Honeywell Fire-Lite IPOTS-COM Product Installation Document

Digital communicator

Quick Links

1 Description

The IP/POTS Communicator card transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched
telephone network and/or Internet protocol. It also allows remote programming or interrogation of the control panel using AlarmNet®.

2 Installation

WARNING: THIS SYSTEM CONTAINS STATIC SENSITIVE COMPONENTS
!
WEAR A PROPER GROUNDING WRIST STRAP AND WORK ON A STATIC-SAFE WORKSPACE TO PROTECT
ELECTRONIC ASSEMBLIES.

2.1 50 Point and 198 Point Panel Installation

1.
Disconnect all power from the fire panel.
2.
Remove the two screws at the bottom of the board that are used to attach the board to the chassis.
3.
Replace the screws with two 3/4" standoffs from the hardware kit.
H/L1
EARTH
N/L2
4.
Insert the plastic PCB spacer into the hole marked "Communicator Support".
5.
Install the 5" cable from the hardware kit into the header on the main PCB marked "Communicator" and the header on the IPOTS-COM
labeled "Main Board Int" as shown below.
6.
Holding the IPOTS-COM on an angle, align the pins on the plastic keypad bezel to the holes on the sides of the communicator.
7.
Lay the IPOTS-COM flat and snap it onto the PCB spacer.
ALRM
TRBL
SUPV
RMT SYNC
NAC1
NO
NC
C
NO
NC
C
NO
NC
C
OUT+
RTN+
RTN-
OUT-
BATTERY
IPOTS-COM IP/POTS Digital Communicator
Product Installation Document
PN LS10184-000GE-E:B 6/6/2018 18-244
ANN-BUS SEC
NAC2
NAC3
NAC4
ANN-BUS PRI
USB-A
DISPLAY
Remove screws and install standoffs
24V
SLC
Plastic pins
Insert PCB spacer
Cable
header
COMMUNICATOR
ANN-LC
loading

Summary of Contents for Honeywell Fire-Lite IPOTS-COM

  • Page 1 IPOTS-COM IP/POTS Digital Communicator Product Installation Document PN LS10184-000GE-E:B 6/6/2018 18-244 1 Description The IP/POTS Communicator card transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network and/or Internet protocol. It also allows remote programming or interrogation of the control panel using AlarmNet®. 2 Installation WARNING: THIS SYSTEM CONTAINS STATIC SENSITIVE COMPONENTS WEAR A PROPER GROUNDING WRIST STRAP AND WORK ON A STATIC-SAFE WORKSPACE TO PROTECT...
  • Page 2 There are two configurable dip switches on the IPOTS-COM communicator. SW2: 6-position dip switch- FUTURE USE- No configuration necessary. SW3: 2-position dip switch- Factory Settings- Do not change unless instructed to do so by Honeywell. IPOTS-COM Installation Document — P/N LS10184-000GE-E:B 6/6/2018...