4.6 Prohibit Frequencies

2.5.1
Prohibit frequency area 1; Low limit
2.5.2
Prohibit frequency area 1; High limit
In some systems it may be necessary to
avoid certain frequencies because of
mechanical resonance problems. With
these parameters it is possible to set a limit
for the "skip frequency" region. See Figure
1- 14.
2.5.3
Acceleration/deceleration ramp speed scaling ratio between prohibit frequency limits
Defines the acceleration/deceleration time when the output frequency is between the selected
prohibit frequency range limits (parameters 2.5.1 and 2.5.2). The ramping time (selected
acceleration/ deceleration time 1 or 2) is multiplied with this factor. E.g. value 0.1 makes the
acceleration time 10 times shorter than outside the prohibit frequency range limits.
Figure 1- 15. Ramp time scaling between prohibit frequencies
Description of parameters
fout [Hz]
Par. 2.5.3 = 0,2
Par. 2.5.2
Par. 2.5.1
Output
frequency [Hz]
2.5.1
Figure 1- 14. Prohibit frequency area setting.
Par. 2.5.3 = 1,2
Time [s]
nxlk37.fh8
Page 37 (68)
2.5.2
Reference [Hz]
NX12K33
4