▪ The precautionary measures described in this document cover very important topics. Follow them meticulously. Daikin Altherma ETS(X/H)(B)-D Installation manual Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
WARNING mentation are available on the regional Daikin website or, on re- quest, from your dealer. The Daikin website is easy to access using Devices that have not been set up and installed correctly the QR code on your device.
CAUTION Use only propylene glycol including the required inhibitors, classified as category III as per EN 1717. Daikin Altherma ETS(X/H)(B)-D Installation manual Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
Proper disposal in compliance with the respective national regulations of the country of use is the respons- ibility of the user/owner. Installation manual Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
Warranty claims can only be made if the annual maintenance work is demonstrably carried out regularly according to the information in the installer reference guide. Daikin Altherma ETS(X/H)(B)-D Installation manual Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
Design and components – Outside of the device Fig. 2-2 Design and components – Top of the device For legend, see Tab. 2-1 Installation manual Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
Page 9
Pressure relief valve Outdoor unit water inlet connection Circulation stop valve Outdoor unit water outlet (accessory) connection For legend, see Tab. 2-1 Daikin Altherma ETS(X/H)(B)-D Installation manual Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
▪ The base must be level and smooth and have sufficient ground load-bearing capacity of 1050 kg/m² plus safety factor. Install a pedestal if necessary. ▪ Observe the installation dimensions (see Chap. 3.1). Installation manual Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
Carefully transport the indoor unit to the installation site, use the handles. Install the indoor unit at the installation site. Daikin Altherma ETS(X/H)(B)-D Installation manual Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
Moving the controller housing to the service position Remove the controller housing from the front and insert it into the bracket with the hooks on the rear brackets. Installation manual Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
Hook in the cover on the controller housing with the lateral hooks. Fig. 3-13 Hooking in the cover Fig. 3-15 Removing the bottom thermal insulation Daikin Altherma ETS(X/H)(B)-D Installation manual Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
(Fig. 3-20, item A) can be pushed vertically in between. Fig. 3-17 Variants for aligning the heating feed and return Installation manual Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
Place the front cover straight over the rotary switch of the RoCon + HP. Press on the top and bottom until the front screen is se- curely engaged again. Daikin Altherma ETS(X/H)(B)-D Installation manual Heat pump (indoor unit) with integrated heat accumulator...
Guide the cable of the Ultra EHS PCB through the cable grom- met and connect it to the RoCon BM2C (see Fig. 3-41). Installation manual Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
▪ If a higher pressure is present in the domestic water pipe, a ▪ The inflow temperature of the external heater should pressure reducer will need to be installed. be limited to max. 95 °C. Make the hydraulic connections to the Daikin Altherma 3 H HT CAUTION ▪ Refer to Fig. 3-1 up to Fig.
(insulation thickness at least 20 mm). ▪ Water shortage protection: the controller's pressure and tem- DANGER: RISK OF ELECTROCUTION perature monitoring function reliably shuts off the Daikin Touching live parts can result in an electric shock and Altherma 3 H HT ECH O if there is a shortage of water.
Page 21
Modifications on the electrical in- stallation are dangerous and prohibited. The operator alone bears responsibility for any resulting damage. Daikin Altherma ETS(X/H)(B)-D Installation manual Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
Overall connection diagram – for the electrical connection during the device installation (for the legend and pin assignment of the PCB, see Chap. 6.3) Installation manual Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
When special functions (e.g. "Manual operation") are activated, the input is not evaluated. Installation manual Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
▪ The connections of the RTX-EHS PCB must not be used simultaneously for connecting mains voltage (~230 V) and SELV ("Safety Extra Low Voltage"). Daikin Altherma ETS(X/H)(B)-D Installation manual Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
The controller can be connected to the internet with the optional EHS157056 gateway. This enables remote control of the indoor unit by mobile phones (by app). Fig. 3-42 Connection with wired room thermostat (RT = Daikin INFORMATION EKRTW) Separate installation instructions are included with this component.
See Controller operating instructions → chapter Parameter settings. Precise information on the electrical connection and the re- quired parameter settings for such bivalent heating sys- tems are available on the Internet (www.daikin.com) or from your service partner. 3.7.14 Off-peak mains connection (HT/NT)
Polluted domestic water is hazardous to health. ▪ When filling the heating system, make sure that heating water cannot flow back into the domestic water pipe. Daikin Altherma ETS(X/H)(B)-D Installation manual Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
Page 30
▪ Protection against freezing: the glycol protects the fluid in the pipes against freezing. if not already installed in the heating system Installation manual Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
If necessary, the configuration of optional components (such as the room thermostat or the solar system) must be carried out according to the respective instructions. Daikin Altherma ETS(X/H)(B)-D Installation manual Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
Bleeding the hydraulic system Make sure that the automatic vent valve cap is open (item A). Fig. 5-2 Manual vent valves Installation manual Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
After the screed program has ended, the RoCon+ HP controller con- tinues to work in the previously set operating mode. Daikin Altherma ETS(X/H)(B)-D Installation manual Heat pump (indoor unit) with integrated heat accumulator...
▪ Show the user what he/she has to do in relation to maintaining the unit. ▪ Explain the user about energy saving tips as described in the op- eration manual. Installation manual Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator 008.1448499_00 – 06/2019 – EN...
Technical data Technical data Operating pressure of storage water pH Part of the current technical data is available on the regional Daikin- Nominal capacity of drinking water website (publicly accessible). The complete technical data is avail- Max. operating pressure PMW (plumbing) able via the Daikin Business Portal (authentication required).