Trouble Judgement Criteria Of Main Parts - Mitsubishi Electric MLZ-KP09NA Service Manual

Split-type air conditioners
Hide thumbs Also See for MLZ-KP09NA:
Table of Contents
OPERATION INDICATOR
Abnormal
No.
Operation indicator lamp
point
Right lamp blink
MXZ type
Operation
1
mode
2.5-second OFF
setting
NOTE: When the indoor unit has started operation and the above failures are detected (the first detection after the power ON),
the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp blinking.

9-5. TROUBLE JUDGEMENT CRITERIA OF MAIN PARTS

MLZ-KP09NA MLZ-KP12NA MLZ-KP18NA
Part name
Room temperature
thermistor (RT11)
Indoor coil thermistor
(RT12,RT14,RT15 (MAIN),
RT13 (SUB))
Indoor fan motor
Float sensor (FS)
Drain pump (DP)
Horizontal vane
motor (MV1)
Vertical vane
motor (MV2)
OBH802A
Lit
· Blinking of OPERATION INDICATOR lamp (right-hand side lamp) indicates
abnormality.
Blinking
· OPERATION INDICATOR lamp (left-hand side lamp) is lighted.
Not lit
Symptom
Outdoor unit
operates but
indoor unit
does not
operate.
Check method and criteria
Measure the resistance with a tester.
[Part temperature 50°F - 86°F (10°C - 30°C)]
Normal
8 kΩ ~ 20 kΩ
Check 9-6.
.
Disconnect connector and check with a tester.
Check open or short according to the float position.
Float sensor
Float
position
Float
Normal
Short
Measure the resistance between the terminals with a tester.
[Part temperature 50°F - 86°F (10°C - 30°C)]
Color of the lead wire
BLUE-BLUE (Drain pump side)
RED-RED (Control P.C. board side)
Measure the resistance between the terminals with a tester.
[Part temperature 68°F - 86°F (20°C - 30°C)]
Color of the lead wire
Each phase 300Ω
RED-YLW
Measure the resistance between the terminals with a tester.
[Part temperature 68°F - 86°F (20°C - 30°C)]
Color of the lead wire
Each phase 300Ω
RED-YLW
sandium.com
Condition
When the operation mode of the each indoor
unit is differently set to COOL (includes DRY)
and HEAT at the same time, the operation
mode of the indoor unit that has operated at
first has the priority.
Float sensor
Float
Open
Normal
520Ω ~ 620Ω
Normal
Normal
27
Remedy
• Unify the operation mode.
Refer to outdoor unit
service manual.
Figure
YLW
ROTOR
YLW
RED
YLW
YLW