Emerson.com/Rosemount. Equipment Damage During normal operation, or in fault condition, the THUM Adapter will cause a 2.5 V drop in the connected loop. It is important to ensure that the power supply can provide at least 2.5 V more than the minimum operating voltage of the wired device to make sure it works properly with the THUM Adapter installed.
Page 3
September 2020 Quick Start Guide AMS Device Manager......................... 28 Field Communicator........................29 Perform loop current test......................30 Verify operation......................... 32 Troubleshooting........................34 Reference information....................... 35 Product Certifications.........................36 Quick Start Guide...
Page 4
Quick Start Guide September 2020 Emerson.com/Rosemount...
Figure 1-1: THUM Adapter Position Conduit entry When installing the THUM Adapter into the conduit entry of a wired device, use an approved thread sealant. Thread sealant provides a water tight seal. The thread sealant also provides lubrication to ensure easy removal of the THUM Adapter.
Page 6
25 mA. Under fault conditions, the maximum voltage drop is 2.5 V. The THUM Adapter will not affect the 4–20 mA signal under normal or fault conditions as long as the loop has at least a 2.5 V margin at the maximum loop current (25 mA for a typical 4–20 mA/HART device).
Bench top configuration When performing bench top configuration it is suggested that you connect the THUM Adapter to a wired device. If this is not possible, the following wiring diagrams can be used. For bench top configuration, ensure the power supply used is limited to 0.5 A maximum.
Quick Start Guide September 2020 Physical installation The THUM Adapter can be installed in one of two configurations: 1. Direct mount: The THUM Adapter is connected directly to the conduit entry of the wired device. 2. Remote mount: The THUM Adapter is mounted separate from the wired device housing and then connected to the wired device using conduit or other suitable means.
Install the HART device according to standard installation practices and the manufacturer’s instructions, being sure to use an approved thread sealant on all connections. Procedure 1. Attach the THUM Adapter to the wired device as shown in Figure 4-1. Figure 4-1: Direct Mount 2.
Wire running from the THUM Adapter to the wired device should be shielded or in conduit when installed in electrically noisy environments. 4. Connect the THUM Adapter to the HART wired device using the Wiring diagrams. 5. Close the housing cover on the HART wired device, so that metal touches metal, but do not overtighten to prevent damaging the unit.
F. Power supply Note In order for the THUM Adapter to function properly there must be at least 250 Ohms resistance in the loop. If the 4–20 mA loop does not have the required resistance, wire a resistor as shown in...
Page 12
4 -20 mA Loop + White 4 -20 mA Loop - Yellow + COMM To Wired Device - COMM A. THUM Adapter B. Remote mount housing C. Ground D. Shield wire E. Load resistor ≥ 250 Ω F. Power supply Emerson.com/Rosemount...
Page 13
4 -20 mA Loop + Black 4 -20 mA Loop - White Yellow - PWR/COMM + PWR/COMM A. THUM Adapter B. Wired device C. Ground D. Splice connector E. Load resistor ≥ 250 Ω F. Power supply Quick Start Guide...
Page 14
4 - 20 mA Loop + White Black 4 - 20 mA Loop - Yellow + COMM To Wired Device - COMM A. THUM Adapter B. Remote mount housing C. Ground D. Shield wire E. Load resistor ≥ 250 Ω F. Power supply Emerson.com/Rosemount...
Page 15
Figure 6-5: Direct Mount Wiring Diagram for 4-Wire Passive Device Green 4 - 20 mA Loop + 4 -20 mA Loop - Black White Yellow A. THUM Adapter B. Wired device C. Ground D. Splice connector E. Load resistor ≥ 250 Ω F. Power supply Note A passive loop exists when the wired device is not supplying power to the 4–...
Page 16
Green 4 -20 mA Loop + 4 -20 mA Loop - + COMM To Wired Device - COMM A. THUM Adapter B. Remote mount housing C. Ground D. Shield wire E. Load resistor ≥ 250 Ω F. Power supply Emerson.com/Rosemount...
Page 17
Figure 6-7: Direct Mount Wiring Diagram for 4-Wire Passive Device with Resistor Green 4 - 20 mA Loop + 4 -20 mA Loop - Black White Yellow A. THUM Adapter B. Wired device C. Ground D. Splice connector E. Load resistor ≥ 250 Ω F. Power supply Quick Start Guide...
Page 18
4 - 20 mA Loop + 4 - 20 mA Loop - + COMM To Wired Device - COMM A. THUM Adapter B. Remote mount housing C. Ground D. Shield wire E. Load resistor ≥ 250 Ω F. Power supply...
Page 19
September 2020 Quick Start Guide Figure 6-9: Direct Mount Wiring Diagram for 4-Wire Active Device Green Yellow White Black A. THUM Adapter B. Wired device C. Ground D. Splice connector E. Load resistor ≥ 250 Ω F. Input card Note An active loop exists when the wired device is supplying the power to the 4–...
Page 20
Figure 6-10: Remote Mount Wiring Diagram for 4-Wire Active Device Green + COMM To Wired Device - COMM 4-20 mA Loop + 4-20 mA Loop - A. THUM Adapter B. Remote mount housing C. Ground D. Shield wire E. Load resistor ≥ 250 Ω F. Input card Emerson.com/Rosemount...
Page 21
Quick Start Guide Figure 6-11: Direct Mount Wiring Diagram for 4-Wire Active Device with Resistor Green Yellow White Black A. THUM Adapter B. Wired device C. Ground D. Splice connector E. Load resistor ≥ 250 Ω F. Input card Quick Start Guide...
Page 22
Figure 6-12: Remote Mount Wiring Diagram for 4-Wire Active Device with Resistor COMM + COMM - 4 - 20 mA Loop + 4 - 20 mA Loop - A. THUM Adapter B. Remote mount housing C. Ground D. Shield wire E. Load resistor ≥ 250 Ω F. Input card G.
Page 23
Quick Start Guide Figure 6-13: Direct Mount Wiring Diagram for 4-Wire Active Device with No 4-20 mA Loop Green Yellow White Black A. THUM Adapter B. Wired device C. Ground D. Splice connector E. Load resistor ≥ 250 Ω Quick Start Guide...
Page 24
Figure 6-14: Remote Mount Wiring Diagram for 4-Wire Active Device with No 4–20 mA Loop Black Green White Yellow + COMM To Wired Device - COMM A. THUM Adapter B. Remote mount housing C. Ground D. Load resistor ≥ 250 Ω Emerson.com/Rosemount...
Page 25
September 2020 Quick Start Guide Figure 6-15: THUM Adapter only, Powered by a 24 V Power Supply with 1200 Ohm resistor to limit current to 20 mA Green Black White Yellow A. THUM Adapter B. Junction box C. Ground D. 250 Ω resistor E.
Page 26
Quick Start Guide September 2020 Figure 6-16: THUM Adapter only, Powered by a 24 V Power Supply with 1200 Ohm Resistor to Limit Current to 20 mA Black Green White Yellow A. THUM Adapter B. Remote mount housing C. Ground D.
If the Network ID and Join Key are not identical, the THUM Adapter will not communicate with the network. The Network ID and Join Key may be obtained from the Gateway on the Setup → Network →...
Quick Start Guide September 2020 AMS Device Manager Right click on the THUM Adapter and select Configure. When the menu opens, select Join Device to Network and follow the method to enter the Network ID and Join Key. Emerson.com/Rosemount...
September 2020 Quick Start Guide Field Communicator The Network ID and Join Key may be changed in the wireless device by using the following Fast Key sequence. Set both Network ID and Join Key. Function Fast Key seques Menu Items Wireless Setup 1, 4 Smart Power, Network ID, Set Join Key,...
Quick Start Guide September 2020 Perform loop current test To verify the THUM Adapter will work under all conditions, a loop current test should be performed. This test will exercise the loop under the highest possible voltage drop conditions. Procedure 1.
Page 31
September 2020 Quick Start Guide a) Right click on the THUM Adapter and select Configure. b) When the menu opens, select Manual Setup from the window on the left and select the Wired Device tab on the top. c) Make sure the Time drop down menu at the bottom of the page has Current selected.
11.2 Verify operation using Emerson Wireless Gateway If the THUM Adapter was configured with the Network ID and Join Key, and sufficient time has passed for network polling, the transmitter will be connected to the network. To verify device operation and connection to the network with the Gateway’s integrated web server, open the Gateway’s...
Setup → Network → Settings page on the web server. The Network ID and Join Key may be changed in the wireless device by using the following Fast Key sequence. Function Fast Key sequence Menu items Wireless Setup 1, 4 Smart Power, Network ID, Set Join Key, Radio State Emerson.com/Rosemount...
Quick Start Guide Reference information Note In order to communicate with a Field Communicator, the wired device must be powered. Table 13-1: THUM Adapter Fast Key Sequence Function Fast Key sequence Menu items Device Info 2, 2, 4, 3 Manufacturer, Model, Final Assembly...
RF spectrum. Nearly every country requires this type of product certification. Emerson is working with governmental agencies around the world to supply fully compliant products and remove the risk of violating country directives or laws governing wireless device usage.
Page 37
September 2020 Quick Start Guide 14.6 14.6.1 E5 USA Explosionproof Certificate CSA 2174201 Standards FM Class 3600 - 2011, FM Class 3615 - 2006, ANSI/UL 61010-1 Edition Markings Class I, Division 1, Groups A, B, C and D; T5, T6; Type 4X and IP66 (–50 °C≤...
Page 38
2. The Rosemount 775 enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in zone 0. 14.9.2 N7 IECEx Type n Certificate IECEx BAS 09.0058 Standards IEC 60079-0:2011, IEC 60079-15:2010; Emerson.com/Rosemount...
Page 39
September 2020 Quick Start Guide Markings Ex nA IIC T4 Gc, T4(–50 °C≤ T ≤ +70 °C) IP66 14.10 Brazil 14.10.1 I2 INMETRO Intrinsic Safety Certificate UL-BR 15.0089X Standards ABNT NBR IEC 60079-0:2013, ABNT NBR IEC 60079-11:2013 Markings Ex ia IIC T4 Ga (–50 °C≤ T ≤...
Page 42
Quick Start Guide September 2020 14.17 Declaration of Conformity Figure 14-1: Emerson THUM Wireless Adapter Declaration of Conformity Emerson.com/Rosemount...
Page 43
September 2020 Quick Start Guide Quick Start Guide...
Page 44
Quick Start Guide September 2020 Emerson.com/Rosemount...
Page 45
September 2020 Quick Start Guide 14.18 China RoHS Rosemount 775 List of Rosemount 775 Parts with China RoHS Concentration above MCVs / Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd) (Cr +6) (PBB) (PBDE) Electronics...
Page 46
Quick Start Guide September 2020 Emerson.com/Rosemount...
Page 47
September 2020 Quick Start Guide Quick Start Guide...
Page 48
The Emerson logo is a Twitter.com/Rosemount_News trademark and service mark of Emerson Electric Facebook.com/Rosemount Co. Rosemount is a mark of one of the Emerson Youtube.com/user/ family of companies. All other marks are the RosemountMeasurement property of their respective owners.