Air-conditioners for building application inverter y-series
Hide thumbs Also See for City Multi PUHY-P72TKMU-A:
Table of Contents
Available languages

Available languages

2 In case of collective installation and continuous installation
When multiple units are installed adjacent to each other, secure enough space to allow for air circulation and passageways between groups of units as shown in the
figures.
* Leave both sides of each group of units open.
As with single installation, if the wall height exceeds the height limit, widen the space in the front and the back of a given group of units by the amount that exceeds
the limit (labeled in the figure).
If there is a wall at both the front and the rear of the unit, install up to six units (three units : P120, 144) consecutively in the side direction and provide a space of 1000
mm or more as inlet space/passage space for each six units (three units : P120, 144).
[Fig. 6.0.2]
(1) Side-by-side installation
*
30 [1-3/16]
h
Unit height
450 [17-23/32] + h
(2) Face-to-face installation
*
h
*
Unit height
450 [17-23/32]
450 [17-23/32] + h
(3) Combination of face-to-face and side-by-side installations
*
h
500
300 [11-13/16] + h
[19-11/16]
h
500 [19-11/16]
300 [11-13/16] + h
*
h
500 [19-11/16]
100 [3-15/16] + h
Unit height
450 [17-23/32]
15 [19/32] + h
h
500
[19-11/16]
1000
300
[39-3/8] + h
[11-13/16] + h
900 [35-7/16]
*
*
100
[3-15/16]
h
500 [19-11/16]
h
100 [3-15/16] + h
Unit height
*
450 [17-23/32] + h
h
450 [17-23/32]
450 [17-23/32]
h
Unit height
*
h
500
[19-11/16]
300
[11-13/16] + h
*
900 [35-7/16]
(Unit : mm [in.])