the indoor unit occurs, check the active
fault codes on control board of each unit.
Please refer to the Service Manual of each unit about the
troubleshooting Gas furnace and Modular Blower.