Hitachi S10mini User Manual page 140

Option
Hide thumbs Also See for S10mini:
Table of Contents
5 USER GUIDE
Transparent message reception request (Hitachi's unique transparent type of support):
toukaread( )
[Linking procedure]
Struct ToukaRead_p {
long node ;
unsigned short *Erradr ;
unsigned char *dataadr ;
unsigned long datasiz ;
} ;
long (*ToukaRead)( ) ;
long rtn ;
struct ToukaRead_p *padr ;
ToukaRead = (long(*)( ))0xD60160 ;/* S10V */
rtn = (*ToukaRead)(padr) ;
Note: For the S10mini, substitute 0xD74178, 0xDF4178 for 0xD60160, 0xDE0160.
[Parameters for mathematical/logical function]
[Parameters]
padr
Struct ToukaRead_p {
unsigned short *Erradr ;
unsigned char *dataadr ;
unsigned long datasiz ;
} ;
Be sure to specify an even-numbered address in padr.
Main
+0x0000
Message transmission service number (17)
+0x0004
Reception destination node number (0 to 254)
+0x0008
Error code storage address
+0x000C
Reception data storage address
+0x0010
Data word count (0 to 1024)
long node ;
C language
Struct ToukaRead_p {
unsigned short *Erradr ;
unsigned char *dataadr ;
unsigned long datasiz ;
} ;
long (*ToukaRead)( ) ;
long rtn ;
struct ToukaRead_p *padr ;
ToukaRead = (long(*)( ))0xDE0160 ;/* S10V*/
rtn = (*ToukaRead)(padr) ;
: Input parameter storage starting address
: Reception destination node number (0 to 254)
: Error code storage address
: Reception data storage address
: Data word count (0 to 1024)
5-88
Sub
long node ;