GE MM3 Instruction Manual page 149

Motor manager 3
Hide thumbs Also See for MM3:
Table of Contents
8 MM3PC SOFTWARE
5. Type 1139 (the address of baud rate setpoint) in the address box and 4 (4 = 19200 baud) in the values box
in the Memory Map Insertion section. Refer to Section 6.5: MEMORY MAP on page 6–18 for details.
6. Click Send and then Yes to confirm the setpoint write action. All communications will immediately be lost –
ignore any errors.
7. Select OK to exit the Troubleshooting window.
8. Select the Communication > Computer menu item.
9. Change the baud rate setting to 19200, click Store, then click OK. Select the Communication > Com-
puter menu item again and click ON in the Communication Control section. The status should now read
"Program is now talking to Multilin device."
10. Select OK to exit the Communication/Computer window and select the Communication > Troubleshoot-
ing menu item.
11. Enter 1147 (address of the parity setpoint) in the address box and 1 (1 = even) in the values box in the
Memory Map Insertion section. Refer to Section 6.5: MEMORY MAP on page 6–18 for details.
12. Click Send and then Yes to confirm the setpoint write action. All communications will immediately be lost –
ignore any errors.
13. Select OK to exit the Troubleshooting window.
14. Select the Communication > Computer menu item.
15. Change the parity setting to even, click Store, then click OK. Select the Communication > Computer
menu item again and click ON in the Communication Control section. The status should now read "Pro-
gram is now talking to Multilin device."
16. Select OK to exit the Communication/Computer window.
GE Power Management
MM3 Motor Manager 3