DEFAULT SETTINGS & MENU ITEM DESCRIPTIONS
Default Settings & Menu Item Descriptions — SETUP
To enter the Settings Menu, press and hold, the "Back" button for 5 seconds, the control will beep once. There are three menu
options, SETUP, ADVANCED SETUP, and VIEW LOG. Place the curser in front of the menu item and press "Select". Once a
setting is changed, the select button must be pressed to save the setting.
SETUP
BOILERS
# OF BOILERS
LEAD BOILER #
LEAD BOILER #
HEAT BAND
HNT
SETPOINTS
LOCAL SETPT
OPERATE LIMIT
LOCAL SETPT
OP LIM BAND
SETPT SOURCE
OUTDOOR AIR RESET
OA RESET
WARM WEATHER SD
WWS SETPOINT
SET OA SETPOINTS
WATER TEMP
At
HIGH OA TEMP
WATER TEMP
At
LOW OA TEMP
PUMP OPTIONS
SYSTEM PUMP
POST PRGE TIME
PUMP ROTATION
ROTATION:
SYSTEM PUMPS
Page 88
DEFAULT
RANGE
VALUE
1
1-16
0
0- 6
0
0-16
2-50 F
30F
M
M-16
160 F
40-220
215 F
45-230
160 F
40-220 F
1-50 F
20F
AUTO
AUTO
4-20mA
OFF
NO
40 – 100 F
68F
60 – 190 F
140F
-35 – 40 F
10F
2 minutes
2-60min
NONE
NONE
SYS HRS
PUMP HRS
1
1 or 2
If operating as a Member.
# of first boiler to run, determines the fire order in rotation. A
# of first boiler to run, determines the fire order in rotation. A 0
disables the Lead Boiler function. Firing Mode determines lead.
Differential temp around setpoint used to stage boiler(s) OFF/ON
This line displays the boilers auto detected by H-Net. While M is the
Master boiler the numbers are the H-Net address of each boiler from
2–16.
°
Local setpoint used to maintain temperature of SETPT SOURCE
F
When running as a Member, boiler shuts off when supply
temperature reached.
°
F
Boiler restarts at lower temp of OP LIM BAND or 10F whichever is
lower
Local setpoint used to maintain temperature of SETPT SOURCE
Limits external input % when in (OP LIM - OP LIM BAND)
AUTO = Local/ System/ WWS Setpoint is used
4-20mA input is mapped to a setpoint.
Outdoor reset ratio (boiler water temp/outside air temp).
If set to YES, the boiler /system shuts down when the temperature
exceeds the WWS SETPOINT.
Temperature at which boiler shuts down, operation is below this.
If boiler is running using either OA RESET or WWS and the OA
OVR input is closed the OA RESET slope is overridden and runs at
local setpoint until OA OVR input opens.
Boiler water temp setpoint when OA temp is at HIGH OATEMP
These four setpoints determine the OA reset slope.
Header/Supply setpoint when OA Temp is at LOW OA TEMP
Time in minutes to keep system circ. pump on after boiler stops
New menu screen
The number of system pumps. Only 1 available in Lite version.
HeatNet Control V3
DESCRIPTION