CALEFFI GEO 110 Series Installation And Commissioning Manual

Distribution manifold for geothermal systems

Quick Links

www.caleffi.com
Distribution manifold for geothermal systems
© Copyright 2011 Calef fi
INSTALLATION AND COMMISSIONING MANUAL
Function
The CALEFFI GEO
®
110 series manifolds are used for the
control and distribution of medium in closed circuit
geothermal plants.
In circuits with geothermal heat pump the thermal medium
is generally a mixture of water and anti-freeze fluid since
the temperatures can be extremely low. The components
are made with high-performance materials for this type of
application.
They are supplied pre-assembled, complete with end
fittings and temperature gauges, or in ready-to-assemble
modules.
CONTENTS
shut-off and regulating valves
with Vortex effect - 111 series
Accessories
1
88156.01
110 series
2
3
4
5
6
7
8-9
10
11
12
13
14
15-16
Table of Contents
loading

Summary of Contents for CALEFFI GEO 110 Series

  • Page 1: Table Of Contents

    Branch circuits connection Closing and opening shut-off and regulating valves Left-side version installation Modular manifold Function The CALEFFI GEO ® 110 series manifolds are used for the Filling the circuit control and distribution of medium in closed circuit geothermal plants.
  • Page 2: Warnings

    WARNINGS These instructions must be read and understood before installing and maintaining the device. CAUTION! FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN A SAFETY HAZARD! CAUTION! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN INJURY THE PRODUCT SUPPLIED WITH THIS INSTRUCTION SHEET IS REFERRED TO BELOW AS ‘DEVICE’...
  • Page 3: Characteristic Components

    Characteristic components Pre-assembled unit complete with: 1) Polymer manifold complete with sealing gasket 2) Brass end fitting 3) Air vent 4) Temperature gauge with pocket 5) Fill/drain cock 6) Closure plate 7) Pair of stainless steel brackets 8) Stainless steel rods including screws and bolts for seal and clamping Package content The package contains: - modules for flow and return manifold...
  • Page 4: Pre-Assembled Manifold

    PRE-ASSEMBLED MANIFOLD 3) Close the insulation and fit the air vent in the upper connection. The pre-assembled manifold is supplied in the right-side version but can be fitted with the main connections on the left side depending on the heat pump position compared to the probes. right-side version Mounting brackets - manifold 1) Hand thread the furnished screws several turns into the rear...
  • Page 5: Shut-Off Valves Installation

    4) Position the manifold and mark the wall anchor holes on the wall. Shut-off valves installation Install the wall anchors and attach the brackets to the wall using the mounting slots. If more convenient, the brackets can be 1) Uncouple the return manifold (the one with medium flowing from installed on the wall first, then connect the manifold to the the heat pump to the geothermal probes) and connect the brackets.
  • Page 6: Branch Circuits Connection

    3) In all three situations, simply position the seal and fully tighten Pipe connection the nut on the manifold outlet. Loosen the locking Insert the pipe to the Snugly tighten the nut of the DECA end stop locking nut fitting without taking it Branch circuits connection Do not disassemble the fitting 1) With the manifold mounted on the brackets, prepare the pipe for...
  • Page 7: Closing And Opening

    5) Connect main pipes. Closing and opening shut-off valves It is advisable to insert a ball valve between the manifold and the main pipe so that the geothermal circuits can be excluded The control lever opens easily. and closes the ball valve.
  • Page 8: Left-Side Version Installation

    Left-side version installation 7) Install the drain fully into the lower connection and the pocket for the temperature gauge into the front connection. The standard right-side version of the manifold can be installed in the left-side version by proceeding as follows: 1) Remove the insulation from the manifold.
  • Page 9: Modular Manifold

    MODULAR MANIFOLD 5) To tighten the nuts follow the adjustment diagram shown The distribution manifold has been designed so that it is easy to opposite with the following mount on a bench. procedure: Since the manifold is reversible, it can be mounted with the main - tighten with torque wrench connections on the right or left depending on the heat pump to 5 N·m.
  • Page 10: Filling The Circuit

    Filling the circuits 3) Connect the system testing pump to the fill cock on the flow manifold and a drain pipe to the cock on the return manifold. 1) Close all the outlets to the geothermal circuits using the shut-off Direct the drain pipe into a container if the medium in the and regulating valves.
  • Page 11: Hydraulic Test

    Hydraulic test Commissioning and circuit balancing 1) When all circuits have been filled the system seal test can be 1) Open all the circuit shut-off valves and the ball valves on the carried out. main pipes, if any. 2) Disconnect the drain pipe and close the corresponding drain cock.
  • Page 12: Shut-Off Valve Fitted For Flow Rate Measuring Sensor

    Shut-off valve fitted for flow rate measuring sensor with 9) Open the ball using the specific knob. These operations must Vortex effect – 111 series also be repeated carefully when replacing the sensor with the closure cap after the balancing operations are complete. Correct installation of the sensor For balancing remove the knob and insert the plug of the flow The sensor is positioned in place of the end cap of the shut-off valve...
  • Page 13: Balancing Valve 112 Series

    After balancing, disconnect the electronic meter and put the Balancing valve – 112 series shut-off valves back into their standard operating condition as Flow rate regulation is carried out as follows: follows: 10) Close the valve using the specific knob and take out the sensor 1) With the aid of the indicator 2) Use the ring (2) to open the by removing the ring stop and the seal ring.
  • Page 14: Float Flow Meter 113 Series

    Float flow meter – 113 series Installation in external pocket 1) Adjust the flow rate by 2) The flow rate can be read The manifold, if coupled with the 111 series shut-off valve or 112 series using a 9 mm fixed hex on the graduated scale in balancing valve, can also be installed in external pocket in the spanner on the ball valve.
  • Page 15 Accessories Float flow meter. Direct reading of flow rate. Ball valve for flow rate adjustment. Ball shut-off valve fitted for integrated flow rate measuring sensor. Brass body. Brass body. Polymer top cap. Female connections with captive nut. Complete with fitting for polyethylene pipe. Female connections with captive nut.
  • Page 16 Instrument and accessories holder for heat pumps Box for coupling with instrument holder anchoring complete with steel anchoring base. base 115 series. Made of painted steel. Connections: 1 1/4” F. Composed of outer casing and door. Max. working pressure: 2,5 bar. Working temperature range: -20–90°C (temperature gauges 50°C).