Allen-Bradley PowerFlex 70 Reference Manual page 212

Adjustable frequency ac drive
Hide thumbs Also See for PowerFlex 70:
Table of Contents
2-184
Start-Up
2-0
StartUp
2. Motr Dat/Ramp
Use motor name-
plate data and
required ramp
times for the
following steps.
Enter
2-1
StartUp
2. Motr Dat/Ramp
Enter choice for
Mtr NP Pwr Units
Enter
2-2
StartUp
2. Motr Dat/Ramp
Enter value for
Motor NP Power
123.4 kW
xxx.x <> yyy.y
Enter
2-3
StartUp
2. Motr Dat/Ramp
Enter value for
Motor NP FLA
+456.78 Amps
xxx.xx <> yyy.yy
Enter
2-4
StartUp
2. Motr Dat/Ramp
Enter value for
Motor NP Volts
123.4 Volt
xxx.x <> yyy.y
Enter
2-5
StartUp
2. Motr Dat/Ramp
Enter value for
Motor NP Hertz
60.0 Hz
x.x <> y.y
Enter
2-6
StartUp
2. Motr Dat/Ramp
Enter value for
Motor NP RPM
+456 RPM
xxx <> yyy
Figure 2.39 PowerFlex 70 & 700 Standard Control Option Startup (2)
2-7
StartUp
2. Motr Dat/Ramp
Enter choice for
Stop Mode A
Enter
Backup
Stop Mode A
= "DC Brake" or
"Ramp to
Hold"?
Yes
2-8
StartUp
2. Motr Dat/Ramp
Enter
Enter value for
DC Brake Level
1.0 Amps
0.0 < 30.0 Amps
Enter
Stop Mode A
Backup
= "DC
Brake"?
Yes
2-9
StartUp
2. Motr Dat/Ramp
Enter value for
DC BrakeTime
1.0 Secs
0.0 < 90.0 Secs
Backup
2-10
StartUp
2. Motr Dat/Ramp
Enter choice for
No
DB Resistor Type
None
Internal
External
Enter
2-11
StartUp
2. Motr Dat/Ramp
Enter value for
No
Accel Time 1
6.0 Secs
0.0 < 60.0 secs
Enter
Enter
2-12
StartUp
2. Motr Dat/Ramp
Enter value for
Decel Time 1
6.0 Secs
0.0 < 60.0 secs
Enter
2-13
StartUp
2. Motr Dat/Ramp
Enter value for
S Curve %
0 %
0 < 100 %
Basic Start Up (Motor Data/Ramp)
None - Bus Reg Mode A = Adj Freq.
Intenal - Bus Reg Mode A = Both, DB 1st.
External - Bus Reg Mode A = Both, DB 1st.
Enter
Go to 0-1 (3)