LG Multi F A2UW14GFA0 Engineering Product Data Book
LG Multi F A2UW14GFA0 Engineering Product Data Book

LG Multi F A2UW14GFA0 Engineering Product Data Book

Heat pump 50hz/r410a
Heat pump 50Hz/R410A
0CIM0-02E (Replaces 0CIM0-02D)
Table of Contents
loading

Summary of Contents for LG Multi F A2UW14GFA0

  • Page 1 Heat pump 50Hz/R410A 0CIM0-02E (Replaces 0CIM0-02D)
  • Page 2 50Hz/R410A Part 1 General information Part 2 Product data Part 3 Design and installation Part 4 Special Part...
  • Page 3 As a part of vertical integration LG makes all the key components in house, which gives us an edge to LG to make better and latest technology products with best quality in optimized time.
  • Page 4 Part 1 General information 1. Model line up 2. Nomenclature 3. Appearance 4. Combination...
  • Page 5: Model Line Up

    1. Model line up 1.1 Outdoor units (1 phase) Nominal Capacity(kW) A2UW14GFA0 A2UW16GFA0 Model Name [MU2M15 UL2] [MU2M17 UL2] No.of connectable indoor units Max.2 Total capacity index of kBtu/h connectable indoor units Power supply 220-240V, 1Ø, 50Hz Chassis Nominal Capacity(kW) A3UW18GFA0 A3UW21GFA0 Model Name...
  • Page 6 1. Model line up (1 phase) Nominal Capacity(kW) 11.7 A5UW40GFA0 Model Name [MU5M40 UO2] No.of connectable indoor units Max.5 Total capacity index of kBtu/h connectable indoor units Power supply 220-240V, 1Ø, 50Hz Chassis (1 phase) Nominal Capacity(kW) 11.7 14.1 16.7 A7UW40GFA0 A8UW48GFA0 A9UW56GFA0...
  • Page 7 1. Model line up 1.2 BD(Branch distributor) units No. of connectable indoor units Max. 2 Max. 3 Max. 4 Model name PMBD3620 PMBD3630 PMBD3640 Connectable indoor unit capacity kBtu/h 5~24 5~24 5~24 BD unit 1.3 Branches Specifications Branch No. of BD Accessory Applicable Type...
  • Page 8 2. Nomenclature 2.1 Outdoor unit(Global) Serial number Function A : Basic Multi type F : Free joint multi type Electrical rating G : 220-240V, 1Ø, 50Hz / 220V, 1Ø, 60Hz L : 380-415V, 3Ø, 50Hz / 380V, 3Ø, 60Hz Cooling/heating capacity Ex) 24,000 Btu/h Class →...
  • Page 9 2. Nomenclature 2.3 Outdoor unit(Europe) Serial number Outdoor unit chassis name Cooling/heating capacity Ex) 18,000 Btu/h Class → '18' Pipe Connecting Type M : Multiple pipes Indicates that this is multi system outdoor unit using R410A Ex) MU3 : Connectable max. 3 indoor units MU4 : Connectable max.
  • Page 10 3. Appearance LG multi system provides various indoor units such as wall mounted, ART COOL, ART COOL Mirror, ceiling cassette, ceiling concealed duct, ceiling & floor , Ceiling suspended and console. Outdoor unit BD(Branch distributor) unit Outdoor unit Y Branch...
  • Page 11: Selection Procedure

    4. Combination 4.1 Selection procedure Outdoor units selection In general, outdoor unit may be selected as follows, though the location of the unit, and usage of the room, etc. should be considered. The combination of indoor and outdoor unit was to be decided that the sum of indoor unit capacity index should be smaller than the max.
  • Page 12 4. Combination (3 phase) Nominal Capacity(kW) 13.5 14.1 16.7 A7UW42LFA0 A8UW48LFA0 A9UW56LFA0 Model name [FM41AH U32] [FM49AH U32] [FM57AH U32] Cooling 11.2 14.0 15.5 Rated capacity (kW) Heating 12.5 16.0 17.4 Number of indoor units Max. 7 units Max. 8 units Max.
  • Page 13 4. Combination 4.2 Combination of indoor and outdoor unit The total capacity index of indoor units is the sum of capacity index of each units and should be within the capacity index of the outdoor unit. Nominal Capacity of Outdoor Unit 4.1 kW 5.3 kW 7.0 kW / 7.9 kW...
  • Page 14: Part 2 Product Data

    Part 2 Product data n Outdoor units 1. Multiple piping type 2. Distributor type (1 phase) 3. Distributor type (3 phase) 4. BD Unit (Distributor Box)
  • Page 15 Multiple piping type 1. Power supply 2. List of functions 3. Specifications 4. Combination table 5. Dimensions 6. Piping diagrams 7. Wiring diagrams 8. Capacity tables 9. Operation range 10. Electrical characteristics 11. Field wiring diagram 12. Sound levels...
  • Page 16: Power Supply

    1. Multiple piping type MULTI F 1.1 Power supply Type Outdoor unit Capacity[kBtu/h(kW)] Circuit breaker capacity Power supply A2UW14GFA0 [MU2M15 UL2] 14.0 (4.10) A2UW16GFA0 [MU2M17 UL2] 16.0 (4.69) A3UW18GFA0 [MU3M19 UE2] 18.0 (5.27) A3UW21GFA0 [MU3U21 UE2] 21.0 (6.15) Heat Pump 220-240V, 1Ø, 50Hz A4UW24GFA0 [MU4M25 U42] 24.0 (7.03)
  • Page 17: List Of Functions

    1. Multiple piping type MULTI F 1.2 List of functions A2UW14GFA0 [MU2M15 UL2] Category Functions A2UW16GFA0 [MU2M17 UL2] Defrost / Deicing High pressure switch Low pressure switch Phase protection Reliability Restart delay (3-minutes) Self diagnosis Soft start Test function Night Silent Operation Wiring Error Check Convenience Peak Control...
  • Page 18 1. Multiple piping type MULTI F A3UW18GFA0 [MU3M19 UE2] A3UW21GFA0 [MU3M21 UE2] Category Functions A4UW24GFA0 [MU4M25 U42] A4UW27GFA0 [MU4M27 U42] A5UW30GFA0 [MU5M30 U42] A5UW40GFA0 [MU5M40 UO2] Defrost / Deicing High pressure switch Low pressure switch Phase protection Reliability Restart delay (3-minutes) Self diagnosis Soft start Test function...
  • Page 19: Specifications

    1. Multiple piping type MULTI F 1.3 Specifications A2UW14GFA0 A2UW16GFA0 Outdoor unit [MU2M15 UL2] [MU2M17 UL2] Testing Combination MS07AQ NB0 x 2EA MS09AQ NB0 x 2EA Min.~Rated~Max. 0.88 ~ 4.10 ~ 5.39 0.88 ~ 4.69 ~ 5.39 Cooling Min.~Rated~Max. Btu/h 3,000 ~ 14,000 ~ 18,400 3,000 ~ 16,000 ~ 18,400 Capacity...
  • Page 20 1. Multiple piping type MULTI F A3UW18GFA0 A3UW21GFA0 Outdoor unit [MU3M19 UE2] [MU3M21 UE2] Testing Combination MS07AQ NB0 x 3EA MS07AQ NB0 x 3EA Min.~Rated~Max. 1.35 ~ 5.27 ~ 6.33 1.41 ~ 6.15 ~ 7.32 Cooling Min.~Rated~Max. Btu/h 4,600 ~ 18,000 ~ 21,600 4,800 ~ 21,000 ~ 25,000 Capacity Min.~Rated~Max.
  • Page 21 1. Multiple piping type MULTI F A4UW24GFA0 A4UW27GFA0 Outdoor unit [MU4M25 U42] [MU4M27 U42] Testing Combination MS07AQ NB0 x 4EA MS07AQ NB0 x 4EA Min.~Rated~Max. 1.32 ~ 7.03 ~ 8.50 1.32 ~ 7.91 ~ 9.49 Cooling Min.~Rated~Max. Btu/h 4,500 ~ 24,000 ~ 29,000 4,500 ~ 27,000 ~ 32,400 Capacity Min.~Rated~Max.
  • Page 22 1. Multiple piping type MULTI F A5UW30GFA0 A5UW40GFA0 Outdoor unit [MU5M30 U42] [MU5M40 UO2] Testing Combination MS07AQ NB0 x 5EA MS09AQ NB0 x 5EA Min.~Rated~Max. 1.32 ~ 8.79 ~ 10.6 0.88 ~ 11.2 ~ 13.5 Cooling Min.~Rated~Max. Btu/h 4,500 ~ 30,000 ~ 36,000 3,000 ~ 38,200 ~ 46,000 Capacity Min.~Rated~Max.
  • Page 23: Combination Table

    1. Multiple piping type MULTI F 1.4 Combination table Models : A2UW14GFA0 [MU2M15 UL2] Cooling Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Total Unit-A Unit-B Btu/h Btu/h Btu/h Rated 3,000 5,000 6,000 4,200 7,000 8,400 1UNIT...
  • Page 24 1. Multiple piping type MULTI F Models : A2UW16GFA0 [MU2M17 UL2] Cooling Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Total Unit-A Unit-B Btu/h Btu/h Btu/h Rated 3,000 5,000 6,000 4,200 7,000 8,400 1 UNIT 5,400 9,000 10,800...
  • Page 25 1. Multiple piping type MULTI F Models : A3UW18GFA0 [MU3M19 UE2] Cooling Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Total Unit-A Unit-B Unit-C Btu/h Btu/h Btu/h Min Rated Max 4,600 5,000 6,000 4,600 7,000 8,400...
  • Page 26 1. Multiple piping type MULTI F Heating Heating Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Total Unit-A Unit-B Unit-C Btu/h Btu/h Btu/h Min Rated Max 4,800 5,500 6,325 4,800 8,400 9,660 1,027 1 Unit 6,480 10,800 12,420...
  • Page 27 1. Multiple piping type MULTI F Models : A3UW21GFA0 [MU3U21 UE2] Cooling Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Total Unit-A Unit-B Unit-C Btu/h Btu/h Btu/h Min Rated Max 4,800 5,000 5,500 6,300 7,000 7,700...
  • Page 28 1. Multiple piping type MULTI F Heating Heating Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Total Unit-A Unit-B Unit-C Btu/h Btu/h Btu/h Min Rated Max 5,000 5,500 6,050 7,560 8,000 8,800 1 Unit 7,560 10,000 10,900...
  • Page 29 1. Multiple piping type MULTI F Models : A4UW24GFA0 [MU4M25 U42] Cooling Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Btu/h Btu/h Btu/h Rated Max 4,500 5,000 5,500 1,029 6,300...
  • Page 30 1. Multiple piping type MULTI F Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Btu/h Btu/h Btu/h Rated Max 12,000 20,000 24,000 1,420 1,971 13,200 22,000 26,400 1,540 2,206 14,400...
  • Page 31 1. Multiple piping type MULTI F Heating Heating Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Btu/h Btu/h Btu/h Rated Max 4,950 5,500 6,050 1,294 7,560 8,000 8,800 1,294 7,560 10,000...
  • Page 32 1. Multiple piping type MULTI F Heating Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Btu/h Btu/h Btu/h Rated Max 13,200 22,000 24,200 1,430 1,873 14,700 24,500 26,950 1,630 2,088 15,840...
  • Page 33 1. Multiple piping type MULTI F Models : A4UW27GFA0 [MU4M27 U42] Cooling Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Btu/h Btu/h Btu/h Rated Max 4,500 5,000 5,500 1,029 6,300...
  • Page 34 1. Multiple piping type MULTI F Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Btu/h Btu/h Btu/h Rated Max 12,000 20,000 24,000 1,420 1,971 13,200 22,000 26,400 1,540 2,206 14,400...
  • Page 35 1. Multiple piping type MULTI F Heating Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Btu/h Btu/h Btu/h Rated Max 5,000 5,500 6,050 1,256 7,560 8,000 8,800 1,256 7,560 10,000...
  • Page 36 1. Multiple piping type MULTI F Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Btu/h Btu/h Btu/h Rated Max 14,400 24,000 26,880 1,032 1,720 2,430 15,840 26,400 29,568 1,104 1,840...
  • Page 37 1. Multiple piping type MULTI F Models : A5UW30GFA0 [MU5M30 U42] Cooling Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Unit-E Total Unit-A Unit-B Unit-C Unit-D Unit-E Btu/h Btu/h Btu/h Min Rated Max 4,500 5,000 5,500...
  • Page 38 1. Multiple piping type MULTI F Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Unit-E Total Unit-A Unit-B Unit-C Unit-D Unit-E Btu/h Btu/h Btu/h Min Rated Max 18,000 5.3 30,000 33,600 9.9 1,584 2,640 3,206 18,000 5.3...
  • Page 39 1. Multiple piping type MULTI F Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Unit-E Total Unit-A Unit-B Unit-C Unit-D Unit-E Btu/h Btu/h Btu/h Min Rated Max 18,000 5.3 30,000 36,000 10.6 1,280 2,200 3,380 18,000 5.3 30,000...
  • Page 40 1. Multiple piping type MULTI F Heating Heating Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Unit-E Total Unit-A Unit-B Unit-C Unit-D Unit-E Btu/h Btu/h Btu/h Min Rated Max 5,000 5,500 6,050 1,294 7,560 8,000 8,800...
  • Page 41 1. Multiple piping type MULTI F Heating Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Unit-E Total Unit-A Unit-B Unit-C Unit-D Unit-E Btu/h Btu/h Btu/h Min Rated Max 20,700 34,500 10.1 38,640 11.3 1,584 2,640 3,775 20,700...
  • Page 42 1. Multiple piping type MULTI F Heating Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Unit-E Total Unit-A Unit-B Unit-C Unit-D Unit-E Btu/h Btu/h Btu/h Min Rated Max 2.8 20,700 34,500 10.1 41,400 12.1 1,320 2,200 3,700 2.8 20,700...
  • Page 43 1. Multiple piping type MULTI F Models : A5UW40GFA0 [MU5M40 UO2] Cooling Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Unit-E Total Unit-A Unit-B Unit-C Unit-D Unit-E Btu/h Btu/h Btu/h Min Rated Max 3,000 5,000 6,000...
  • Page 44 1. Multiple piping type MULTI F Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Unit-E Total Unit-A Unit-B Unit-C Unit-D Unit-E Btu/h Btu/h Btu/h Min Rated Max 22,920 6.7 38,200 11.2 46,000 13.5 1,693 2,730 4,150 22,920...
  • Page 45 1. Multiple piping type MULTI F Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Unit-E Total Unit-A Unit-B Unit-C Unit-D Unit-E Btu/h Btu/h Btu/h Min Rated Max 22,920 6.7 38,200 11.2 46,000 13.5 1,693 2,730 4,150 22,920...
  • Page 46 1. Multiple piping type MULTI F Cooling Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Unit-E Total Unit-A Unit-B Unit-C Unit-D Unit-E Btu/h Btu/h Btu/h Min Rated Max 2.7 22,920 6.7 38,200 11.2 46,000 13.5 1,693 2,730 4,150 5.4 22,920...
  • Page 47 1. Multiple piping type MULTI F Heating Heating Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Unit-E Total Unit-A Unit-B Unit-C Unit-D Unit-E Btu/h Btu/h Btu/h Min Rated Max 3,300 5,500 6,600 1,120 1,826 4,620 7,700...
  • Page 48 1. Multiple piping type MULTI F Heating Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Unit-E Total Unit-A Unit-B Unit-C Unit-D Unit-E Btu/h Btu/h Btu/h Min Rated Max 25,620 42,700 12.5 51,200 15.0 1,742 2,810 4,450 25,620...
  • Page 49 1. Multiple piping type MULTI F Heating Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Unit-E Total Unit-A Unit-B Unit-C Unit-D Unit-E Btu/h Btu/h Btu/h Min Rated Max 25,620 42,700 12.5 51,200 15.0 1,742 2,810 4,450 25,620...
  • Page 50 1. Multiple piping type MULTI F Heating Combination Total Capacity (kW) Each capacity Input (kBtu/h) Operation (kW) Rated Unit-A Unit-B Unit-C Unit-D Unit-E Total Unit-A Unit-B Unit-C Unit-D Unit-E Btu/h Btu/h Btu/h Min Rated Max 3.0 25,620 42,700 12.5 51,200 15.0 1,742 2,810 4,450 3.0 25,620...
  • Page 51 1. Multiple piping type MULTI F 1.5 Dimensions 36 _ Heat Pump 50Hz/R410A...
  • Page 52 1. Multiple piping type MULTI F _ 37 Heat Pump 50Hz/R410A...
  • Page 53 1. Multiple piping type MULTI F 38 _ Heat Pump 50Hz/R410A...
  • Page 54 1. Multiple piping type MULTI F Heat Pump _ 39 50Hz/R410A...
  • Page 55: Piping Diagrams

    1. Multiple piping type MULTI F 1.6 Piping diagrams Models : A2UW14GFA0 [MU2M15 UL2], A2UW16GFA0 [MU2M17 UL2] Outdoor Unit Inlet Air Temperature Thermistor Ø6.35 / 2 way Flare Connection Electronic Expansion Valve Condenser Out Temperature Thermistor ROOM A ROOM B ROOM A ROOM B Suction...
  • Page 56 1. Multiple piping type MULTI F Models : A3UW18GFA0 [MU3M19 UE2], A3UW21GFA0 [MU3M21 UE2] Outdoor Unit Inlet Air Temperature Thermistor Condensing Ø6.35 Temperature Thermistor Flare Connection Electronic Expansion Valve Condenser Out ROOM A Temperature Main SVC V/V Thermistor ROOM B ROOM C Pressure Sensor...
  • Page 57 1. Multiple piping type MULTI F Models : A4UW24GFA0 [MU4M25 U42], A4UW27GFA0 [MU4M27 U42], A5UW30GFA0 [MU5M30 U42] Outdoor Unit Condenser Out Inlet Air Ø 6.35 Temperature Temperature Thermistor Flare Connection Thermistor Electronic Condensing Expansion Temperature Valve Thermistor ROOM A ROOM B Main SVC V/V ROOM C ROOM D...
  • Page 58 1. Multiple piping type MULTI F Models : A5UW40GFA0 [MU5M40 UO2] Outdoor Unit Condenser Out Inlet Air Ø 6.35 Temperature Temperature Thermistor Flare Connection Thermistor Electronic Condensing Expansion Temperature Valve Thermistor ROOM A ROOM B ROOM C Electronic Main Expansion SVC V/V ROOM D Valve...
  • Page 59: Wiring Diagrams

    1. Multiple piping type MULTI F 1.7 Wiring diagrams Models : A2UW14GFA0 [MU2M15 UL2], A2UW16GFA0 [MU2M17 UL2] Models : A3UW18GFA0 [MU3M19 UE2] 44 _ Heat Pump 50Hz/R410A...
  • Page 60 1. Multiple piping type MULTI F Models : A3UW21GFA0 [MU3U21 UE2] Models : A4UW24GFA0 [MU4M25 U42] _ 45 Heat Pump 50Hz/R410A...
  • Page 61 1. Multiple piping type MULTI F Models : A4UW27GFA0 [MU4M27 U42] Models : A5UW30GFA0 [MU5M30 U42] 46 _ Heat Pump 50Hz/R410A...
  • Page 62 1. Multiple piping type MULTI F Models : A5UW40GFA0 [MU5M40 UO2] _ 47 Heat Pump 50Hz/R410A...
  • Page 63: Capacity Tables

    1. Multiple piping type MULTI F 1.8 Capacity tables Models : A2UW14GFA0 [MU2M15 UL2] [Cooling capacity] Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 1.39 0.26 1.48 0.35 1.57 0.38 1.61 0.39 1.74 0.39 1.83 0.39 1.36 0.28...
  • Page 64 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.46 0.68 4.74 0.92 5.02 1.00 5.16 1.01 5.58 1.02 5.85 1.02 4.35 0.73 4.63 0.95 4.91 1.03 5.05 1.04 5.47 1.06 5.75 1.07...
  • Page 65 1. Multiple piping type MULTI F [Heating capacity] Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 0.96 0.37 1.13 0.39 1.29 0.42 1.46 0.44 1.63 0.46 1.70 0.46 1.71 0.44 0.96 0.38 1.12 0.40 1.29 0.43 1.45 0.45...
  • Page 66 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 2.78 0.99 3.39 1.05 3.99 1.11 4.60 1.16 5.33 1.24 5.57 1.23 5.58 1.16 2.76 1.01 3.36 1.07 3.96 1.13 4.57 1.19 5.30 1.26...
  • Page 67 1. Multiple piping type MULTI F Models : A2UW16GFA0 [MU2M17 UL2] [Cooling capacity] Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 1.39 0.26 1.48 0.35 1.57 0.38 1.61 0.39 1.74 0.39 1.83 0.39 1.36 0.28 1.45 0.36 1.54...
  • Page 68 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.46 0.68 4.74 0.92 5.02 1.00 5.16 1.01 5.58 1.02 5.85 1.02 4.35 0.73 4.63 0.95 4.91 1.03 5.05 1.04 5.47 1.06 5.75 1.07...
  • Page 69 1. Multiple piping type MULTI F [Heating capacity] Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 1.04 0.37 1.19 0.39 1.34 0.42 1.48 0.44 1.63 0.46 1.70 0.46 1.71 0.44 1.04 0.38 1.18 0.40 1.33 0.43 1.47 0.45...
  • Page 70 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 2.78 0.99 3.39 1.05 3.99 1.11 4.60 1.16 5.33 1.24 5.57 1.23 5.58 1.16 2.76 1.01 3.36 1.07 3.96 1.13 4.57 1.19 5.30 1.26...
  • Page 71 1. Multiple piping type MULTI F Models : A3UW18GFA0 [MU3M19 UE2] [Cooling capacity] Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 1.39 0.19 1.48 0.26 1.57 0.28 1.61 0.29 1.74 0.29 1.83 0.29 1.36 0.21 1.45 0.27 1.54...
  • Page 72 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 3.90 0.55 4.15 0.74 4.39 0.80 4.51 0.81 4.88 0.81 5.12 0.81 3.81 0.58 4.05 0.76 4.30 0.82 4.42 0.83 4.79 0.84 5.03 0.85...
  • Page 73 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.74 0.66 5.03 0.89 5.33 0.97 5.48 0.98 5.92 0.99 6.22 0.99 4.63 0.70 4.92 0.92 5.22 0.99 5.37 1.01 5.81 1.02 6.11 1.03...
  • Page 74 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.02 0.70 5.33 0.95 5.64 1.03 5.80 1.04 6.27 1.05 6.59 1.05 4.90 0.74 5.21 0.97 5.53 1.05 5.68 1.07 6.15 1.08 6.47 1.09...
  • Page 75 1. Multiple piping type MULTI F [Heating capacity] Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 1.17 0.33 1.29 0.35 1.40 0.37 1.51 0.39 1.63 0.41 1.70 0.41 1.71 0.39 1.17 0.34 1.28 0.36 1.39 0.38 1.51 0.39...
  • Page 76 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 3.07 1.05 3.72 1.12 4.38 1.18 5.03 1.24 5.68 1.31 5.94 1.30 5.95 1.23 3.05 1.08 3.70 1.14 4.35 1.20 5.00 1.26 5.65 1.34...
  • Page 77 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 3.34 1.18 4.06 1.26 4.79 1.32 5.52 1.39 6.39 1.48 6.68 1.46 6.70 1.39 3.31 1.21 4.03 1.28 4.76 1.36 5.48 1.42 6.36 1.50...
  • Page 78 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 3.34 1.18 4.06 1.26 4.79 1.32 5.52 1.39 6.39 1.48 6.68 1.46 6.70 1.39 3.31 1.21 4.03 1.28 4.76 1.36 5.48 1.42 6.36 1.50...
  • Page 79 1. Multiple piping type MULTI F Models : A3UW21GFA0 [MU3U21 UE2] [Cooling capacity] Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 1.43 0.20 1.52 0.28 1.61 0.30 1.65 0.30 1.78 0.31 1.87 0.31 1.39 0.22 1.48 0.28 1.57...
  • Page 80 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.47 0.65 4.75 0.88 5.03 0.96 5.17 0.97 5.59 0.98 5.87 0.98 4.36 0.69 4.64 0.91 4.92 0.98 5.06 0.99 5.48 1.01 5.76 1.02...
  • Page 81 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.18 0.61 4.45 0.83 4.71 0.90 4.84 0.91 5.23 0.92 5.49 0.92 4.09 0.65 4.35 0.85 4.61 0.92 4.74 0.93 5.13 0.95 5.39 0.96...
  • Page 82 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.90 0.86 6.27 1.16 6.63 1.26 6.82 1.27 7.37 1.28 7.74 1.28 5.76 0.91 6.13 1.19 6.49 1.29 6.68 1.31 7.23 1.33 7.60 1.34...
  • Page 83 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.99 0.86 6.37 1.16 6.74 1.26 6.93 1.27 7.49 1.28 7.87 1.28 5.85 0.91 6.22 1.19 6.60 1.29 6.79 1.31 7.35 1.33 7.72 1.34...
  • Page 84 1. Multiple piping type MULTI F [Heating capacity] Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 1.17 0.31 1.29 0.33 1.40 0.35 1.51 0.37 1.63 0.39 1.70 0.39 1.71 0.37 1.17 0.32 1.28 0.34 1.39 0.36 1.51 0.38...
  • Page 85 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 3.53 1.19 4.29 1.27 5.06 1.34 5.82 1.41 6.75 1.49 7.05 1.48 7.07 1.40 3.49 1.23 4.26 1.30 5.02 1.37 5.79 1.44 6.71 1.52...
  • Page 86 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 3.71 1.32 4.52 1.40 5.32 1.48 6.13 1.56 7.11 1.65 7.42 1.64 7.44 1.55 3.67 1.36 4.48 1.43 5.29 1.51 6.09 1.59 7.06 1.68...
  • Page 87 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 3.71 1.32 4.52 1.40 5.32 1.48 6.13 1.56 7.11 1.65 7.42 1.64 7.44 1.55 3.67 1.36 4.48 1.43 5.29 1.51 6.09 1.59 7.06 1.68...
  • Page 88 1. Multiple piping type MULTI F Models : A4UW24GFA0 [MU4M25 U42] [Cooling capacity] Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 1.39 0.40 1.48 0.54 1.57 0.59 1.61 0.60 1.74 0.60 1.83 0.60 1.36 0.43 1.45 0.56 1.54...
  • Page 89 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.46 0.58 4.74 0.78 5.02 0.84 5.16 0.85 5.58 0.86 5.85 0.86 4.35 0.61 4.63 0.80 4.91 0.86 5.05 0.88 5.47 0.89 5.75 0.90...
  • Page 90 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.69 1.28 7.11 1.72 7.53 1.87 7.74 1.89 8.36 1.91 8.78 1.91 6.53 1.36 6.95 1.78 7.37 1.91 7.58 1.94 8.21 1.97 8.62 1.99...
  • Page 91 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.85 0.67 6.22 0.90 6.59 0.98 6.77 0.99 7.32 1.00 7.68 1.00 5.72 0.71 6.08 0.93 6.45 1.00 6.63 1.02 7.18 1.03 7.55 1.04...
  • Page 92 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.69 0.90 7.11 1.21 7.53 1.31 7.74 1.33 8.36 1.34 8.78 1.34 6.53 0.95 6.95 1.25 7.37 1.34 7.58 1.36 8.21 1.39 8.62 1.40...
  • Page 93 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.69 0.90 7.11 1.21 7.53 1.31 7.74 1.33 8.36 1.34 8.78 1.34 6.53 0.95 6.95 1.25 7.37 1.34 7.58 1.36 8.21 1.39 8.62 1.40...
  • Page 94 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.69 0.91 7.11 1.23 7.53 1.33 7.74 1.34 8.36 1.36 8.78 1.36 6.53 0.96 6.95 1.26 7.37 1.36 7.58 1.38 8.21 1.40 8.62 1.42...
  • Page 95 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.69 0.91 7.11 1.23 7.53 1.33 7.74 1.34 8.36 1.36 8.78 1.36 6.53 0.96 6.95 1.26 7.37 1.36 7.58 1.38 8.21 1.40 8.62 1.42...
  • Page 96 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.69 0.91 7.11 1.23 7.53 1.33 7.74 1.34 8.36 1.36 8.78 1.36 6.53 0.96 6.95 1.26 7.37 1.36 7.58 1.38 8.21 1.40 8.62 1.42...
  • Page 97 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.69 0.91 7.11 1.23 7.53 1.33 7.74 1.34 8.36 1.36 8.78 1.36 6.53 0.96 6.95 1.26 7.37 1.36 7.58 1.38 8.21 1.40 8.62 1.42...
  • Page 98 1. Multiple piping type MULTI F [Heating capacity] Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 1.17 0.64 1.29 0.68 1.40 0.72 1.51 0.76 1.63 0.80 1.70 0.79 1.71 0.75 1.17 0.66 1.28 0.70 1.39 0.74 1.51 0.77...
  • Page 99 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 2.99 1.10 3.63 1.17 4.26 1.24 4.90 1.30 5.54 1.38 5.78 1.37 5.80 1.30 2.97 1.13 3.61 1.20 4.24 1.27 4.87 1.33 5.50 1.41...
  • Page 100 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.45 2.07 5.42 2.20 6.39 2.32 7.36 2.44 8.53 2.59 8.90 2.57 8.93 2.43 4.41 2.12 5.38 2.25 6.34 2.37 7.31 2.49 8.48 2.64...
  • Page 101 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.45 1.53 5.42 1.63 6.39 1.71 7.36 1.80 8.53 1.91 8.90 1.90 8.93 1.79 4.41 1.57 5.38 1.66 6.34 1.75 7.31 1.84 8.48 1.95...
  • Page 102 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.45 1.53 5.42 1.63 6.39 1.71 7.36 1.80 8.53 1.91 8.90 1.90 8.93 1.79 4.41 1.57 5.38 1.66 6.34 1.75 7.31 1.84 8.48 1.95...
  • Page 103 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 3.79 1.26 4.61 1.34 5.43 1.41 6.26 1.48 7.25 1.57 7.58 1.56 7.60 1.48 3.75 1.29 4.57 1.37 5.40 1.44 6.22 1.51 7.21 1.60...
  • Page 104 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.45 1.39 5.42 1.48 6.39 1.56 7.36 1.64 8.53 1.74 8.90 1.72 8.93 1.63 4.41 1.43 5.38 1.51 6.34 1.59 7.31 1.67 8.48 1.77...
  • Page 105 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.45 1.39 5.42 1.48 6.39 1.56 7.36 1.64 8.53 1.74 8.90 1.72 8.93 1.63 4.41 1.43 5.38 1.51 6.34 1.59 7.31 1.67 8.48 1.77...
  • Page 106 1. Multiple piping type MULTI F Models : A4UW27GFA0 [MU4M27 U42] [Cooling capacity] Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 1.39 0.40 1.48 0.54 1.57 0.59 1.61 0.60 1.74 0.60 1.83 0.60 1.36 0.43 1.45 0.56 1.54...
  • Page 107 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 3.90 0.45 4.15 0.60 4.39 0.65 4.51 0.66 4.88 0.67 5.12 0.67 3.81 0.47 4.05 0.62 4.30 0.67 4.42 0.68 4.79 0.69 5.03 0.70...
  • Page 108 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 7.53 1.60 8.00 2.16 8.47 2.34 8.70 2.38 9.41 2.39 9.88 2.40 7.35 1.70 7.82 2.23 8.29 2.40 8.52 2.44 9.23 2.48 9.70 2.50...
  • Page 109 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.85 0.67 6.22 0.90 6.59 0.98 6.77 0.99 7.32 1.00 7.68 1.00 5.72 0.71 6.08 0.93 6.45 1.00 6.63 1.02 7.18 1.03 7.55 1.04...
  • Page 110 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 7.53 1.13 8.00 1.53 8.47 1.65 8.70 1.67 9.41 1.69 9.88 1.69 7.35 1.20 7.82 1.57 8.29 1.69 8.52 1.72 9.23 1.75 9.70 1.76...
  • Page 111 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 7.53 1.13 8.00 1.53 8.47 1.65 8.70 1.67 9.41 1.69 9.88 1.69 7.35 1.20 7.82 1.57 8.29 1.69 8.52 1.72 9.23 1.75 9.70 1.76...
  • Page 112 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 7.53 1.13 8.00 1.53 8.47 1.65 8.70 1.67 9.41 1.69 9.88 1.69 7.35 1.20 7.82 1.57 8.29 1.69 8.52 1.72 9.23 1.75 9.70 1.76...
  • Page 113 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 7.53 1.08 8.00 1.45 8.47 1.57 8.70 1.59 9.41 1.61 9.88 1.61 7.35 1.14 7.82 1.50 8.29 1.61 8.52 1.64 9.23 1.66 9.70 1.68...
  • Page 114 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 7.53 1.08 8.00 1.45 8.47 1.57 8.70 1.59 9.41 1.61 9.88 1.61 7.35 1.14 7.82 1.50 8.29 1.61 8.52 1.64 9.23 1.66 9.70 1.68...
  • Page 115 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 7.53 1.08 8.00 1.45 8.47 1.57 8.70 1.59 9.41 1.61 9.88 1.61 7.35 1.14 7.82 1.50 8.29 1.61 8.52 1.64 9.23 1.66 9.70 1.68...
  • Page 116 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 7.53 1.08 8.00 1.45 8.47 1.57 8.70 1.59 9.41 1.61 9.88 1.61 7.35 1.14 7.82 1.50 8.29 1.61 8.52 1.64 9.23 1.66 9.70 1.68...
  • Page 117 1. Multiple piping type MULTI F [Heating capacity] Outdoor air temp.: (°CWB) Indoor Combination air temp.: Operation capacity index (°CDB) (kBtu/h) 1.17 0.64 1.29 0.68 1.40 0.72 1.51 0.76 1.63 0.80 1.70 0.79 1.71 0.75 1.17 0.66 1.28 0.70 1.39 0.74 1.51 0.77...
  • Page 118 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 3.38 1.10 4.05 1.17 4.71 1.24 5.38 1.30 6.04 1.38 6.31 1.37 6.33 1.30 3.36 1.13 4.02 1.20 4.68 1.27 5.34 1.33 6.00 1.41...
  • Page 119 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.79 2.22 5.83 2.36 6.88 2.49 7.92 2.62 9.18 2.78 9.58 2.76 9.61 2.61 4.75 2.28 5.79 2.41 6.83 2.55 7.87 2.68 9.13 2.83...
  • Page 120 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.64 1.62 5.65 1.72 6.65 1.82 7.66 1.91 8.88 2.03 9.28 2.01 9.30 1.90 4.59 1.66 5.60 1.76 6.61 1.86 7.61 1.95 8.83 2.07...
  • Page 121 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.79 1.83 5.83 1.95 6.88 2.06 7.92 2.17 9.18 2.30 9.58 2.28 9.61 2.16 4.75 1.89 5.79 2.00 6.83 2.11 7.87 2.21 9.13 2.34...
  • Page 122 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.79 1.83 5.83 1.95 6.88 2.06 7.92 2.17 9.18 2.30 9.58 2.28 9.61 2.16 4.75 1.89 5.79 2.00 6.83 2.11 7.87 2.21 9.13 2.34...
  • Page 123 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.79 1.55 5.83 1.65 6.88 1.74 7.92 1.83 9.18 1.94 9.58 1.92 9.61 1.82 4.75 1.59 5.79 1.68 6.83 1.78 7.87 1.87 9.13 1.98...
  • Page 124 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.79 1.55 5.83 1.65 6.88 1.74 7.92 1.83 9.18 1.94 9.58 1.92 9.61 1.82 4.75 1.59 5.79 1.68 6.83 1.78 7.87 1.87 9.13 1.98...
  • Page 125 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.79 1.55 5.83 1.65 6.88 1.74 7.92 1.83 9.18 1.94 9.58 1.92 9.61 1.82 4.75 1.59 5.79 1.68 6.83 1.78 7.87 1.87 9.13 1.98...
  • Page 126 1. Multiple piping type MULTI F Models : A5UW30GFA0 [MU5M30 U42] [Cooling capacity] Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 1.40 0.40 1.49 0.54 1.57 0.59 1.62 0.60 1.75 0.60 1.84 0.60 1.37 0.43 1.45 0.56 1.54...
  • Page 127 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 3.91 0.45 4.16 0.60 4.40 0.65 4.53 0.66 4.89 0.67 5.14 0.67 3.82 0.47 4.07 0.62 4.31 0.67 4.43 0.68 4.80 0.69 5.05 0.70...
  • Page 128 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.11 1.70 8.62 2.29 9.12 2.48 9.38 2.51 10.14 2.53 10.64 2.53 7.92 1.80 8.42 2.36 8.93 2.54 9.19 2.58 9.95 2.62 10.45 2.65...
  • Page 129 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.31 0.52 5.64 0.70 5.98 0.75 6.14 0.76 6.64 0.77 6.97 0.77 5.19 0.55 5.52 0.72 5.85 0.77 6.02 0.78 6.52 0.80 6.85 0.81...
  • Page 130 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 7.27 1.06 7.72 1.44 8.18 1.56 8.41 1.58 9.09 1.59 9.54 1.59 7.10 1.13 7.55 1.48 8.01 1.60 8.23 1.62 8.92 1.65 9.37 1.66...
  • Page 131 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.39 1.43 8.91 1.94 9.44 2.10 9.70 2.13 10.49 2.14 11.01 2.14 8.19 1.52 8.71 1.99 9.24 2.15 9.50 2.18 10.29 2.22 10.81 2.24...
  • Page 132 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.39 1.43 8.91 1.94 9.44 2.10 9.70 2.13 10.49 2.14 11.01 2.14 8.19 1.52 8.71 1.99 9.24 2.15 9.50 2.18 10.29 2.22 10.81 2.24...
  • Page 133 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.39 1.43 8.91 1.94 9.44 2.10 9.70 2.13 10.49 2.14 11.01 2.14 8.19 1.52 8.71 1.99 9.24 2.15 9.50 2.18 10.29 2.22 10.81 2.24...
  • Page 134 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 7.83 1.11 8.32 1.50 8.81 1.62 9.05 1.64 9.79 1.66 10.28 1.66 7.64 1.18 8.13 1.54 8.62 1.66 8.87 1.69 9.60 1.71 10.09 1.73...
  • Page 135 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.39 1.22 8.91 1.65 9.44 1.79 9.70 1.81 10.49 1.83 11.01 1.83 8.19 1.30 8.71 1.70 9.24 1.83 9.50 1.86 10.29 1.89 10.81 1.91...
  • Page 136 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.39 1.22 8.91 1.65 9.44 1.79 9.70 1.81 10.49 1.83 11.01 1.83 8.19 1.30 8.71 1.70 9.24 1.83 9.50 1.86 10.29 1.89 10.81 1.91...
  • Page 137 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.39 1.22 8.91 1.65 9.44 1.79 9.70 1.81 10.49 1.83 11.01 1.83 8.19 1.30 8.71 1.70 9.24 1.83 9.50 1.86 10.29 1.89 10.81 1.91...
  • Page 138 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.39 1.22 8.91 1.65 9.44 1.79 9.70 1.81 10.49 1.83 11.01 1.83 8.19 1.30 8.71 1.70 9.24 1.83 9.50 1.86 10.29 1.89 10.81 1.91...
  • Page 139 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.39 1.20 8.91 1.61 9.44 1.75 9.70 1.77 10.49 1.79 11.01 1.79 8.19 1.27 8.71 1.66 9.24 1.79 9.50 1.82 10.29 1.85 10.81 1.87...
  • Page 140 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.39 1.20 8.91 1.61 9.44 1.75 9.70 1.77 10.49 1.79 11.01 1.79 8.19 1.27 8.71 1.66 9.24 1.79 9.50 1.82 10.29 1.85 10.81 1.87...
  • Page 141 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.39 1.20 8.91 1.61 9.44 1.75 9.70 1.77 10.49 1.79 11.01 1.79 8.19 1.27 8.71 1.66 9.24 1.79 9.50 1.82 10.29 1.85 10.81 1.87...
  • Page 142 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.39 1.20 8.91 1.61 9.44 1.75 9.70 1.77 10.49 1.79 11.01 1.79 8.19 1.27 8.71 1.66 9.24 1.79 9.50 1.82 10.29 1.85 10.81 1.87...
  • Page 143 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.39 1.20 8.91 1.61 9.44 1.75 9.70 1.77 10.49 1.79 11.01 1.79 8.19 1.27 8.71 1.66 9.24 1.79 9.50 1.82 10.29 1.85 10.81 1.87...
  • Page 144 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.39 1.20 8.91 1.61 9.44 1.75 9.70 1.77 10.49 1.79 11.01 1.79 8.19 1.27 8.71 1.66 9.24 1.79 9.50 1.82 10.29 1.85 10.81 1.87...
  • Page 145 1. Multiple piping type MULTI F [Heating capacity] Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 1.17 0.64 1.29 0.68 1.40 0.72 1.51 0.76 1.63 0.80 1.70 0.79 1.71 0.75 1.17 0.66 1.28 0.70 1.39 0.74 1.51 0.77...
  • Page 146 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 3.38 1.10 4.05 1.17 4.71 1.24 5.38 1.30 6.04 1.38 6.31 1.37 6.33 1.30 3.36 1.13 4.02 1.20 4.68 1.27 5.34 1.33 6.00 1.41...
  • Page 147 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.33 2.22 6.49 2.36 7.65 2.49 8.81 2.62 10.21 2.78 10.67 2.76 10.70 2.61 5.28 2.28 6.44 2.41 7.60 2.55 8.76 2.68 10.16 2.83...
  • Page 148 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.41 1.44 5.35 1.53 6.29 1.62 7.23 1.70 8.17 1.81 8.53 1.79 8.56 1.70 4.39 1.48 5.32 1.57 6.26 1.66 7.19 1.74 8.12 1.84...
  • Page 149 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.33 2.03 6.49 2.17 7.65 2.29 8.81 2.40 10.21 2.55 10.67 2.53 10.70 2.39 5.28 2.09 6.44 2.21 7.60 2.34 8.76 2.45 10.16 2.60...
  • Page 150 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.33 2.03 6.49 2.17 7.65 2.29 8.81 2.40 10.21 2.55 10.67 2.53 10.70 2.39 5.28 2.09 6.44 2.21 7.60 2.34 8.76 2.45 10.16 2.60...
  • Page 151 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.33 2.03 6.49 2.17 7.65 2.29 8.81 2.40 10.21 2.55 10.67 2.53 10.70 2.39 5.28 2.09 6.44 2.21 7.60 2.34 8.76 2.45 10.16 2.60...
  • Page 152 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.33 1.90 6.49 2.03 7.65 2.14 8.81 2.25 10.21 2.38 10.67 2.36 10.70 2.24 5.28 1.96 6.44 2.07 7.60 2.19 8.76 2.29 10.16 2.43...
  • Page 153 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.33 1.90 6.49 2.03 7.65 2.14 8.81 2.25 10.21 2.38 10.67 2.36 10.70 2.24 5.28 1.96 6.44 2.07 7.60 2.19 8.76 2.29 10.16 2.43...
  • Page 154 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.33 1.90 6.49 2.03 7.65 2.14 8.81 2.25 10.21 2.38 10.67 2.36 10.70 2.24 5.28 1.96 6.44 2.07 7.60 2.19 8.76 2.29 10.16 2.43...
  • Page 155 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.33 1.90 6.49 2.03 7.65 2.14 8.81 2.25 10.21 2.38 10.67 2.36 10.70 2.24 5.28 1.96 6.44 2.07 7.60 2.19 8.76 2.29 10.16 2.43...
  • Page 156 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.33 1.70 6.49 1.81 7.65 1.91 8.81 2.00 10.21 2.12 10.67 2.11 10.70 1.99 5.28 1.74 6.44 1.84 7.60 1.95 8.76 2.04 10.16 2.16...
  • Page 157 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.33 1.70 6.49 1.81 7.65 1.91 8.81 2.00 10.21 2.12 10.67 2.11 10.70 1.99 5.28 1.74 6.44 1.84 7.60 1.95 8.76 2.04 10.16 2.16...
  • Page 158 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.33 1.70 6.49 1.81 7.65 1.91 8.81 2.00 10.21 2.12 10.67 2.11 10.70 1.99 5.28 1.74 6.44 1.84 7.60 1.95 8.76 2.04 10.16 2.16...
  • Page 159 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.33 1.70 6.49 1.81 7.65 1.91 8.81 2.00 10.21 2.12 10.67 2.11 10.70 1.99 5.28 1.74 6.44 1.84 7.60 1.95 8.76 2.04 10.16 2.16...
  • Page 160 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.33 1.70 6.49 1.81 7.65 1.91 8.81 2.00 10.21 2.12 10.67 2.11 10.70 1.99 5.28 1.74 6.44 1.84 7.60 1.95 8.76 2.04 10.16 2.16...
  • Page 161 1. Multiple piping type MULTI F Models : A5UW40GFA0 [MU5M40 UO2] [Cooling capacity] Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 1.40 0.61 1.49 0.82 1.57 0.89 1.62 0.90 1.75 0.91 1.84 0.91 1.37 0.65 1.45 0.85 1.54...
  • Page 162 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 3.90 0.61 4.14 0.82 4.39 0.89 4.51 0.90 4.87 0.91 5.12 0.91 3.81 0.65 4.05 0.85 4.29 0.91 4.42 0.93 4.78 0.94 5.03 0.95...
  • Page 163 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.08 1.10 8.59 1.49 9.10 1.61 9.35 1.63 10.11 1.65 10.61 1.65 7.89 1.17 8.40 1.53 8.90 1.65 9.16 1.68 9.92 1.71 10.42 1.72...
  • Page 164 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.30 0.72 5.63 0.98 5.96 1.06 6.13 1.07 6.62 1.08 6.95 1.08 5.17 0.77 5.50 1.00 5.83 1.08 6.00 1.10 6.50 1.12 6.83 1.13...
  • Page 165 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 7.25 0.99 7.70 1.34 8.15 1.45 8.38 1.47 9.06 1.48 9.51 1.48 7.08 1.05 7.53 1.37 7.98 1.48 8.21 1.50 8.89 1.53 9.34 1.54...
  • Page 166 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 9.20 1.26 9.77 1.70 10.35 1.84 10.63 1.86 11.50 1.87 12.07 1.88 8.98 1.33 9.55 1.75 10.13 1.88 10.42 1.91 11.28 1.94 11.86 1.96...
  • Page 167 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 10.65 1.48 11.32 2.00 11.98 2.17 12.32 2.20 13.32 2.22 13.98 2.22 10.40 1.57 11.07 2.06 11.73 2.22 12.07 2.26 13.06 2.29 13.73 2.31...
  • Page 168 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 10.65 1.48 11.32 2.00 11.98 2.17 12.32 2.20 13.32 2.22 13.98 2.22 10.40 1.57 11.07 2.06 11.73 2.22 12.07 2.26 13.06 2.29 13.73 2.31...
  • Page 169 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 7.25 0.99 7.70 1.34 8.15 1.45 8.38 1.47 9.06 1.48 9.51 1.48 7.08 1.05 7.53 1.37 7.98 1.48 8.21 1.50 8.89 1.53 9.34 1.54...
  • Page 170 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.92 1.22 9.48 1.64 10.04 1.78 10.32 1.80 11.15 1.82 11.71 1.82 8.71 1.29 9.27 1.69 9.83 1.82 10.11 1.85 10.94 1.88 11.50 1.90...
  • Page 171 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 10.03 1.37 10.66 1.85 11.29 2.00 11.60 2.03 12.54 2.05 13.17 2.05 9.80 1.45 10.42 1.90 11.05 2.05 11.37 2.08 12.31 2.12 12.93 2.14...
  • Page 172 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 10.65 1.48 11.32 2.00 11.98 2.17 12.32 2.20 13.32 2.22 13.98 2.22 10.40 1.57 11.07 2.06 11.73 2.22 12.07 2.26 13.06 2.29 13.73 2.31...
  • Page 173 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 10.65 1.48 11.32 2.00 11.98 2.17 12.32 2.20 13.32 2.22 13.98 2.22 10.40 1.57 11.07 2.06 11.73 2.22 12.07 2.26 13.06 2.29 13.73 2.31...
  • Page 174 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 10.65 1.48 11.32 2.00 11.98 2.17 12.32 2.20 13.32 2.22 13.98 2.22 10.40 1.57 11.07 2.06 11.73 2.22 12.07 2.26 13.06 2.29 13.73 2.31...
  • Page 175 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 8.08 1.10 8.59 1.49 9.10 1.61 9.35 1.63 10.11 1.65 10.61 1.65 7.89 1.17 8.40 1.53 8.90 1.65 9.16 1.68 9.92 1.71 10.42 1.72...
  • Page 176 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 10.03 1.37 10.66 1.85 11.29 2.00 11.60 2.03 12.54 2.05 13.17 2.05 9.80 1.45 10.42 1.90 11.05 2.05 11.37 2.08 12.31 2.12 12.93 2.14...
  • Page 177 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 10.65 1.48 11.32 2.00 11.98 2.17 12.32 2.20 13.32 2.22 13.98 2.22 10.40 1.57 11.07 2.06 11.73 2.22 12.07 2.26 13.06 2.29 13.73 2.31...
  • Page 178 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 10.65 1.48 11.32 2.00 11.98 2.17 12.32 2.20 13.32 2.22 13.98 2.22 10.40 1.57 11.07 2.06 11.73 2.22 12.07 2.26 13.06 2.29 13.73 2.31...
  • Page 179 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 10.65 1.48 11.32 2.00 11.98 2.17 12.32 2.20 13.32 2.22 13.98 2.22 10.40 1.57 11.07 2.06 11.73 2.22 12.07 2.26 13.06 2.29 13.73 2.31...
  • Page 180 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 10.65 1.48 11.32 2.00 11.98 2.17 12.32 2.20 13.32 2.22 13.98 2.22 10.40 1.57 11.07 2.06 11.73 2.22 12.07 2.26 13.06 2.29 13.73 2.31...
  • Page 181 1. Multiple piping type MULTI F Indoor air temp.: (°CWB) Combination Outdoor Operation capacity index air temp.: (kBtu/h) (°CDB) 10.65 1.48 11.32 2.00 11.98 2.17 12.32 2.20 13.32 2.22 13.98 2.22 10.40 1.57 11.07 2.06 11.73 2.22 12.07 2.26 13.06 2.29 13.73 2.31...
  • Page 182 1. Multiple piping type MULTI F [Heating capacity] Outdoor air temp.: (°CWB) Indoor Combination Operation air temp.: capacity index (°CDB) 1.17 0.86 1.29 0.92 1.40 0.97 1.51 1.02 1.63 1.08 1.70 1.07 1.71 1.02 1.17 0.89 1.28 0.94 1.39 0.99 1.51 1.04 1.62...
  • Page 183 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 3.27 0.92 3.83 0.98 4.40 1.03 4.97 1.08 5.54 1.15 5.78 1.14 5.80 1.08 3.25 0.94 3.81 1.00 4.38 1.05 4.94 1.11 5.50 1.17...
  • Page 184 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.12 1.94 7.45 2.07 8.78 2.18 10.12 2.29 11.72 2.43 12.24 2.41 12.28 2.28 6.06 2.00 7.39 2.11 8.72 2.23 10.05 2.34 11.66 2.48...
  • Page 185 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.19 1.24 5.02 1.32 5.84 1.39 6.67 1.46 7.49 1.55 7.82 1.54 7.85 1.46 4.17 1.28 4.99 1.35 5.81 1.43 6.63 1.50 7.45 1.58...
  • Page 186 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.63 1.73 6.83 1.84 8.02 1.94 9.22 2.04 10.42 2.16 10.88 2.14 10.92 2.03 5.60 1.78 6.79 1.88 7.98 1.98 9.17 2.08 10.36 2.20...
  • Page 187 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.60 2.17 8.04 2.31 9.47 2.43 10.91 2.56 12.64 2.71 13.20 2.69 13.24 2.55 6.54 2.23 7.97 2.36 9.40 2.49 10.84 2.61 12.57 2.76...
  • Page 188 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.60 2.17 8.04 2.31 9.47 2.43 10.91 2.56 12.64 2.71 13.20 2.69 13.24 2.55 6.54 2.23 7.97 2.36 9.40 2.49 10.84 2.61 12.57 2.76...
  • Page 189 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 4.92 1.51 5.97 1.61 7.02 1.70 8.07 1.78 9.12 1.89 9.52 1.88 9.55 1.78 4.90 1.55 5.94 1.64 6.98 1.74 8.02 1.82 9.07 1.93...
  • Page 190 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.98 1.83 7.25 1.95 8.53 2.06 9.80 2.17 11.07 2.30 11.56 2.28 11.60 2.16 5.94 1.89 7.21 2.00 8.48 2.11 9.74 2.21 11.01 2.34...
  • Page 191 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.60 2.17 8.04 2.31 9.47 2.43 10.91 2.56 12.64 2.71 13.20 2.69 13.24 2.55 6.54 2.23 7.97 2.36 9.40 2.49 10.84 2.61 12.57 2.76...
  • Page 192 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.60 2.17 8.04 2.31 9.47 2.43 10.91 2.56 12.64 2.71 13.20 2.69 13.24 2.55 6.54 2.23 7.97 2.36 9.40 2.49 10.84 2.61 12.57 2.76...
  • Page 193 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.60 2.17 8.04 2.31 9.47 2.43 10.91 2.56 12.64 2.71 13.20 2.69 13.24 2.55 6.54 2.23 7.97 2.36 9.40 2.49 10.84 2.61 12.57 2.76...
  • Page 194 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 5.80 1.78 7.04 1.90 8.27 2.00 9.51 2.10 10.75 2.23 11.22 2.21 11.26 2.09 5.77 1.83 7.00 1.94 8.23 2.05 9.46 2.15 10.69 2.27...
  • Page 195 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.46 2.05 7.87 2.18 9.27 2.30 10.68 2.42 12.37 2.57 12.92 2.55 12.96 2.41 6.40 2.11 7.80 2.23 9.21 2.36 10.61 2.47 12.30 2.62...
  • Page 196 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.60 2.17 8.04 2.31 9.47 2.43 10.91 2.56 12.64 2.71 13.20 2.69 13.24 2.55 6.54 2.23 7.97 2.36 9.40 2.49 10.84 2.61 12.57 2.76...
  • Page 197 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.60 2.17 8.04 2.31 9.47 2.43 10.91 2.56 12.64 2.71 13.20 2.69 13.24 2.55 6.54 2.23 7.97 2.36 9.40 2.49 10.84 2.61 12.57 2.76...
  • Page 198 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.60 2.17 8.04 2.31 9.47 2.43 10.91 2.56 12.64 2.71 13.20 2.69 13.24 2.55 6.54 2.23 7.97 2.36 9.40 2.49 10.84 2.61 12.57 2.76...
  • Page 199 1. Multiple piping type MULTI F Outdoor air temp.: (°CWB) Combination Indoor Operation capacity index air temp.: (kBtu/h) (°CDB) 6.60 2.17 8.04 2.31 9.47 2.43 10.91 2.56 12.64 2.71 13.20 2.69 13.24 2.55 6.54 2.23 7.97 2.36 9.40 2.49 10.84 2.61 12.57 2.76...
  • Page 200: Operation Range

    1. Multiple piping type MULTI F 1.9 Operation range Models : A2UW14GFA0 [MU2M15 UL2], A2UW16GFA0 [MU2M17 UL2] Cooling Heating Continuous Operation Continuous Operation _ 185 Heat Pump 50Hz/R410A...
  • Page 201 1. Multiple piping type MULTI F Models : A3UW18GFA0 [MU3M19 UE2], A3UW21GFA0 [MU3M21 UE2] A4UW24GFA0 [MU4M25 U42], A4UW27GFA0 [MU4M27 U42] A5UW30GFA0 [MU5M30 U42], A5UW40GFA0 [MU5M40 UO2] Cooling Heating Continuous Operation Continuous Operation 186 _ Heat Pump 50Hz/R410A...
  • Page 202: Electric Characteristics

    1. Multiple piping type MULTI F 1.10 Electric characteristics Unit Power Compressor Model Type Voltage Voltage range A2UW14GFA0 16.7 0.04 0.25 [MU2M15 UL2] A2UW16GFA0 16.7 0.04 0.25 [MU2M17 UL2] A3UW18GFA0 12.8 22.5 0.09 0.59 [MU3M19 UE2] A3UW21GFA0 13.5 23.8 10.3 0.09 0.59 [MU3M21 UE2]...
  • Page 203: Field Wiring Diagrams

    1. Multiple piping type MULTI F 1.11 Field wiring diagrams Models : A2UW/A3UW Outdoor unit Power supply Main switch Circuit breaker Terminal Block outdoor 1(L) 2(N) 3(L) 4(N) 5(A) 5(B) 3(L) 4(N) 5(C) Fuse Power cable (Including earth) 1(L) 2(N) 3(A) 1(L) 2(N)
  • Page 204 1. Multiple piping type MULTI F Models : A4UW/A5UW Outdoor unit Power supply Main switch Terminal Block outdoor Circuit breaker 1(L) 2(N) 1(L) 2(N) 3(A) 1(L) 2(N) 3(B) 1(L) 2(N) 3(C) 1(L) 2(N) 3(D) 1(L) 2(N) 3(E) Fuse Power cable (Including earth) 1(L) 2(N)
  • Page 205 1. Multiple piping type MULTI F Models : A5UW40GFA0 Model only Outdoor unit Power supply Main switch Terminal Block outdoor Circuit breaker 1(L) 2(N) 1(L) 2(N) 3(A) 3(B) 1(L) 2(N) 3(C) 3(D) 1(L) 2(N) 3(E) Fuse Power cable (Including earth) 1(L) 2(N) 1(L)
  • Page 206: Sound Pressure Level

    1. Multiple piping type MULTI F 1.12 Sound levels 1.12.1 Sound pressure level Notes: - Sound measured at 1m away from the center of the unit. Microphone - Data is valid at free field condition. - Data is valid at nominal operation condition. - Reference accoustic pressure 0dB=20 μ...
  • Page 207 1. Multiple piping type MULTI F A3UW21GFA0 [MU3M21 UE2] A4UW24GFA0 [MU4M25 U42] A4UW27GFA0 [MU4M27 U42] ▲ Cooling ▲ Cooling ▲ Cooling Heating Heating Heating NC-65 NC-65 NC-65 NC-60 NC-60 NC-60 NC-55 NC-55 NC-55 NC-50 NC-50 NC-50 NC-45 NC-45 NC-45 NC-40 NC-40 NC-40 NC-35...
  • Page 208: Sound Power Level

    1. Multiple piping type MULTI F 1.12.2 Sound power level Notes: 1. Reference acoustic intensity 0dB = 10E-6μW/m 2. Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of particular room in which the equipment in installed. Sound power Levels [dB(A)] Sound power Levels [dB(A)] Model...
  • Page 209 1. Multiple piping type MULTI F A5UW40GFA0 [MU5M40 UO2] NR-90 NR-85 NR-80 NR-75 NR-70 NR-65 NR-60 NR-55 NR-50 NR-45 NR-40 NR-35 NR-30 1000 2000 4000 8000 Octave Band Center Frequency (Hz) 194 _ Heat Pump 50Hz/R410A...
  • Page 210: Distributor Type

    Distributor type (1 phase) 1. Power supply 2. List of functions 3. Specifications 4. Combination table 5. Dimensions 6. Piping diagrams 7. Wiring diagrams 8. Capacity tables 9. Capacity coefficient factor 10. Operation range 11. Electrical characteristics 12. Field wiring diagram 13.
  • Page 211: Power Supply

    2. Distributor type MULTI F DX (1 phase) 2.1 Power supply Type Outdoor unit Capacity [kBtu/h(kW)] Circuit breaker capacity Power supply A7UW40GFA0 [FM40AH UO2] 38.2 (11.2) A8UW48GFA0 [FM48AH U32] Heat pump 47.8 (12.0) 220-240V, 1Ø, 50Hz A9UW56GFA0 [FM56AH U32] 52.9 (15.5) External wiring procedure - The power supply work is needed only to the outdoor unit.
  • Page 212: List Of Functions

    2. Distributor type MULTI F DX (1 phase) 2.2 List of functions A7UW40GFA0 [FM40AH UO2] Category Functions A8UW48GFA0 [FM48AH U32] A9UW56GFA0 [FM56AH U32] Defrost / Deicing High pressure switch Low pressure switch Phase protection Reliability Restart delay (3-minutes) Self diagnosis Soft start Test function Night Silent Operation...
  • Page 213: Specifications

    2. Distributor type MULTI F DX (1 phase) 2.3 Specifications A7UW40GFA0 A8UW48GFA0 A9UW56GFA0 Outdoor unit [FM40AH UO2] [FM48AH U32] [FM56AH U32] Testing Combination MS09AQ NB0 x 5EA MS07AQ NB0 x 7EA MS09AQ NB0 x 7EA Min.~Rated~Max. 2.8 ~ 11.2 ~ 13.5 3.3 ~ 14.0 ~ 17.0 4.0 ~ 15.5 ~ 18.5 Cooling...
  • Page 214 2. Distributor type MULTI F DX (1 phase) 2.4 Combination table The individual indoor unit capacity can be calculated as follows depending on the total connected capacity of all indoor units. Individual indoor unit Individual indoor unit rated capacity [Q Outdoor unit rated capacity idu(rated) combinational capacity...
  • Page 215 2. Distributor type MULTI F DX (1 phase) [Heating capacity] Heating capacity Total indoor unit Input (W) capacity Rated (kBtu/h) Rated Btu/h Btu/h Btu/h 10,560 17,600 21,120 1,120 1,826 11,880 19,800 23,760 1,260 2,054 12,540 20,900 25,080 1,330 2,168 13,860 23,100 27,720 1,470...
  • Page 216 2. Distributor type MULTI F DX (1 phase) Models : A8UW48GFA0 [FM48AH U32] [Cooling capacity] Cooling capacity Total indoor unit Input (W) capacity Rated (kBtu/h) Rated Btu/h Btu/h Btu/h 11,400 18,535 20,900 1,222 1,665 12,000 19,510 22,000 1,282 1,746 12,600 20,486 23,100 1,341...
  • Page 217 2. Distributor type MULTI F DX (1 phase) [Heating capacity] Heating capacity Total indoor unit Input (W) capacity Rated (kBtu/h) Rated Btu/h Btu/h Btu/h 12,768 23,088 27,365 1,300 1,728 2,470 13,440 24,303 28,482 1,348 1,863 2,663 14,112 25,518 29,600 1,395 1,997 2,855 14,784...
  • Page 218 2. Distributor type MULTI F DX (1 phase) Models : A9UW56GFA0 [FM56AH U32] [Cooling capacity] Cooling capacity Total indoor unit Input (W) capacity Rated (kBtu/h) Rated Btu/h Btu/h Btu/h 13,800 22,437 25,300 1,000 1,460 1,989 14,400 23,412 25,705 1,085 1,520 2,071 15,000 24,388...
  • Page 219 2. Distributor type MULTI F DX (1 phase) [Heating capacity] Heating capacity Total indoor unit Input (W) capacity Rated (kBtu/h) Rated Btu/h Btu/h Btu/h 15,456 27,948 32,138 1,490 2,267 3,240 16,023 28,973 33,407 1,579 2,402 3,433 16,590 29,998 34,676 10.2 1,626 2,473 3,535...
  • Page 220 2. Distributor type MULTI F DX (1 phase) 2.5 Dimensions 1) Outdoor units 10 _ Heat pump 50Hz/R410A...
  • Page 221 2. Distributor type MULTI F DX (1 phase) Heat pump _ 11 50Hz/R410A...
  • Page 222: Piping Diagrams

    2. Distributor type MULTI F DX (1 phase) 2.6 Piping diagrams 1) Outdoor unit Models : A7UW40GFA0 [FM40AH UO2] Outdoor Unit Condenser Out Inlet Air Temperature Temperature Thermistor Thermistor Condensing Temperature Thermistor Ø9.52 Flare Connection Electronic Expansion Valve Ø19.05 Flare Connection Pressure Sensor Discharge...
  • Page 223 2. Distributor type MULTI F DX (1 phase) Models : A8UW48GFA0 [FM48AH U32], A9UW56GFA0 [FM56AH U32] Outdoor Unit Condenser Out Inlet Air Temperature Temperature Thermistor Thermistor Condensing Temperature Thermistor Ø9.52 Flare Connection Electronic Expansion Valve Ø19.05 Flare Connection Pressure Sensor Suction Temperature Thermistor...
  • Page 224: Wiring Diagrams

    2. Distributor type MULTI F DX (1 phase) 2.7 Wiring diagrams 1) Outdoor unit Models : A7UW40GFA0 [FM40AH UO2] 14 _ Heat pump 50Hz/R410A...
  • Page 225 2. Distributor type MULTI F DX (1 phase) Models :A8UW48GFA0 [FM48AH U32], A9UW56GFA0 [FM56AH U32] _ 15 Heat pump 50Hz/R410A...
  • Page 226: Capacity Tables

    2. Distributor type MULTI F DX (1 phase) 2.8 Capacity tables Models : A7UW40GFA0 [FM40AH UO2] [Cooling capacity] Indoor Air Temp.: (°CWB) Combination Outdoor 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CDB) 11.86 1.71 12.42 1.73 13.06 1.74...
  • Page 227 2. Distributor type MULTI F DX (1 phase) Indoor Air Temp.: (°CWB) Combination Outdoor 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CDB) 10.19 2.45 10.74 2.47 11.37 2.48 11.70 2.49 11.87 2.49 12.72 2.51 13.36 2.52 10.04 2.55...
  • Page 228 2. Distributor type MULTI F DX (1 phase) Indoor Air Temp.: (°CWB) Combination Outdoor 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CDB) 6.76 1.29 7.11 1.30 7.51 1.31 7.72 1.31 7.83 1.31 8.36 1.32 8.77 1.33 6.66 1.35...
  • Page 229 2. Distributor type MULTI F DX (1 phase) [Heating Capacity] Indoor Air Temp.: (°CDB) Combination Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CWB) -15.0 10.45 2.49 10.34 2.52 10.26 2.56 10.23 2.58 10.21 2.61 10.18 2.67 -13.0 10.64...
  • Page 230 2. Distributor type MULTI F DX (1 phase) Indoor Air Temp.: (°CDB) Combination Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CWB) 11.90 2.75 11.87 2.76 11.86 2.77 11.59 2.76 11.59 2.77 11.32 2.79 12.04 2.77 12.02 2.77 12.01...
  • Page 231 2. Distributor type MULTI F DX (1 phase) Indoor Air Temp.: (°CDB) Combination Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CWB) -10.0 6.31 1.52 6.31 1.55 6.31 1.57 6.38 1.59 6.38 1.61 6.39 1.64 -9.1 6.39 1.53 6.39...
  • Page 232 2. Distributor type MULTI F DX (1 phase) Models : A8UW48GFA0 [FM48AH U32] [Cooling capacity] Indoor Air Temp.: (°CWB) Combination Outdoor 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CDB) 16.42 2.42 17.19 2.44 18.08 2.46 18.55 2.47 18.79...
  • Page 233 2. Distributor type MULTI F DX (1 phase) Indoor Air Temp.: (°CWB) Combination Outdoor 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CDB) 12.47 2.81 13.14 2.83 13.91 2.85 14.31 2.85 14.52 2.86 15.55 2.88 16.34 2.89 12.29 2.92...
  • Page 234 2. Distributor type MULTI F DX (1 phase) Indoor Air Temp.: (°CWB) Combination Outdoor 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CDB) 8.02 1.40 8.43 1.40 8.90 1.41 9.15 1.42 9.28 1.42 9.91 1.43 10.39 1.44 7.90 1.46...
  • Page 235 2. Distributor type MULTI F DX (1 phase) [Heating capacity] Indoor Air Temp.: (°CDB) Combination Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CWB) -15.0 13.88 3.68 13.73 3.72 13.62 3.79 13.59 3.82 13.56 3.86 13.51 3.95 -13.0 14.13...
  • Page 236 2. Distributor type MULTI F DX (1 phase) Indoor Air Temp.: (°CDB) Combination Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CWB) 14.94 3.50 14.91 3.52 14.89 3.53 14.56 3.52 14.55 3.53 14.22 3.56 15.12 3.52 15.10 3.53 15.08...
  • Page 237 2. Distributor type MULTI F DX (1 phase) Indoor Air Temp.: (°CDB) Combination Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CWB) -10.0 8.20 2.50 8.20 2.54 8.20 2.58 8.29 2.61 8.29 2.64 8.29 2.69 -9.1 8.30 2.51 8.30...
  • Page 238 2. Distributor type MULTI F DX (1 phase) Models : A9UW56GFA0 [FM56AH U32] [Cooling capacity] Indoor Air Temp.: (°CWB) Combination Outdoor 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CDB) 17.58 2.59 18.41 2.61 19.36 2.63 19.87 2.64 20.13...
  • Page 239 2. Distributor type MULTI F DX (1 phase) Indoor Air Temp.: (°CWB) Combination Outdoor 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CDB) 13.47 3.16 14.19 3.18 15.02 3.20 15.46 3.21 15.69 3.21 16.80 3.23 17.65 3.25 13.27 3.28...
  • Page 240 2. Distributor type MULTI F DX (1 phase) Indoor Air Temp.: (°CWB) Combination Outdoor 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CDB) 9.37 1.70 9.85 1.71 10.40 1.72 10.70 1.73 10.84 1.73 11.59 1.75 12.15 1.76 9.23 1.77...
  • Page 241 2. Distributor type MULTI F DX (1 phase) [Heating Capacity] Indoor Air Temp.: (°CDB) Combination Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CWB) -15.0 15.13 3.83 14.97 3.88 14.86 3.94 14.81 3.98 14.78 4.02 14.73 4.11 -13.0 15.41...
  • Page 242 2. Distributor type MULTI F DX (1 phase) Indoor Air Temp.: (°CDB) Combination Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CWB) 15.89 3.90 15.86 3.91 15.84 3.93 15.49 3.92 15.48 3.93 15.12 3.96 16.09 3.92 16.06 3.93 16.05...
  • Page 243 2. Distributor type MULTI F DX (1 phase) Indoor Air Temp.: (°CDB) Combination Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Air Temp.: (kBtu/h(%)) (°CWB) -10.0 9.43 2.74 9.43 2.79 9.43 2.84 9.53 2.87 9.53 2.90 9.54 2.95 -9.1 9.55 2.76 9.55...
  • Page 244 2. Distributor type MULTI F DX (1 phase) 2.9 Capacity coefficient factor 1) Rate of change in capacity due to the main piping length Rate of change in cooling capacity Main piping length(m) Rate of change 100.0 98.8 97.3 95.8 94.3 92.8 91.3...
  • Page 245 2. Distributor type MULTI F DX (1 phase) 2) Rate of change in capacity due to the branch piping length 5 / 7k Btu/h 2.1 kW models 9k Btu/h 2.6 kW models Piping Rate of change in capacity Piping Rate of change in capacity length(m) length(m) Cooling(%)
  • Page 246 2. Distributor type MULTI F DX (1 phase) 3) Calculation of actual system capacity ① Outdoor unit rated capacity [from specification table] odu(rated) ② Outdoor unit capacity at Ti, To temperature. [from capacity table] odu(Ti, To) ③ Outdoor unit capacity coefficient factor (Ti, To) odu(Ti, To) odu(rated)
  • Page 247: Operation Range

    2. Distributor type MULTI F DX (1 phase) 2.10 Operation range Cooling Heating Continuous Operation Continuous Operation _ 37 Heat pump 50Hz/R410A...
  • Page 248: Electrical Characteristics

    2. Distributor type MULTI F DX (1 phase) 2.11 Electrical characteristics Unit Power Compressor Model Type Voltage Voltage range A7UW40GFA0 21.2 37.0 15.8 0.12 x 2 0.73 x 2 [FM40AH UO2] A8UW48GFA0 MIN.:198 Inverter 220-240 27.7 48.7 21.0 0.12 x 2 0.73 x 2 [FM48AH U32] MAX.:264 A9UW56GFA0...
  • Page 249: Field Wiring Diagram

    2. Distributor type MULTI F DX (1 phase) 2.12 Field wiring diagram Models : A7UW/A8UW/A9UW Power supply Outdoor unit Main switch Terminal Block outdoor Circuit breaker 1(L) 2(N) 1(L) 2(N) 3(A) 1(L) 2(N) 3(B) 1(L) 2(N) 3(C) Power cable Fuse (Including earth) Distributor box (C) 1(L) 2(N) S...
  • Page 250 2. Distributor type MULTI F DX (1 phase) 2.13 Sound levels Overall Notes: - Sound measured at 1m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operation condition - Reference accoustic pressure 0dB = 20μPa - Sound level will vary depending on a range of factors such 1.5m...
  • Page 251 Distributor type (3 phase) 1. Power supply 2. List of functions 3. Specifications 4. Combination table 5. Dimensions 6. Piping diagrams 7. Wiring diagrams 8. Capacity tables 9. Capacity coefficient factor 10. Operation range 11. Electrical characteristics 12. Field wiring diagram 13.
  • Page 252 3. Distributor type MULTI F DX (3 phase) 3.1 Power supply Type Outdoor unit Capacity [kBtu/h(kW)] Circuit breaker capacity Power supply A7UW42LFA0 [FM41AH U32] 38.2(11.2) Heat pump A8UW48LFA0 [FM49AH U32] 47.8(14.0) 380-415V, 3Ø, 50Hz A9UW56LFA0 [FM57AH U32] 52.9(15.5) External wiring procedure - The power supply work is needed only to the outdoor unit.
  • Page 253 3. Distributor type MULTI F DX (3 phase) 3.2 List of functions A7UW42LFA0 [FM41AH U32] Category Functions A8UW48LFA0 [FM49AH U32] A9UW56LFA0 [FM57AH U32] Defrost / Deicing High pressure switch Low pressure switch Phase protection Reliability Restart delay (3-minutes) Self diagnosis Soft start Test function Night Silent Operation...
  • Page 254 3. Distributor type MULTI F DX (3 phase) 3.3 Specifications A7UW42LFA0 A8UW48LFA0 Outdoor unit [FM41AH U32] [FM49AH U32] Testing Combination MS07AQ NB0 x 7EA MS07AQ NB0 x 7EA Min.∼Rated∼Max. 2.8 ~ 12.1 ~ 14.1 3.3 ~ 14.0 ~ 17.0 Cooling Min.∼Rated∼Max.
  • Page 255 3. Distributor type MULTI F DX (3 phase) A9UW56LFA0 Outdoor unit [FM57AH U32] Testing Combination MS09AQ NB0 x 7EA Min.∼Rated∼Max. 4.0 ~ 15.5 ~ 18.5 Cooling Min.∼Rated∼Max. Btu/h 13,800 ~ 52,900 ~ 63,200 Capacity Min.∼Rated∼Max. 4.5 ~ 17.4 ~ 18.8 Heating Min.∼Rated∼Max.
  • Page 256: Combination Table

    3. Distributor type MULTI F DX (3 phase) 3.4 Combination table The individual indoor unit capacity can be calculated as follows depending on the total connected capacity of all indoor units. Individual indoor unit Individual indoor unit rated capacity [Q Outdoor unit rated capacity idu(rated) combinational capacity...
  • Page 257 3. Distributor type MULTI F DX (3 phase) [Heating capacity] Heating capacity Total indoor unit Input (W) capacity Rating (kBtu/h) Rated Btu/h Btu/h Btu/h 10,752 21,633 25,188 1,066 1,162 11,760 22,407 25,913 1,116 1,258 12,768 23,182 26,637 1,166 1,354 13,440 23,956 27,362 1,013...
  • Page 258 3. Distributor type MULTI F DX (3 phase) Models : A8UW48LFA0 [FM49AH U32] [Cooling capacity] Cooling capacity Total indoor unit Input (W) capacity Rated (kBtu/h) Rated Btu/h Btu/h Btu/h 11,400 18,535 20,900 1,222 1,665 12,000 19,510 22,000 1,282 1,746 12,600 20,486 23,100 1,341...
  • Page 259 3. Distributor type MULTI F DX (3 phase) [Heating capacity] Heating capacity Total indoor unit Input (W) capacity Rating (kBtu/h) Rated Btu/h Btu/h Btu/h 12,768 23,088 27,365 1,300 1,728 2,470 13,440 24,303 28,482 1,348 1,863 2,663 14,112 25,518 29,600 1,395 1,997 2,855 14,784...
  • Page 260 3. Distributor type MULTI F DX (3 phase) Models : A9UW56LFA0 [FM57AH U32] [Cooling capacity] Cooling capacity Total indoor unit Input (W) capacity Rated (kBtu/h) Rated Btu/h Btu/h Btu/h 13,800 22,437 25,300 1,000 1,460 1,989 14,400 23,412 25,705 1,085 1,520 2,071 15,000 24,388...
  • Page 261 3. Distributor type MULTI F DX (3 phase) [Heating capacity] Heating capacity Total indoor unit Input (W) capacity Rating (kBtu/h) Rated Btu/h Btu/h Btu/h 15,456 27,948 32,138 1,490 2,267 3,240 16,023 28,973 33,407 1,579 2,402 3,433 16,590 29,998 34,676 10.2 1,626 2,473 3,535...
  • Page 262 3. Distributor type MULTI F DX (3 phase) 3.5 Dimensions 1) Outdoor units 11 _ Heat pump 50Hz/R410A...
  • Page 263: Outdoor Unit

    3. Distributor type MULTI F DX (3 phase) 3.6 Piping diagrams 1) Outdoor unit Models : A7UW42LFA0 [FM41AH U32], A8UW48LFA0 [FM49AH U32], A9UW56LFA0 [FM57AH U32] Outdoor Unit Condenser Out Inlet Air Temperature Temperature Thermistor Thermistor Condensing Temperature Thermistor Ø9.52 Flare Connection Electronic Expansion Valve...
  • Page 264 3. Distributor type MULTI F DX (3 phase) 3.7 Wiring diagrams 1) Outdoor unit Models : A7UW42LFA0 [FM41AH U32], A8UW48LFA0 [FM49AH U32], A9UW56LFA0 [FM57AH U32] 13 _ Heat pump 50Hz/R410A...
  • Page 265 3. Distributor type MULTI F DX (3 phase) 3.8 Capacity tables Models : A7UW42LFA0 [FM41AH U32] [Cooling capacity] Indoor Air Temperature (°CWB) Combination Outdoor Air 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CDB) 13.03 1.58 13.64 1.60 14.35 1.61...
  • Page 266 3. Distributor type MULTI F DX (3 phase) Indoor Air Temperature (°CWB) Combination Outdoor Air 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CDB) 10.36 1.21 10.83 1.22 11.38 1.22 11.67 1.23 11.82 1.23 12.55 1.24 13.11 1.25 10.22 1.26...
  • Page 267 3. Distributor type MULTI F DX (3 phase) Indoor Air Temperature (°CWB) Combination Outdoor Air 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CDB) 6.17 0.64 6.46 0.65 6.78 0.65 6.95 0.66 7.04 0.66 7.48 0.66 7.81 0.66 6.09 0.67...
  • Page 268 3. Distributor type MULTI F DX (3 phase) [Heating capacity] Indoor Air Temperature (°CDB) Combination Outdoor Air 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CWB) -15.0 10.70 2.39 10.58 2.42 10.51 2.46 10.48 2.49 10.45 2.51 10.42 2.57 -13.0 10.90...
  • Page 269 3. Distributor type MULTI F DX (3 phase) Indoor Air Temperature (°CDB) Combination Outdoor Air 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CWB) -15.0 8.60 1.88 8.53 1.91 8.49 1.94 8.47 1.96 8.45 1.98 8.43 2.03 -13.0 8.84 1.90 8.78...
  • Page 270 3. Distributor type MULTI F DX (3 phase) Indoor Air Temperature (°CDB) Combination Outdoor Air 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CWB) -15.0 5.50 1.11 5.49 1.13 5.49 1.16 5.49 1.17 5.49 1.18 5.49 1.22 -13.0 5.66 1.12 5.66...
  • Page 271 3. Distributor type MULTI F DX (3 phase) Models : A8UW48LFA0 [FM49AH U32] [Cooling capacity] Indoor Air Temperature (°CWB) Combination Outdoor Air 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CDB) 16.42 2.42 17.19 2.44 18.08 2.46 18.55 2.47 18.79...
  • Page 272 3. Distributor type MULTI F DX (3 phase) Indoor Air Temperature (°CWB) Combination Outdoor Air 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CDB) 12.87 1.78 13.46 1.79 14.14 1.80 14.50 1.81 14.68 1.81 15.60 1.83 16.29 1.84 12.70 1.85...
  • Page 273 3. Distributor type MULTI F DX (3 phase) Indoor Air Temperature (°CWB) Combination Outdoor Air 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CDB) 7.22 0.92 7.55 0.93 7.93 0.93 8.13 0.94 8.24 0.94 8.75 0.95 9.14 0.95 7.12 0.96...
  • Page 274 3. Distributor type MULTI F DX (3 phase) [Heating Capacity] Indoor Air Temperature (°CDB) Combination Outdoor Air 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CWB) -15.0 13.88 3.68 13.73 3.72 13.62 3.79 13.59 3.82 13.56 3.86 13.51 3.95 -13.0 14.13...
  • Page 275 3. Distributor type MULTI F DX (3 phase) Indoor Air Temperature (°CDB) Combination Outdoor Air 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CWB) -15.0 11.00 2.92 10.92 2.96 10.86 3.01 10.83 3.04 10.82 3.07 10.78 3.14 -13.0 11.31 2.95 11.23...
  • Page 276 3. Distributor type MULTI F DX (3 phase) Indoor Air Temperature (°CDB) Combination Outdoor Air 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CWB) -15.0 6.49 2.10 6.49 2.15 6.48 2.20 6.48 2.22 6.48 2.25 6.48 2.31 -13.0 6.68 2.13 6.68...
  • Page 277 3. Distributor type MULTI F DX (3 phase) Models : A9UW56LFA0 [FM57AH U32] [Cooling capacity] Indoor Air Temperature (°CWB) Combination Outdoor Air 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CDB) 17.58 2.59 18.41 2.61 19.36 2.63 19.87 2.64 20.13...
  • Page 278 3. Distributor type MULTI F DX (3 phase) Indoor Air Temperature (°CWB) Combination Outdoor Air 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CDB) 14.75 1.95 15.43 1.96 16.21 1.98 16.62 1.99 16.83 1.99 17.88 2.01 18.67 2.02 14.56 2.03...
  • Page 279 3. Distributor type MULTI F DX (3 phase) Indoor Air Temperature (°CWB) Combination Outdoor Air 14.0 16.0 18.0 19.0 19.5 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CDB) 8.37 1.06 8.75 1.07 9.20 1.08 9.43 1.08 9.55 1.09 10.14 1.09 10.59 1.10 8.26 1.11...
  • Page 280 3. Distributor type MULTI F DX (3 phase) [Heating Capacity] Indoor Air Temperature (°CDB) Combination Outdoor Air 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CWB) -15.0 15.13 3.83 14.97 3.88 14.86 3.94 14.81 3.98 14.78 4.02 14.73 4.11 -13.0 15.41...
  • Page 281 3. Distributor type MULTI F DX (3 phase) Indoor Air Temperature (°CDB) Combination Outdoor Air 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CWB) -15.0 12.47 3.33 12.38 3.38 12.31 3.44 12.28 3.47 12.26 3.51 12.23 3.59 -13.0 12.82 3.37 12.73...
  • Page 282 3. Distributor type MULTI F DX (3 phase) Indoor Air Temperature (°CDB) Combination Outdoor Air 16.0 18.0 20.0 21.0 22.0 24.0 Capacity Index Temperature (kBtu/h(%)) (°CWB) -15.0 7.41 2.35 7.40 2.40 7.40 2.46 7.40 2.49 7.40 2.52 7.40 2.58 -13.0 7.63 2.38 7.62...
  • Page 283 3. Distributor type MULTI F DX (3 phase) 3.9 Capacity coefficient factor 1) Rate of change in capacity due to the main piping length Rate of change in cooling capacity Main piping length(m) Rate of change 100.0 95.5 95.6 92.7 89.7 86.8 85.4...
  • Page 284 3. Distributor type MULTI F DX (3 phase) 2) Rate of change in capacity due to the branch piping length 5 / 7k Btu/h 2.1 kW models 9k Btu/h 2.6 kW models Piping Rate of Change in Capacity Piping Rate of Change in Capacity Length Length Cooling(%)
  • Page 285 3. Distributor type MULTI F DX (3 phase) 3) Calculation of actual system capacity ① Outdoor unit rated capacity [from specification table] odu(rated) ② Outdoor unit capacity at Ti, To temperature. [from capacity table] odu(Ti, To) ③ Outdoor unit capacity coefficient factor (Ti, To) odu(Ti, To) odu(rated)
  • Page 286 3. Distributor type MULTI F DX (3 phase) 3.10 Operation Range Cooling Heating Continuous Operation Continuous Operation 35 _ Heat pump 50Hz/R410A...
  • Page 287 3. Distributor type MULTI F DX (3 phase) 3.11 Electrical characteristics Unit Power Compressor Model Type Voltage Voltage range A7UW42LFA0 12.2 20.8 0.12 x 2 0.73 x 2 [FM41AH U32] A8UW48LFA0 MIN.:342 Inverter 380-415 12.3 21.0 0.12 x 2 0.73 x 2 [FM49AH U32] MAX.:456 A9UW56LFA0...
  • Page 288 3. Distributor type MULTI F DX (3 phase) 3.12 Field wiring diagram Models : A7UW/A8UW/A9UW Power supply Main switch Outdoor unit R S T Terminal Block outdoor Circuit breaker 1(L) 2(N) 3(A) 1(L) 2(N) 3(B) 1(L) 2(N) 3(C) Fuse Power cable (Including earth) Distributor box (C) 1(L) 2(N) S...
  • Page 289 3. Distributor type MULTI F DX (3 phase) 3.13 Sound levels Overall Notes: - Sound measured at 1m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operation condition - Reference accoustic pressure 0dB = 20μPa 1.5m - Sound level will vary depending on a range of factors such as...
  • Page 290 BD Unit (Distributor Box) 1. Specifications 2. Dimensions 3. Piping Diagrams 4. Wiring Diagrams...
  • Page 291 4. BD Unit (Distributor Box) 4.1 Specifications BD unit PMBD3620 PMBD3630 PMBD3640 Connectable indoor units Number of indoor units Capacity Btu/h 5k/7k/9k/12k/18k/24k 5k/7k/9k/12k/18k/24k 5k/7k/9k/12k/18k/24k Power source V, Ø, Hz 220-240, 1, 50 220-240, 1, 50 220-240, 1, 50 Power consumption Running current 0.05 0.05...
  • Page 292 4. BD Unit (Distributor Box) 4.2 Dimensions Models : PMBD3620, PMBD3630, PMBD3640 Ø19.05 Ø9.52 (EEV service) Suspension bolt pitch. Main Pipe (36) (56) Branch Pipe Cover Control (Controller service) (Servicing space) Min 400 Min 400 Inspection opening (Side view) (Bottom view) (Unit : mm) 2 _ Heat pump 50Hz/R410A...
  • Page 293 4. BD Unit (Distributor Box) 4.3 Piping Diagrams Refrigerant flow Cooling Heating Main gas piping (ø19.05) Outdoor unit Main liquid piping (ø9.52) D Gas(Ø9.52) EEV-A C Gas(Ø9.52) B Gas(Ø9.52) EEV-B A Gas(Ø9.52) EEV-C Indoor unit EEV-D D Liquid(Ø6.35) C Liquid(Ø6.35) B Liquid(Ø6.35) A Liquid(Ø6.35) [Unit : mm]...
  • Page 294 4. BD Unit (Distributor Box) 4.4 Wiring Diagrams Models : PMBD3620, PMBD3630, PMBD3640 CN_JIG3 CN_JIG2 LED1 LED2 LED3 LED4 PCB PARTS LAYOUT CN_JIG1 FUSE_2 FUSE_3 FUSE_4 FUSE_5 FUSE_1 CN_EEV_A CN_EEV_B CN_EEV_C CN_EEV_D CN_ROOM_A CN_ROOM_B CN_ROOM_C CN_ROOM_D CN_PWR OUTDOOR FROM OUTDOOR TO INDOOR UNIT UNIT TROUBLE DIAGNOSIS...
  • Page 295: Part 3 Design And Installation

    Part 3 Design and installation 1. General installation guideline 2. Guideline for each installation process 3. Installation of outdoor unit...
  • Page 296 1. General installation guideline 1.1 Installation process & Guideline Striking a balance between system installation & General construction work. Construction work Air conditioning work Setting sleeve and insert work details Preparation of Fitting of steel sleeves contract drawing Moulding box and reinforcement work Sleeve and insert work Removal moulding boxes...
  • Page 297: Installation Procedure

    1. General installation guideline 1.2 Checking the drawing Installation procedure Remarks Check and confirm required loads calculation, Determination of work scope model selection, drawings etc. Preparation of contract drawings Make a relationship between outdoor ,indoor controller and option connection clear. (prepare control circuit diagram) Sleeve and insert works Determine sleeve position, size and...
  • Page 298 2. Guideline for each installation process 2.1 Sleeve and insert work 2.1.1 Positioning of the pipe holes 1) The through holes for the drain piping should be positioned such that pipes have a downward gradient (the gradient must be at least 1/100.The thickness of the insulating materials must also be taken into consideration.) 2) The diameter of the through holes for the refrigerant piping should include an allowance for the thickness of the heat insu- lation materials.
  • Page 299 2. Guideline for each installation process 2.1.3 Sleeve type Sleeve Insulation Pipe NOTE Sleeve type should be considered as per local regulation & laws. CAUTION 1. In high voltage generation places, water-proof flexible conduit should be used. (in substation room, in elevator room) 2.
  • Page 300 2. Guideline for each installation process 2) Support work. Insulated U-bolt type supporting Insulated O-ring band type supporting Bolt Foam resin Bolt 1.5t plate Saddle supporting Supporting interval 1.5~2.0m CAUTION During saddle supporting work, insulation should not be pressed by saddle as this can lead to tearing of insulation and thus falling of condensed water during product operation.
  • Page 301 2. Guideline for each installation process 2.2 Refrigerant piping work 2.2.1 Principles of refrigerant piping The “ principles of refrigerant piping “ must be strictly observed. Cause of problem Action to avoid problem -Rainwater, work water, etc gets into pipes from outside Flushing Pipe covering Vacuum drying...
  • Page 302: Flaring Work

    2. Guideline for each installation process 2.2.2 Flaring work Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure. 1) Cut the pipes and the cable. Copper ① Use the piping kit accessory or the pipes purchased locally. Slanted Uneven Rough tube 90°...
  • Page 303 2. Guideline for each installation process Choice of material for refrigerant piping NOTE Copper pipe selection a. The wall thickness of the refrigerant piping should comply with relevant local and national regulation for R410A the design pressure is 3.8MPa.(38.7kgf/cm b. If not, we recommend to use with phosphorus deoxidized copper type c.
  • Page 304 2. Guideline for each installation process NOTE Flange connection and procedure 1) Cut the pipe using a pipe cutter. 7) Apply refrigerant oil on the inside and outside of the flared section. (Do not apply SUNISO oil) (Be careful to keep dust away) 2) The cut edge has burrs.
  • Page 305 2. Guideline for each installation process 2.2.3 Pipe connection flaring NOTE CAUTION 1. After installation completion make sure to open the Improper piping and flaring can lead to the leakage of valve. operating the unit with the valve shut off will refrigerant destroy the compressor (Refer to the additional refrigerant charge detail information)
  • Page 306: Brazing Work

    2. Guideline for each installation process 2.2.4 Brazing work If brazing work is carried out without passing nitrogen gas CAUTION through the pipes then it allows the formation of oxidation bubbles on the inside surface of the pipes. Brazing of refrigerant piping : These oxidation bubbles are then carried along inside the The following precaution should be taken.
  • Page 307 2. Guideline for each installation process Brazing work should be carried out either downwards or sideways. An upward direction should be avoided wherever possible(to prevent leakage). over 10mm over 10mm (Expending pipe brazing) (Pipe brazing with socket) (Flare part brazing) (Butt-brazing) Table 1: Correlation of nozzle tip and size of refrigeration piping (Unit : mm)
  • Page 308 2. Guideline for each installation process 2.2.5 Refrigerant pipe flushing Flushing is a method of cleaning extraneous matter out of pipes using pressurized gas. NOTE Refrigerant pipe flushing of 3 major effects 1. Removal of oxidation bubbles formed inside copper pipes when “nitrogen replacement is insufficient” during soldering work 2.
  • Page 309 2. Guideline for each installation process 2.3 Drain piping work The purpose of drain piping is to prevent damage of products and ceiling materials by proper draining of dew condensation which is generated from the evaporator of indoor unit when the hot vapors come in contact with the evaporator. 1) Application Pipes for draining water generated from indoor unit on cooling operation Specification for drain piping...
  • Page 310 2. Guideline for each installation process 2.3.1 Drain pipe slope and support • Slope gradient for drain should be (1/50~1/100mm) and PVC pipes should be used. • Support hanger should be at 1~1.5m interval to prevent from loosing and dropping. •...
  • Page 311 2. Guideline for each installation process 2.3.2 Drain pipe trap (only for high static duct) A 70mm B 4 x SP SP = External Pressure (mmAq) Ex) External Pressure U-Trap = 10mmAq A 50mm B 40mm Indoor unit Plug - In case of duct high static pressure, the U trap maintains a positive pressure on the indoor side of the unit.
  • Page 312 2. Guideline for each installation process 2.3.3 Grouped drain pipes It is standard work practice to make connections to the main pipe from above. The pipe down from the combination should be as large as possible. The diameter of ventilation pipe should be same or larger than drain pipe diameter. 45~60°...
  • Page 313 2. Guideline for each installation process 2.3.4 Caution for drain piping work 1) Notice on drain working ① Flexible tube should not be crooked sharply. The tube can be broken by continuous vibration for a long time. Sharp crook Sharp crook Sharp crook CAUTION Flexible tube should be connected with clamp concentrically.
  • Page 314 2. Guideline for each installation process 2) Drain pipe insulation - Drain pipe should be insulated all connected joints and ends. Insulation Insulation Loose fitting Fitting insulation not required required wrong insulation - Do not use the loose fitting insulation. 3) Drain water leakage test - Water leakage test should be performed 24 hours later after drain work finishing.
  • Page 315: Operational Steps

    2. Guideline for each installation process 2.4 Insulation work 2.4.1 Insulation 1) Operational steps EPDM length should be more Put the pipe in EPDM insulation Bond on both side of cut surfaces Dry it until it becomes thick, sticky longer than pipe length. carefully so that the pipe will not of move sure to use the correct type and does not get detached.
  • Page 316: Forming The Piping

    2. Guideline for each installation process 2.4.2 Forming the piping 1) Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tape. • If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
  • Page 317 2. Guideline for each installation process 2.4.3 Essential points of thermal insulation 1) Thermal insulation of refrigerant piping Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with enough thickness heat-resistant insulation materials, so that no gap is observed in the joint between indoor unit and insulating material, and insulating materials themselves.
  • Page 318 2. Guideline for each installation process 3) Insulation tube thickness ① Thickness decision of insulation tube • Insulation material: EPDM or polyethylene foam • Thermal conductivity 0.035 kcal~0.040kcal/mh°C • Heat resistance=100°C(Cooling only) or more 120°C(Heat pump) or over ② The thickness of the thermal insulation material must be determined in the light of the pipe sizes. Thickness of insulation material Pipe size (normal)
  • Page 319 2. Guideline for each installation process 2.5 Electrical Work Precautions CAUTION When knocking out knock holes • To punch a knock hole, hit on it with a hammer. • After knocking out the holes, we recommend you paint the edges and areas around the edges using paint to prevent rusting.
  • Page 320 2. Guideline for each installation process • Use only copper wires. • Make sure to shut down the power before starting the electric wiring work. Do not set ON any switch until the work is completed. • The outdoor unit has an inverter compresser which generates noise and charges the outer casing with the leakag current. The outdoor unit should be grounded so that the effect of the generated noise on othe equipment can be reduced, and that the outer casing can be discharged.
  • Page 321: Air Purging

    2. Guideline for each installation process 2.6. Air tight test 2.6.1 Air purging CAUTION Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. To avoid nitrogen entering the refrigerant system ① Pressure in the system rises. in a liquid state, the top of the cylinder must be higher ②...
  • Page 322 2. Guideline for each installation process 2.6.2 Essential points of testing The key to successful testing is strict adherence to the following procedure: 1) The liquid and gas piping in each refrigerant system should be pressurized in turn in accordance with the following steps. (Nitrogen gas must be used.) Step 1: increase pressure to 0.3MPa for 3 minutes or more Major leaks indicate...
  • Page 323: Checking For Leakage

    2. Guideline for each installation process 2.6.3 Checking for leakage [Check 1] (Where pressure falls while carrying out Steps 1 to 3 described on previous page) ▶ Check by measure gage..Gas detector. ▶ Check by ear..Listen for the sound of a major leakage. ▶...
  • Page 324 2. Guideline for each installation process 2.7. Vacuum drying work 2.7.1 What is Vacuum drying? Vacuum drying is : The use of a vacuum pump to vaporize(gasify) the moisture (liquid) inside the pipe and expel it leaving the pipes completely dry inside. At 1 atm(760mmHg) the boiling point (evaporating temperature) of water is 100°C but if a vacuum is created inside the pipes using a vacuum pump then the boiling point is rapidly reduced as the degree of the vacuum is increased.
  • Page 325 2. Guideline for each installation process 2.7.2 Evacuation ① Connect the manifold hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump.
  • Page 326 2. Guideline for each installation process 2.7.3 Choosing a vacuum pump The necessity for counter flow prevention After the vacuum process of the refrigerant cycle, the inside of the hose will be vacuumed after stopping the vacuum pump, the oil of vacuumpump may flow back. Moreover, if the vacuum pump stops during the operation for some reason. Therefore, in order to prevent the counter flow from the vacuum pump, a check valve is reguired.
  • Page 327: Vacuum Pump Maintenance

    2. Guideline for each installation process 2) Vacuum pump maintenance Because of their nature, most vacuum pumps contain large amounts of oil which lubricates bearings, etc., and functions to enhance airtightness of pistons. When using a vacuum pump to discharge air from refrigerant piping, moisture in the air tends to get mixed in with the oil.
  • Page 328 2. Guideline for each installation process 2.7.4 Vacuum drying procedure There are two vacuum drying methods and the appropriate one should always be chosen to confirm with individual local conditions. [Normal vacuum drying]..The standard method [Operational steps] ① Vacuum drying (1st time): Connect a manifold gauge to the service port of the liquid or gas pipe and operate the vacuum pump for at least 2 hours.
  • Page 329: Refrigerant Charging Instructions

    2. Guideline for each installation process 2.8 Additional charge of refrigerant 2.8.1 Refrigerant charging instructions ① The results of all calculations must be recorded. (make a list) ② The refrigerant will need to be additionally charged when the distance between the outdoor Unit and the most distant indoor unit is more than length (refer to section 8 outdoor unit installation condition) ③...
  • Page 330 2. Guideline for each installation process 2.9 Trial test run operation 2.9.1 Test run procedure Check the following before turning power on Wrong power wiring , loosed screws Wrong control transmission wiring , loose screws Piping size , presence of thermal insulation Use a mega-tester Measurement of main power circuit insulation Be sure to record the additional...
  • Page 331 2. Guideline for each installation process 2.9.3 Transfer to customer with explanation Operational step Make final report Explain how to Hand over Complete test run (test run operate and relevant printed inspection sheet) maintain equipment materials ① The measurements taken during the test run should be recorded and kept on a test run inspection sheet. ②...
  • Page 332 3. Installation of outdoor unit 3.1 Safety precautions Please strictly follow the instructions given in the Installation manual .Improper installation by ignoring the instructions can lead to damage to life and property. Make sure to read the following safety instructions very carefully and throughly . WARNING This symbol indicates the possibility of death or serious injury.
  • Page 333: Installation Of Outdoor Unit

    3. Installation of outdoor unit Be sure to use only those parts which are listed in the svc parts list. Never attempt to modify the equipment. • The use of inappropriate parts can cause an electrical shock, excessive heat generation or fire. Indoor/outdoor wiring connections must be secured tightly and the cable should be routed properly so that there is no force pulling the cable at the connection terminals.
  • Page 334 3. Installation of outdoor unit CAUTION Use two or more people to lift and transport the product. • Avoid personal injury. Do not install the product where it will be exposed to sea wind (salt spray) directly. • It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
  • Page 335: Note To The Installer

    3. Installation of outdoor unit 3.1.1 Points for explanation about operations The items with WARNING and CAUTION marks in the operation manual are the items pertaining to possibillties for bodily injury and material damage in addition to the general usage of the product. Accordingly, it is necessary that you make a full explanation about the described contents and also ask your customers to read the operation manual.
  • Page 336 3. Installation of outdoor unit 3.1.4 For the following items, take special care during construction and check after installation is finished 1. Items to be checked after completion of work Unit Items to be checked If not properly done, what is likely to occur Check Are the indoor and outdoor unit fixed firmly? The units may drop, vibrate or make noise.
  • Page 337: Before Installation

    3. Installation of outdoor unit 3.1.5 Before installation • During product unpacking and removing it from the packing case, be sure to lift it without exerting any pressure on other parts, especially, horizontal flaps, the refrigerant piping, drain piping, and other resin parts. •...
  • Page 338: Lifting Method

    3. Installation of outdoor unit 3.2 Introduction This installation guidance describes the procedures for outdoor unit installation, piping, wiring, and control between outdoor units, indoor units and controller. Installation of the indoor units is not described in this part. Please refer to the installation guidance manual which supplied with indoor units for their respective installation.
  • Page 339 3. Installation of outdoor unit 3.3 Foundation A2UW14GFA0 [MU2M15 UL2] A2UW16GFA0 [MU2M17 UL2] Bolt Factor M10-J type Concrete height 100mm or more Bolt inserted depth 70mm or more A3UW18GFA0 [MU3M19 UE2] A3UW21GFA0 [MU3U21 UE2] Bolt Factor M10-J type Concrete height 100mm or more...
  • Page 340 3. Installation of outdoor unit A5UW40GFA0 [MU5M40 UO2] Bolt Factor M10-J type Concrete height 200mm or more Bolt inserted depth 70mm or more A7UW40GFA0 [FM40AH UO2] A8UW48GFA0 [FM48AH U32] A9UW56GFA0 [FM56AH U32] A7UW42LFA0 [FM41AH U32] A8UW48LFA0 [FM49AH U32] A9UW56LFA0 [FM57AH U32] ...
  • Page 341 3. Installation of outdoor unit 3.4 Settlement of the outdoor unit • Anchor the outdoor unit with a bolt and nut tightly and horizontally on a concrete or rigid mount. • When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
  • Page 342 3. Installation of outdoor unit 3.5 Selection of the best location This Multi F & Multi F DX unit is suitable for installation in a residential and commercial environmental situation. If installed near a household appliance it can cause electromagnetic interference. The units should be installed in a location that meets the following requirements: ①...
  • Page 343 3. Installation of outdoor unit 3.6 Clearance space 3.6.1 Clearance around outdoor unit 300 mm or more 300 mm or more 300 mm or more 100 mm 100 mm 300 mm • Ensure that the space around the back is or more or more or more...
  • Page 344 3. Installation of outdoor unit Clearance of side discharge unit [Unit:mm(inch)] 1) Where there is an obstacle on the air intake side: n No obstacle above • Obstacle on the suction side only • Obstacle on the both sides n Obstacle above, too •...
  • Page 345: Series Installation

    3. Installation of outdoor unit 3. Installation of outdoor unit n Where the obstacles on the discharge side is lower than the unit: [Unit:mm(inch)] • No obstacle above • Obstacle above, too ʻLʼ should be lower than ʻHʼ. Close the bottom of the installation frame to prevent the discharged air from being bypassed.
  • Page 346 3. Installation of outdoor unit 3. Installation of outdoor unit 3.7 Outdoor unit piping 3.7.1 Outdoor unit piping Required tools 2) Align the center of the piping and suffi- ciently tighten the flare nut by hand. Screw Driver Drill M/C f 3.5/F14.5 Measuring Tape, Blade Core drill Spanner...
  • Page 347 3. Installation of outdoor unit 3. Installation of outdoor unit 3.8 Outdoor unit installation requirements 3.8.1 Piping elevation and length Installaton irrespective of indoor, outdoor elevation Max 15m Max 7.5m [Unit : m] Max piping length each indoor unit Standard length Model Max total [Outdoor unit]...
  • Page 348 3. Installation of outdoor unit Installation of the outdoor unit is at higher elevation than the indoor units. BD unit BD unit Main piping Branch piping [Unit : m] Standard Standard Max. Elevation Max. Main Total Branch Max. Capacity Total Main Pipe Branch Pipe Phase...
  • Page 349: Refrigerant Charge

    3. Installation of outdoor unit 3. Installation of outdoor unit 3.8.2 Refrigerant charge The calculation of the additional charge should be taken into account for the additional length of pipe. (1Ø) Additional charge (g) = ((A Room Installation Length – Standard Length (A) ) x a + (B Room Installation Length –...
  • Page 350 3. Installation of outdoor unit Additional refrigerant charge calculation example - 1 • Each branch pipe a = 5m b = 10m c = 15m d = 25m Ex) A5UW30GFA0[MU5M30 U42] ❖ Additional Charge = (5-7.5) x 20 + (10-7.5) x 20 + (15-7.5) x 20 + (25-7.5) x 20 –...
  • Page 351: Piping Connection Size

    3. Installation of outdoor unit 3.8.3 Piping connection size [Unit : mm] Liquid Ø 9.52 Adjust to indoor unit piping size Ø 19.05 BD Unit 1 BD Unit Connection Branch unit(Accessory PMBL5620) BD Unit 2 BD Units Connection BD Unit 3 BD Units Connection Branch unit...
  • Page 352 3. Installation of outdoor unit 3.9 Y-Branch and branch distributor(BD) unit 3.9.1 Branch (Accessory) Y- Branch(PMBL5620) To outdoor unit To BD unit • Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.) Facing upwards Horizontal plane Within 10°...
  • Page 353 3. Installation of outdoor unit Branch kit(PMBL1203F0) • When installing the branch pipe, direction and angle of installation is not limited. • Take care so that burrs and foreign material may not enter into the cutting surface when connecting. Thermal insulation work •...
  • Page 354: General Information

    3. Installation of outdoor unit 3.9.2 Branch distributor(Accessory) 1) General information Model name: Functional description: • Distribution of refrigerant to various indoor uits. BD unit Product • 3 types available (2, 3, 4 indoor units) PMBD3620 • Consists of EEV's inside PMBD3630 Multi FDX •...
  • Page 355 3. Installation of outdoor unit [Unit : mm] (Servicing space) Ø19.05 Min 400 Ø9.52 Min 400 (Side view) (EEV service) Suspension bolt pitch. Main Pipe (36) (56) Branch Pipe Cover Control Inspection opening (Controller service) (Bottom view) NOTE • This unit has two different installation types: (1) Ceiling-suspended type and (2) wall-mounted type.
  • Page 356 3. Installation of outdoor unit Procedure Procedure (1) Fix the furnished hanger metal with two screws.(4 loca- (1) Fix the furnished hanger metal with two screws. tions in total). (3 locations in total). (2) Using an insert-hole-in- anchor, hang the hanging bolt. (2) After checking with a level that the unit is level, fix the unit (3) Install a hexagon nut and a flat washer (locally-...
  • Page 357 3. Installation of outdoor unit ① Remove the control cover, unscrew the two screws and slide the cover in the direction of the arrow given below. ② Perform wiring with reference to the wiring diagram on a control cover of the out- door unit.
  • Page 358 3. Installation of outdoor unit a) Align the center of the pipings and sufficiently tight- [Unit : mm] en the flare nut by hand. Indoor unit side flare b) Tighten the flare nut with a wrench. CASE. 1 Ø 9.52(7k/9k/12k Btu/h) c) Wrap the insulation material around the connect- Pipes ing portion.
  • Page 359: Dip S/W Setting

    3. Installation of outdoor unit 3.10 New Functions 3.10.1 Dip S/W Setting If you set the Dip Switch when power is on, the change in setting is not applicable. The changing setting is enabled only when Power is reset. Dip Switch Function Normal Operation (No Function) Forced Cooling Operation...
  • Page 360: Forced Cooling Operation

    3. Installation of outdoor unit 14/16/18/21(1Ø) kBtu/h 40/48/56(1Ø) kBtu/h 42/48/56(3Ø) kBtu/h 3.10.2 Forced Cooling Operation Adding the refrigerant in winter. DIP-SW Setting Procedure 1. Set the Dip Switch as follow after shutting the power source down. 24/27/30(1Ø) kBtu/h 2. Reset the power. 3.
  • Page 361: Wiring Error Check

    3. Installation of outdoor unit 3.10.3 Wiring Error Check CAUTION You can check whether or not the wiring is correct. • If Indoor unit doesnʼt communicate to outdoor Unit, function could not be operated correctly. Setting Procedure • Only the wrong wiring connection is displayed. You 1.
  • Page 362 3. Installation of outdoor unit Saving Power Consumption Current level. Phase 1Ø 3Ø Model Step1(A) Step2(A) Saving Power Consumption with Mode Lock. Saving Power Consumption Saving Power Consumption (step 1) + Mode Lock (Heating) (step 1) + Mode Lock (Cooling) Saving Power Consumption Saving Power Consumption (step 2) + Mode Lock (Cooling)
  • Page 363 3. Installation of outdoor unit 3.10.6 Mode Lock Setting Procedure 1. Set the Dip Switch as follow after shutting the power source down. Only Cooling Mode Only Heating Mode 2. Reset the power. Mode Lock with Night Quiet Mode Mode Lock (Cooling) + Night Mode Lock (Cooling) + Night Quiet Mode (step 1) Quiet Mode (step 2)
  • Page 364: Operating Method

    3. Installation of outdoor unit 3.10.7 PCB Display(14/16/18/21k Model Only) It is useful to check the cycle data without LGMV. Operating Method Whenever you push the Tact Switch, the cycle information will be shown as below. h After 1page is displayed, subsequently 2page is displayed. Tact S/W Display Item...
  • Page 365 3. Installation of outdoor unit 3.11 Outdoor unit cabin 3.11.1 Outdoor cabin louver requirement 1) Outdoor cabin type : Manual door open type 2) Louver angle : less than 15° on the horizontal base Max15° 3) Louver interval: over 100mm (recommend) (Recommended) 4) Louver shape : wing type or plane type Over 100mm...
  • Page 366 3. Installation of outdoor unit 3.11.2 Air flow rate confirmation Example. 1 n Application Model : A7UW40GFA0 [FM40AH UO2] Airflow rate 90 m /min [Total opening rate] n Case : velocity of discharging air: 5m/s, velocity of suction air: 2.5m/s n Openness rate = 80% or more Effective face area(Af) Air guide duct...
  • Page 367 Part 4 Special Part 1. Installation guide at the seaside 2. Seasonal wind and cautions in winter...
  • Page 368: Seasonal Wind And Cautions In Winter

    1. Installation guide at the seaside CAUTION 1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced. 2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product.
  • Page 369 Yeouido P.O.Box 335 Seoul, 150-721, Korea. http://www.lgeaircon.com All rights reserved The air conditioners manufactured by LG have received ISO9001 certificate for Printed in Korea March / 2013 quality assurance and ISO14001 certificate for environmental management system. The specifications, designs, and information in this brochure are subject to change without notice.

Table of Contents