Panasonic SL-VTPR Series Instruction Manual

Flexible wire-saving link system s-link v relay output terminal

Quick Links

Flexible Wire-saving Link System S-LINK V
Relay Output Terminal
SL-VTPR□
Thank you very much for purchasing Panasonic products. Read this Instruc-
tion Manual carefully and thoroughly for the correct and optimum use of this
product. Kindly keep this manual in a convenient place for quick reference.
● Never use this product in a device for personnel protection.
● In case of using devices for personnel protection, use products which
meet laws and standards, such as OSHA, ANSI or IEC etc., for person-
nel protection applicable in each region or country.
● Before touching this product, remove any electrostatic charge that may
be present on your body. There is a danger of this product getting dam-
aged due to the electrostatic charge.
Please refer to the "S-LINK V User's Manual" for details of the entire
S-LINK V system.
1
PARTS NAMES AND FUNCTIONS
SL-VTPR4
4-core flat cable, 0.6m long
1
5
2
3
4
6
7
8
Designation
1
Address setting switches
Used for setting of the terminal address.
Used for setting of the output holding function.
Output holding function
2
ON: Hold the current output conditions (output holding).
setting switch
OFF: Will not hold the current output conditions (output OFF).
3
Power indicator (Green)
This indicator will light when the power is supplied.
Transmission indicator
This indicator will blink when the synchronization
4
(Green)
signal is sent from the S-LINK V controller.
Operation indicator
5
Lights when each output relay is turned ON.
(Orange)
6
Relay remover key
Use this key to remove the output relays.
PA-N relay APAN3124 manufactured by Panasonic
7
Output relay
Co., Ltd. (Note)
8
Terminal block
Used for connection of output devices.
Note: You can replace the output relays.
For a detailed description, refer to "
2
MOUNTING
Mounting method
1. Push the DIN rail stopper inside.
2. Fit the tab on the opposite side of the
DIN rail stopper into the 35mm width
DIN rail.
3. Press down the tab on the other side
against the 35mm width DIN rail to fit it.
Removing method
1. Insert a flathead screwdriver to the
groove on the DIN rail stopper and pull
out the stopper.
2. Push the product to the other side of
the DIN rail stopper.
3. While maintaining the condition in the
procedure 2, and lift up the product to
remove it.
Note: Take care that if the product is lifted with the stopper remained inside, the tabs crack.
INSTRUCTION MANUAL
MJE-SLVTPR No.0063-19V
SL-VTPR8
4-core flat cable, 0.6m long
1
5
2
3
4
6
7
8
Function
RELAY REPLACEMENT."
DIN rail stopper
3
2
35mm width DIN rail
Flathead screwdriver
DIN rail stopper
● In case of mounting with screws, use
M4 pan-head screws and the tighten-
ing torque should be 0.8N·m or less.
Dimensions for mounting holes
W
59.2mm
● In case of using PA-N relay (APAN3124), use this product in the ambient
temperature range of -10 to +55° and with 3A output current.
● In case of using PhotoMOS relay (AQZ20□D), the output current is
restricted depending on ambient temperature and the number of Photo-
MOS relay ON points.
Ambient temperature and number of PhotoMOS relay ON points -
Load current characteristics
● The upper limit value of the load current depends on the ambient tem-
perature and the number of PhotoMOS relay ON points.
SL-VTPR8 + AQZ202D
4.00
No. of output-ON relay pts.: 1 or 2
No. of output-ON relay pts.: 3 or 4
3.00
No. of output-ON relay pts.: 5 or 6
2.00
1.00
No. of output-ON relay pts.: 7 or 8
0
0
20
-20
Ambient
temperature (°C)
SL-VTPR8 + AQZ205D
2.00
No. of output-ON relay pts.: 1 or 2
No. of output-ON relay pts.: 3 or 4
1.50
No. of output-ON relay pts.: 5 or 6
1.00
0.50
No. of output-ON relay pts.: 7 or 8
0
0
20
-20
Ambient
temperature (°C)
3
OUTPUT CIRCUIT DIAGRAM (per channel)
+24V
D
G
0V
S-LINK V system side
● Terminal arrangement diagram
SL-VTPR4
1
DIN rail stopper
5
6
7
Terminal
No.
1
2
3
Cover
Model No.
W
SL-VTPR4
47.5mm
SL-VTPR8
78mm
SL-VTPR8 + AQZ204D
0.40
0.30
0.20
0.10
No. of output-ON relay pts.: 7 or 8
0
40
60
0
-20
Ambient
temperature (°C)
SL-VTPR8 + AQZ207D
0.80
No. of output-ON relay pts.: 1 or 2
0.60
0.40
0.20
No. of output-ON relay pts.: 7 or 8
0
40
60
0
-20
Ambient
temperature (°C)
Output relay
Output
Internal circuit
SL-VTPR8
Terminal
No.
Upper side
Lower side
DIN rail stopper
8
9
10 11 12 13 14 15 16
Terminal
No.
4
1
2
M4 pan head screw
Please arrange
separately
No. of output-ON relay pts.: 1 or 2
No. of output-ON relay pts.: 3 or 4
No. of output-ON relay pts.: 5 or 6
20
40
60
No. of output-ON relay pts.: 3 or 4
No. of output-ON relay pts.: 5 or 6
20
40
60
SL-VTPR4: Output 0 to 3
SL-VTPR8: Output 0 to 7
Output device side
Terminal
No.
Upper side
Lower side
3
4
5
6
7
8
loading

Summary of Contents for Panasonic SL-VTPR Series

  • Page 1 0.8N·m or less. Relay Output Terminal Dimensions for mounting holes SL-VTPR□ MJE-SLVTPR No.0063-19V Thank you very much for purchasing Panasonic products. Read this Instruc- Model No. 59.2mm tion Manual carefully and thoroughly for the correct and optimum use of this SL-VTPR4 47.5mm...
  • Page 2 VD1.25-3 R1.25-3 Notes: 1) This product is incorporated with the PA-N relay manufactured by Panasonic Co., • When using the above crimp terminals, the suitable wire conductor Ltd. However, when you replace the relay, you can also use the PhotoMOS relay manufactured by Panasonic Co., Ltd.

This manual is also suitable for:

Sl-vtpr4Sl-vtpr8