SIMATIC ET 200S distributed I/O 2 AI I 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0)
SIMATIC
ET 200S distributed I/O
2 AI I 2/4WIRE HF analog electronic
module (6ES7134-4MB02-0AB0)
Manual
04/2007
A5E01076111-01
Preface
______________
Properties
______________
Parameters
______________
Diagnostics
______________
Analog value representation
______________
Connecting
1
2
3
4
5
Table of Contents
loading

Summary of Contents for Siemens 2AI 2/4WIRE HF

  • Page 1 Preface SIMATIC ET 200S distributed I/O 2 AI I 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0) ______________ Properties ______________ Parameters SIMATIC ______________ Diagnostics ET 200S distributed I/O 2 AI I 2/4WIRE HF analog electronic ______________ Analog value representation module (6ES7134-4MB02-0AB0) ______________ Connecting Manual 04/2007...
  • Page 2 Trademarks All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
  • Page 3: Preface

    Additional support If you have any questions relating to the products described in these operating instructions, and do not find the answers in this document, please contact your local Siemens representative. http://www.siemens.com/automation/partner...
  • Page 4 Please contact your regional training center or the central training center in D - 90327, Nuremberg, Germany. Phone: +49 (911) 895-3200. http://www.siemens.com/sitrain Technical Support You can reach technical support for all A&D projects ● using the support request web form: http://www.siemens.com/automation/support-request...
  • Page 5: Table Of Contents

    Table of contents Preface ..............................3 Properties ..............................7 2AI 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0) ..........7 Parameters .............................. 13 Parameters...........................13 Parameter description........................14 Diagnostics .............................. 15 Diagnostics using LED display.....................15 Error types............................16 Analog value representation ........................17 Introduction ..........................17 Analog value representation for measuring range with SIMATIC S7 ..........17 Measuring ranges ........................18...
  • Page 6 Table of contents 2 AI I 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0) Manual, 04/2007, A5E01076111-01...
  • Page 7: Properties

    Properties 2AI 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0) Properties ● 2 inputs for measuring current ● Input ranges: – ± 20 mA, resolution 15 bits + sign – 4 mA to 20 mA, resolution 15 bits ● Isolated from the load voltage L+ ●...
  • Page 8 Properties 1.1 2AI 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0) Terminal assignment for the 2 AI I 2/4WIRE HF (6ES7134-4MB02-0AB0) Terminal Assignment Terminal Assignment Notes for 2-wire transducer: : Input signal "-", Channel n • : Connect to L- • L+: Input signal "+", Channel n •...
  • Page 9 Properties 1.1 2AI 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0) Block diagram Figure 1-1 Block diagram of the 2AI I 2/4WIRE HF 2 AI I 2/4WIRE HF (6ES7134-4MB02-0AB0) technical data Dimensions and weight Width (mm) Weight Approx. 45 g Module-specific data Supports isochronous operation Supports I&M functions...
  • Page 10 Properties 1.1 2AI 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0) Permissible potential difference Between channels (U • 140 VDC/100 VAC (with isolated power supply for the measuring transducer) Between M and the central grounding point • 75 V DC/60 V AC Insulation tested •...
  • Page 11 Properties 1.1 2AI 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0) Data for selecting a sensor Input range (rated value)/input resistance Current • Approx. 44 Ω Permitted input current (destruction limit) Approx. 50 mA (can be limited electronically) Load of the two-wire transmitter: Max.
  • Page 12 Properties 1.1 2AI 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0) 2 AI I 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0) Manual, 04/2007, A5E01076111-01...
  • Page 13: Parameters

    Parameters Parameters Table 2-1 Parameters for analog input module 2AI I 2/4WIRE HF Range of values Default setting Applicability Disable Group diagnostics (parameter assignment error, • Disable Module internal error) Enable • Disable Diagnostics: Overflow/underflow • Disable Module Enable • Disable Diagnostics: Wire break Disable...
  • Page 14: Parameter Description

    Parameters 2.2 Parameter description Parameter description Smoothing The individual measured values are smoothed by digital filtering. The smoothing can be adjusted in four steps, in which the smoothing factor k multiplied with cycle time of the electronic module equals the time constant of the smoothing filter. The greater the smoothing, the greater the time constant of the filter.
  • Page 15: Diagnostics

    Diagnostics Diagnostics using LED display LED display ① Batch error (red) Status and error displays Event (LED) Cause Remedy No configuration or incorrect Check the parameter module plugged in. No load assignment. Check the load voltage.present There is a voltage. Evaluate the diagnostic message.
  • Page 16: Error Types

    Diagnostics 3.2 Error types Error types Analog input module error types Table 3-1 Error types Error type Meaning Remedy 10000: Parameter Module cannot use the Correct the configuration (align assignment error parameter for the channel: actual and set configuration). Inserted module does not Correct the parameter match the one configured.
  • Page 17: Analog Value Representation

    Analog value representation Introduction Electronic modules with analog outputs With the electronic module with analog inputs, continuously variable signals, such as those occurring in temperature measurement and resistance measurement, can be acquired, evaluated, and converted to digital values for further processing. Analog value representation for measuring range with SIMATIC S7 Analog value representation With the same nominal range, the digitized analog value is the same for input and output...
  • Page 18: Measuring Ranges

    Analog value representation 4.3 Measuring ranges Output value The following table shows the representation of the binary analog values and the corresponding decimal and hexadecimal representation of the units of the analog values. The table below shows the resolutions 11, 12, 13, and 15 bit + sign. Each analog value is entered left aligned in the ACCU.
  • Page 19 Analog value representation 4.3 Measuring ranges Current measuring range: ± 20 mA Table 4-4 SIMATIC S7 format: Measuring range ± 20 mA Measuring range ± 20 mA Units Range Decimal Hexadecimal > 23,5150 32767 7FFF Overflow 23,5150 32511 7EFF Overshoot range 20,0007 27649 6C01...
  • Page 20: Effect On Analog Value Representation

    Analog value representation 4.4 Effect on analog value representation Effect on analog value representation 4.4.1 Effect of the supply voltage and the operating state on analog input values The input values of the analog modules are dependent on the supply voltage for electronics/encoders and on the operating state of the PLC (CPU of the DP master).
  • Page 21: Connecting

    Connecting Connecting measuring sensors Introduction You can connect different measuring encoders to the analog input module: ● Current transmitters as: – 2-wire transmitters – 4-wire transmitters In this chapter you will find out how to connect the measuring encoders and what to watch out for when doing so.
  • Page 22 Connecting 5.1 Connecting measuring sensors Connecting measuring encoders to analog inputs There can only be a limited potential difference U (common mode) between the measuring lines of the input channels. To ensure that the permitted value is not exceeded, you must take different steps depending on the whether the encoders are isolated or non-isolated.
  • Page 23 Connecting 5.1 Connecting measuring sensors Isolated measuring encoders The isolated measuring encoders are not connected to the local ground potential. These can be potential-free. Depending on local conditions or interference, potential differences U (static or dynamic) can occur between the measuring lines M- of the input channels and the reference point of the measuring circuit M The permitted value for U must not be exceeded, even in environments with strong EMC...
  • Page 24 Connecting 5.1 Connecting measuring sensors Non-isolated measuring encoders The non-isolated measuring encoders are connected to the local ground potential. Depending on local conditions or interference, potential differences U (static or dynamic) can occur between the locally distributed measuring points. If the permitted value for U is exceeded, there must be equipotential bonding conductors between the measuring points.
  • Page 25: Wiring Unused Channels Of The Analog Input Modules

    Connecting 5.2 Wiring unused channels of the analog input modules Wiring unused channels of the analog input modules Rules Pay attention to the following instructions when wiring unused channels: ● "Deactivate" unused input channels when assigning parameters. ● A deactivated channel always returns the value 7FFF Using the shield connection Rules To prevent interference we recommend the following for analog electronic modules:...
  • Page 26 Connecting 5.3 Using the shield connection 2 AI I 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0) Manual, 04/2007, A5E01076111-01...
  • Page 27: Index

    Index Service & Support, 4 Isolated measuring encoders, 23 2 AI I 2/4WIRE HF analog electronic module Block diagram, 9 Technical data, 9 LED display, 15 2AI I 2/4WIRE HF analog electronic module Block diagram, 9 Properties, 7 Terminal assignment, 7 Measured value resolution, 18 Measuring ranges with SIMATIC S7, 17 4-wire transmitters, 24...
  • Page 28 Index SIMATIC ET 200S distributed I/O 2 AI I 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0) Manual, 04/2007, A5E01076111-01...

Table of Contents