YOKOGAWA YFGW520 User Manual

Field wireless access point
Hide thumbs Also See for YFGW520:

Quick Links

User's
Manual
This document specifies the important information to use this product correctly and
safely and the License Agreement of Attached Software for YFGW520 Field Wireless Ac-
cess Point.
Before use the product, be sure to read this document first.
The configuration of the field wireless system is described in User's Manual of the
YFGW410 Field Wireless Management Station (IM 01W02D01-01EN). Read that document
first.
Contents
Introduction ...................................................................................................2
Safety Precautions .......................................................................................3
Explosion Protected Type Specifications ...............................................11
FM Approval (United States) ............................................................... 14
FM Approval (Canada) ......................................................................... 17
ATEX ...................................................................................................... 21
IECEx ..................................................................................................... 28
Ground Cable Connection .................................................................. 36
How to Use Online Manual ....................................................................... 37
Preparation to Use YFGW520 Attached Software ................................. 37
Copyright and Trademark Notices .......................................................... 38
Patent Notice ............................................................................................. 38
Open Source Software ............................................................................. 39
About User's Manual ................................................................................ 39
Information of User's Manual Revision .................................................. 40
Software License Agreement ................................................................... 41
YFGW520
Field Wireless Access Point
Read Me First
IM 01W02E02-11EN
IM 01W02E02-11EN
3rd Edition
Table of Contents
loading

Summary of Contents for YOKOGAWA YFGW520

  • Page 1: Table Of Contents

    IM 01W02E02-11EN This document specifies the important information to use this product correctly and safely and the License Agreement of Attached Software for YFGW520 Field Wireless Ac- cess Point. Before use the product, be sure to read this document first.
  • Page 2: Introduction

    This manual (IM 01W02E02-11EN) describes the safety precautions, explosion protected type specifications and the license agreement of attached software for the YFGW520. There are three documents including this one for the YFGW520 listed below. Read them along with this manual.
  • Page 3: Safety Precautions

    If any protection or safety circuit is required for the system controlled by the product or for the product itself, prepares it separately. Be sure to use the spare parts approved by Yokogawa Electric Corporation (hereafter simply referred to as Yokogawa) when replacing parts or consumables.
  • Page 4 If these instructions are not heeded, the protection provided by this instrument may be impaired. In this case, Yokogawa cannot guarantee that the instrument can be safely operated. Please pay special attention to the...
  • Page 5 If you need to repair or modification, please contact the nearest Yokogawa office. (f) Modification • Yokogawa will not be liable for malfunctions or damage resulting from any modificationmade to this instrument by the customer. (g) Product Disposal •...
  • Page 6 Yokogawa shall have neither liability nor responsibility to any person or entity with respect to any direct or indirect loss or damage arising from using the product or any defect of the product that Yokogawa can not predict in advance.
  • Page 7 (interface) are provided. (3) Laser Safety 100BASE-FX (Single mode Fiber) model of YFGW520 is compliant with IEC 825-1 Class 1 and CDRH 21-CFR 1040 Class 1 eye safety requirements. CAUTION •...
  • Page 8 Spectrum Conformity Standard EN 300 328 FCC compliance FCC ID: SGJ-WFC015 FCC Approval (Part 15C) This device complies with part 15 of the FCC Rules. Operation is subject to the following two con- ditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
  • Page 9 RRA compliance This product complies with the Radio Waves Act (Republic of Korea). Registration No: R-R-YHQ-WRA011, R-C-YHQ-WRA013 Equipment Name: Field Wireless Access Point Model name: YFGW520 Trade Name: Yokogawa Electric Corp. Manufacturer: Yokogawa Electric Corp. Country of Origin: Japan IM 01W02E02-11EN...
  • Page 10 (Cd) (Cr(VI)) (PBB) (PBDE) 壳体 × ○ ○ ○ ○ ○ 基板组件 × ○ ○ ○ ○ ○ YFGW520 现场无线接入点 电源连接线 × ○ ○ ○ ○ ○ 天线组件 × ○ ○ ○ ○ ○ ○ :表示该部件的所有均质材料中的有害物质的含量均在GB/T26572 标准中所规定的限量以下。 × :表示至少该部件的某些均质材料中的有害物质的含量均在GB/T26572 标准中所规定的限量以上。...
  • Page 11: Explosion Protected Type Specifications

    Explosion Protected Type Specifications Optional Specifications (For Explosion Protected Type) Item Description Code Factory United FM Nonincendive Approval (United States) Mutual States Certificate: FM17US0294X (FM) * Applicable standard: FM Class 3600:2018, FM Class 3611:2018, FM Class 3810:2018, NEMA 250:2014 FN17 Nonincendive for Class I, Division 2, Groups A, B, C and D.
  • Page 12: Installation Of An Explosion Protected Instrument

    If a customer makes a repair or modification to an explosion protected instrument and the instrument is not restored to its original condition, its explosion protected construction may be compromised and the instrument may be hazardous to operate. Please contact Yokogawa before making any repair or modification to an instrument.
  • Page 13 NOTE • YFGW520 should be installed in upright position. • YFGW520 does not have a power switch inside. Prepare a dedicated breaker for the external power line to turn ON/OFF the device. • Make sure that the breakers are installed in the power supply circuits located in non- hazardous areas so that the power can be shutoff when abnormality occurs.
  • Page 14: Fm Approval (United States)

    Caution for FM Nonincendive Approval (United States). (1) Technical Data Note 1. Model YFGW520 Field Wireless Access Point with optional code FN17 is applica- ble for use in hazardous (classified) locations. • Applicable standards: FM Class 3600:2018, FM Class 3611:2018, FM Class 3810:2018, NEMA 250:2014 •...
  • Page 15 (5) Control Drawing F03.ai IM 01W02E02-11EN...
  • Page 16 F04.ai NOTE The equipment must be installed in accordance with the user’s manual. IM 01W02E02-11EN...
  • Page 17: Fm Approval (Canada)

    The equipment shall not be operated outside the range. • Power dissipation: ≤ 3.5 W • RF Power: ≤ 60 mW (2) Electrical Connection The type of electrical connection depends on the marking below on YFGW520. Marking The type of electrical connection Note M20 (ISO) M20 X 1.5...
  • Page 18 The maintenance of the equipment must be in accordance with the user’s manual. When opening the cover, the enclosure should be dry and clean to prevent the ingress of water and dust. WARNING • Only personnel authorized by Yokogawa Electric Corporation can repair the equipment. IM 01W02E02-11EN...
  • Page 19 (5) Control Drawing F06.ai IM 01W02E02-11EN...
  • Page 20 F07.ai NOTE The equipment must be installed in accordance with the user’s manual. IM 01W02E02-11EN...
  • Page 21: Atex

    (1) Technical Data a. Caution for ATEX Type n declaration Note 1. Model YFGW520 Field Wireless Access Point with optional code /KN27 is applicable for use in hazardous area. • Applicable standard: EN 60079-0: 2012+A11:2013, EN 60079-11: 2012, EN 60079-15: 2010 •...
  • Page 22 Note 4. Installation Hazardous Hazardous Nonhazardous Location Location Location Zone 2 Electrical Equipment YFGW520 (e.g.) “d”,”i”,”Type n” equipment Field Wireless Access Point Radio wave (IEEE802.15.4) Control Equipment1 metal wiring optical fiber Power Supply wiring F08.ai *1:These apparatus are simple apparatus.
  • Page 23 Caution for ATEX Flameproof Certification Note 1. Model YFGW520 Field Wireless Access Point with optional code KF27 is applicable for use in hazardous locations. • Certification: DEKRA 15ATEX0042 X •...
  • Page 24 • WHEN THE AMBIENT TEMPERATURE IS ≥ 60°C, USE HEAT-RESISTING CABLES AND CABLE GLANDS WITH RATED TEMPERATURES OF ≥ 80°C. Note 4. Installation Hazardous Hazardous Nonhazardous Location Location Location Zone 1 Electrical Equipment YFGW520 Field Wireless Access Point Radio wave (IEEE802.15.4) Control Equipment metal wiring optical fiber 100BASE-TX/ 100BASE-FX Power...
  • Page 25 NOTE • The equipment must be installed in accordance with EN 60079-14 and relevant local codes. • The equipment must be installed in accordance with the user’s manual. • Electrostatic charges on the non-metallic parts (excluding glass parts) or coated parts of the Field Wireless Access Point must be avoided.
  • Page 26 (2) Electrical Connection • The type of electrical connection depends on the marking below on YFGW520. Marking The type of electrical connection Note M20 (ISO) M20 X 1.5 A or N ANSI 1/2 NPT 1/2-14 NPT This marking is incused at the back side of the electrical connection block.
  • Page 27 Style code. SUPPLY: Specified supply voltage and wattage. NO.: Serial number and year of production YOKOGAWA TOKYO 180-8750 JAPAN: The manufacturer name and the address Production year and month are shown as yyyy.mm. For example, 2013.01 denotes January 2013. “180-8750” is a zip code which represents the following address.
  • Page 28: Iecex

    IECEx (1) Technical Data a. Caution for IECEx Type n Certification Note 1. Model YFGW520 Field Wireless Access Point with optional code SN27 is applicable for use in hazardous area. • No. IECEx DEK 14.0028X • Applicable standards: IEC 60079-0:2011, IEC 60079-11:2011, IEC 60079-15:2010 •...
  • Page 29 Note 4. Installation Hazardous Hazardous Nonhazardous Location Location Location Zone 2 Electrical Equipment YFGW520 (e.g.) “d”,”i”,”Type n” equipment Field Wireless Access Point Radio wave (IEEE802.15.4) Control Equipment1 metal wiring optical fiber Power Supply wiring F14.ai *1:These apparatus are simple apparatus.
  • Page 30 NOTE • The equipment must be installed in accordance with IEC 60079-14 and relevant local codes. • The equipment must be installed in accordance with the user’s manual. • Electrostatic charges on the non-metallic parts (excluding glass parts) or coated parts of the Field Wireless Access Point must be avoided.
  • Page 31 b. Caution for IECEx Flameproof Certification Note 1. Model YFGW520 Field Wireless Access Point with optional code SF27 is applicable for use in hazardous locations. • Certification: IECEx DEK 15.0021X • Applicable Standards: IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-11:2011 •...
  • Page 32 Note 4. Warning Hazardous Hazardous Nonhazardous Location Location Location Zone 1 Electrical Equipment YFGW520 Field Wireless Access Point Radio wave (IEEE802.15.4) Control Equipment metal wiring optical fiber 100BASE-TX/ 100BASE-FX Power Supply Wiring F15.ai *1: These apparatus are simple apparatus.
  • Page 33 NOTE • The equipment must be installed in accordance with IEC 60079-14 and relevant local codes. • The equipment must be installed in accordance with the user’s manual. • Electrostatic charges on the non-metallic parts (excluding glass parts) or coated parts of the Field Wireless Access Point must be avoided.
  • Page 34 (2) Electrical Connection • The type of electrical connection depends on the marking below on YFGW520. Marking The type of electrical connection Note M20 (ISO) M20 X 1.5 A or N ANSI 1/2 NPT 1/2-14 NPT This marking is incused at the back side of the electrical connection block.
  • Page 35 Style code. SUPPLY: Specified supply voltage and wattage. NO.: Serial number and year of production YOKOGAWA TOKYO 180-8750 JAPAN: The manufacturer name and the address Production year and month are shown as yyyy.mm. For example, 2015.01 denotes January 2015. “180-8750” is a zip code which represents the following address.
  • Page 36: Ground Cable Connection

    For details of the connection, see C5.1 Power Supply Cable Connection of IM 01W02E02-01EN. 2) External grounding terminal To connect the grounding cable to YFGW520 directly, use the ground terminal on the right side of the housing. For details of the connection, see C5.2 Grounding Cable Connection of IM 01W02E02-01EN.
  • Page 37: How To Use Online Manual

    How to Use Online Manual It is necessary to install Adobe Acrobat Reader to read the instruction manual (YFGW520 Field Wireless Access Point: IM 01W02E02-01EN). Install the following Adobe Reader by the administrator authority. • Adobe Reader 9.3 or later Adobe Reader can be downloaded from the Web site of Adobe Systems Incorporated.
  • Page 38: Copyright And Trademark Notices

    PC network or the like), or registered or recorded on video tapes or other media. Trademark Acknowledgments • FieldMate is a trademark or registered trademark of Yokogawa. • Microsoft, Windows, and Microsoft .NET Framework are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries.
  • Page 39: Open Source Software

    The following printed user’s manual is attached to YFGW520 hardware. • IM 01W02E02-11EN: YFGW520 Field Wireless Access Point Read Me First The following online user’s manual is stored in the attached DVD-ROM for YFGW520. • IM 01W02E02-01EN: YFGW520 Field Wireless Access Point...
  • Page 40: Information Of User's Manual Revision

    Information of User’s Manual Revision Material Name: YFGW520 Field Wireless Access Point Read Me First Material Number: IM 01W02E02-11EN Edition Date Page Revised Item 1st Edition March 2018 New Issue 2nd Edition Aug. 2018 ― Add FCC and ISED compliance ―...
  • Page 41: Field Wireless Access Point Setup Tool Software License Agreement

    Licensee a non-exclusive and non-transferable right to use the Software Product on the hardware specified by Yokogawa or if not specified, on a single hardware and solely for your Licensee’s internal operation use, in consideration of full payment by Licensee of the license fee separately agreed upon.
  • Page 42 Software Product are the intellectual property or trade secret of Yokogawa or any of its licensors. Copyright, trademark and any other intellectual property rights in and ownership of the Software Product shall be retained by Yokogawa or any of its licensors and none of the rights will be transferred to Licensee hereunder.
  • Page 43 4.4 The above warranties shall not be applied to and Yokogawa shall not be liable for the defect or noncompliance which is subject to any of the following circumstances: a) the hardware on which the Software Product is installed has ceased to be covered by the warranty or maintenance contract of the hardware supplier;...
  • Page 44 Yokogawa, except those carried out on the express instruction of Yokogawa, or f) any other causes not attributable to Yokogawa. 6.5 This section states the entire liability of Yokogawa and its suppliers and the sole remedy of Licensee with respect to any claim of infringement of third party’s intellectual property rights.
  • Page 45 11. Termination Yokogawa shall have the right to terminate this Agreement with immediate effect upon notice to Licensee, if Licensee or end users breach any of the terms and conditions hereof. Upon termination of this Agreement, Licensee shall, and make end users, promptly cease using the Software Product and, in accordance with sub-clause 2.5, return or irretrievably delete all...

This manual is also suitable for:

Wfc015