7
PARAMETER SETTING
7.1
Network Configuration Setting
Set the parameters of the I/O module with the network parameters written to the CPU module of the master station.
For the setting procedure for the master station, refer to the following.
User's manual for the master station used
Communication cycle interval setting
When using the I/O module in CC-Link IE TSN, set the communication cycle interval setting as follows.
■For the I/O module with the firmware version of "03" or later
Communication speed
Master station
I/O module
1Gbps
1Gbps
*2
100Mbps
100Mbps
1Gbps
*3
100Mbps
*1 Set with function setting switch 10. ( Page 120 Function setting switch setting)
*2 To use the I/O module in this combination, set the low speed in the multi-cycle settings of the master station to "x16", and set the
communication cycle setting of the I/O module to "Low-Speed".
*3 To use the I/O module in this combination, do not set the communication cycle setting of the I/O module to "Low-Speed".
■For the I/O module with the firmware version of "02"
Communication speed
Master station
I/O module
1Gbps
1Gbps
*2
100Mbps
100Mbps
1Gbps
*3
100Mbps
*1 Set with function setting switch 10. ( Page 120 Function setting switch setting)
*2 To use the I/O module in this combination, set the low speed in the multi-cycle settings of the master station to "x16", and set the
communication cycle setting of the I/O module to "Low-Speed".
*3 To use the I/O module in this combination, do not set the communication cycle setting of the I/O module to "Low-Speed".
■For the I/O module with the firmware version of "01"
Item
Communication cycle interval setting (Not set in units of 1s)
Communication cycle interval setting (Set in units of 1s)
Value that can be set
*1
• When the value is set in increments of 1s: 125.00s or more and 10000.00s or less
• When the value is not set in increments of 1s: 31.25s, 62.50s, 125.00s, 250.00s, 500.00s,
1000.00s, 2000.00s, 4000.00s, or 8000.00s
• When the value is set in increments of 1s: 125.00s or more and 625.00s or less
• When the value is not set in increments of 1s: 125.00s, 250.00s, or 500.00s
• When the value is set in increments of 1s: 125.00s or more and 10000.00s or less
• When the value is not set in increments of 1s: 31.25s, 62.50s, 125.00s, 250.00s, 500.00s,
1000.00s, 2000.00s, 4000.00s, or 8000.00s
• When the value is set in increments of 1s: 500.00s or more, 10000.00s or less, and divisible by 2s
• When the value is not set in increments of 1s: 500.00s, 1000.00s, 2000.00s, 4000.00s, or
8000.00s
Value that can be set
*1
• When the value is set in increments of 1s: 125.00s or more and 8000.00s or less
• When the value is not set in increments of 1s: 31.25s, 62.50s, 125.00s, 250.00s, 500.00s,
1000.00s, 2000.00s, 4000.00s, or 8000.00s
• When the value is set in increments of 1s: 125.00s or more and 500.00s or less
• When the value is not set in increments of 1s: 125.00s, 250.00s, or 500.00s
• When the value is set in increments of 1s: 125.00s or more and 8000.00s or less
• When the value is not set in increments of 1s: 31.25s, 62.50s, 125.00s, 250.00s, 500.00s,
1000.00s, 2000.00s, 4000.00s, or 8000.00s
• When the value is set in increments of 1s: 500.00s or more, 8000.00s or less, and divisible by 2s
• When the value is not set in increments of 1s: 500.00s, 1000.00s, 2000.00s, 4000.00s, or
8000.00s
Value that can be set
125.00s or more and 8000.00s or less
7.1 Network Configuration Setting
7 PARAMETER SETTING
151