Indications; Premapped Indications; Common Data 1 - ABB RELION 611 Series Modbus Point List Manual

Voltage protection and control
Hide thumbs Also See for RELION 611 Series:
Table of Contents
Section 2
Modbus data mappings
2.3
2.3.1
2.3.1.1
Table 4:

Common data 1

BitA
RegA
2720
170.00
2721
170.01
2722
170.02
2723
170.03
12
Function
Residual voltage measurement
Frequency measurement
Other
Input switch group
Output switch group
Selector
Minimum pulse timer (2 pcs)
Move (8 pcs)
1, 2, ... = Number of included instances. The instances of a protection function represent the number of
identical protection function blocks available in the standardized configuration.
() = optional

Indications

Table 3:
Explanations of the indications table columns
Column name
Description
BitA
Default 0X and 1X bit address for the data.
RegA
Default 3X and 4X register.bit (00-15) address for the data.
IEC 61850
Original IED data object identification. Described in the IEC 61850 format as Logical
name
Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the
same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description
Short description of the signal. See the technical manual for more information.
Value
Meaning of the value states.

Premapped indications

Common data 1
IEC 61850 name
SA name
CTRL.LLN0
.Loc.stVal
-
.LocKeyHMI.stVal.Statio
-
n
DR.RDRE1
.RcdMade.stVal
-
.mcd
IEC 61850
RESVMMXU
FMMXU
ISWGAPC
OSWGAPC
SELGAPC
TPGAPC
MVGAPC
Description
Remote/Local state
Station state
DR recording made
1MRS758336 B
A
UE/C101
1
1
10
20
6
10
1
Values
0/1=Rem/Loc
1=Station
1=Made
REU611
Point List Manual
Table of Contents
loading

This manual is also suitable for:

Relion 611 reu611