Maintenance and troubleshooting
August 2019
Functional test procedure
Perform a functional test of the detector as described in
4.1.3
Keeping maintenance records
Emerson recommends that you record maintenance operations performed on a detector
in a log book. The record should include the following:
Installation date and contractor
Serial and tag number
Entries for every maintenance operation performed, including the description of the
operation, date, and personnel ID
If you send a unit to Rosemount or a distributer for service, include a copy of the
maintenance records.
4.2

Troubleshooting

This section is intended to be a guide to correct problems that may happen during normal
operation.
4.2.1
Fault relay at N.O.
LEDs off
0-20 mA at 0 mA
No power to the unit
Recommended actions
1. Check that the correct power is sent to the detector.
2. Check power polarity.
3. Check wiring in the detector.
4. Send the detector back for repairs.
4.2.2
Fault relay at N.O.
Yellow/amber LED flashes at 4 Hz.
0-20 mA at 0 mA
Detector fault
Low voltage
Faulty detector
Recommended actions
1. Check the voltage at the detector; verify at least 24 V at the detector terminal.
44