  • Page 1 UPS5000 Optional BSC Card User Manual Issue Date 2019-12-10 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    User Manual About This Document About This Document Purpose This document describes the optional BSC card for the UPS5000 in terms of its performance specifications, appearance, structure, installation, and operation and maintenance (O&M). Intended Audience This document is intended for: ...
  • Page 4 Changes between document issues are cumulative. The latest document issue contains all the changes made in earlier issues. Issue 02 (2019-12-10) Updated the sampling cable description. Issue 01 (2017-12-04) This issue is the first official release. Issue 02 (2019-12-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 5: Table Of Contents

    4 Setting BSC Card Parameters ....................5 5 Parts Replacement ........................6 5.1 Replacing a Fuse ..............................6 5.2 Replacing an Optional BSC Card ........................... 7 6 Alarm References ........................8 A Acronyms and Abbreviations ....................9 Issue 02 (2019-12-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 6: Safety Precautions

    UPS5000 Optional BSC Card User Manual 1 Safety Precautions Safety Precautions  Only professional technical personnel designated by Huawei are allowed to install and operate the product.  High voltage operations and installation of AC-powered facilities must be performed by qualified personnel.
  • Page 7: Optional Bsc Card

    An optional BSC card enables Huawei's UPS and other vendor's UPS to form a dual-bus system. With the optional BSC card, Huawei UPS can function as a slave device to trace the output phases of other vendor's UPS or the phases of other 80–280 V AC power supplies in real time.
  • Page 8: Installing An Optional Bsc Card

    The customer can also purchase and install these components by themselves. Procedure Step 1 Connect the ground cable for the ESD wrist strap, and put on the ESD wrist strap and ESD gloves. Issue 02 (2019-12-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 9 3 Installing an Optional BSC Card Step 2 Insert the optional BSC card into the control module in Huawei's UPS and secure the card. The optional BSC card must be installed in the control module that contains a monitoring interface card.
  • Page 10: Setting Bsc Card Parameters

    4 Setting BSC Card Parameters Setting BSC Card Parameters Procedure Step 1 Log in to Huawei's UPS LCD. The initial passwords for admin and operator are both 000001. This document corresponds to the monitor display module (MDU) version V126B083D00 and is for reference only.
  • Page 11: Parts Replacement

    Material: fuse Context During fuse replacement, a BSC signal abnormal alarm will be triggered. There is no need to clear this alarm. Procedure Step 1 Open the cover and remove the fuse. Issue 02 (2019-12-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 12: Replacing An Optional Bsc Card

    Step 3 Install a new BSC card. Step 4 Connect the sampling cable and signal cables based on the recorded information. Step 5 Verify that the POWER indicator on the BSC card is on. ----End Issue 02 (2019-12-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 13: Alarm References

    2. Check whether the rack BSC synchronization cable is loose. 3. Replace the inter-rack BSC synchronization cable. 4. Check whether the inter-rack parallel cable is loose. 5. Replace the inter-rack parallel cable. Issue 02 (2019-12-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 14: A Acronyms And Abbreviations

    UPS5000 Optional BSC Card User Manual A Acronyms and Abbreviations Acronyms and Abbreviations Bus Sync Controller uninterruptible power system Issue 02 (2019-12-10) Copyright © Huawei Technologies Co., Ltd.