INTRODUCTION CONTROL PANEL LIMITATIONS This control panel may not show an alarm condition without compatible initiating devices (smoke detectors, etc.) and notification devices (horn, strobes, etc.) connected to it. Electrical ratings of the initiation and notification appliances must be compatible with the electrical ratings of the control panel and must be properly interconnected.
PREFACE Along with the use of this instruction manual, the appropriate following standards and the manufacturer's instructions for initiating and notification devices should be used to install and maintain a functioning fire alarm signaling system. NFPA 72 National Fire Alarm Code For other standards that may apply contact the authority having jurisdiction.
Page 10
It is the responsibility of users requiring service to report the need for service to our Company or to one of our authorized agents. Service can be facilitated through our office at: SIEMENS INDUSTRY, INC. – BUILDING TECHNOLOGIES DIVISION – FIRE SAFETY 8 FERNWOOD RD., FLORHAM PARK, NJ 07932 -800-248-7976...
DESCRIPTIONS FC901 SYSTEM DESCRIPTION The FC901 is a compact but powerful standalone fire alarm control panel. It features advanced addressable fire detection, keypad and offline programming, notification circuits, a 160 by 64 dots LCD display and event history retention capability. It’s typical configuration includes a power supply, a signaling addressable device circuit, two notification appliance circuits (NAC), Digital Alarm Communication Transmitter (DACT), four system status relays and a USB programming port.
There is also a system coder capable of zone operation. All of the NACs are power limited and support synchronization of listed devices using the Siemens sync protocol. Serial Interface Circuit (UFP) The FC901 control panel has a Serial Interface Circuit (UFP) that will drive up to 8 devices, eg.
Note: For printer connection, wiring between the RPM and printer must be in conduit within 6 feet and in the same room as the panel. AUXILIARY MODULES Serial LCD Annunciators The FSD901 Serial LCD Annunciator consists of a backlit 160 by 64 dot (7 by 26 characters) LCD display, acknowledge, silence, unsilence, and reset buttons, a four-way button for event navigation, seven system status LED indicators and a security key switch.
SLC ADDRESSABLE DEVICES Smoke Detector The control panel processor sends the sensitivity settings to the detectors and polls the detectors for their status. The detector determines normal, trouble and alarm conditions and communicates the conditions to the control panel. Variable Thresholds - The detectors can be set to operate in various pre-programmed profiles, depending on the environment where the detectors are used.
the system configuration tool. When users need to disable the audible base , they will need to select the “disable audible base” option. When the audible base ABHW-4B and ABHW-4S is used with H/8700 series detectors, it can be programmed to 1 output channel, and only 2 tone patterns (steady, temporal 3) can be selected using the system configuration tool.
EVENT HISTORY The control panel includes a non-volatile memory recording 1000 system events. Identified alarm, trouble, supervisory, status and other significant events will be recorded along with the date and time of occurrence. The history event log can be viewed at the main system display by operating menu controls from the panel.
GENERAL DESIGN FEATURES Environmental The FC901 panels and subassemblies are suitable for use in a dry, indoor or protected location. Power Limiting The AC power connection, battery wiring and four system status relays are not power limited. All other circuits leaving the control panel meet the requirements for power limited circuits when installed in accordance with the National Electrical Code and local requirements.
Configured device is missing. Unconfigured device is installed. Two devices are programmed with the same address. Signaling line circuit experiences a wire-to-wire short. Signaling line circuit experiences an earth ground condition. REGULATORY STANDARDS The FC901 control panel meets the requirements of industry and government regulatory agencies as noted.
GENERAL SPECIFICATIONS Operating specifications for the FC901 are as follows: Environmental Operating temperature - 32 - 120°F (0 - 49°C) Relative humidity - Up to 93% @ 90°F (32°C) To be installed in a indoor dry protected environment only Primary Power Supply Input: 120VAC, 60Hz or 240VAC, 50Hz @ 2.0A Max.
Status Relays Non-power limited One programmable relay Three non-programmable relays: Trouble, Supervisory, Alarm Contact rating: 2A, 30VDC maximum Form C contact Notification Appliance Circuits Power limited Supervised Current Draw Maximum Line Resistance 2.5A 3.2Ω 2.0A 4.0Ω 1.5A 5.3Ω 1.0A 8.0Ω 0.5A 16.0Ω...
CONTROL PANEL OPERATION OPERATION INSTRUCTIONS Standby Condition In normal standby operation, the green AC POWER ON LED should be illuminated and no other indicator operating. The display will show the system label and the current time. Alarm Conditions ALARM When the system detects an alarm condition, the alarm LED activates (ON – flashing) and the local panel buzzer activates in a specific pattern to indicate an alarm condition.
PRE-SIGNAL ALARMS Activation of an initiating device in an input group programmed for PRE-SIGNAL, activates the Alarm LED, LCD display, and the local panel buzzer. System and user-programmed outputs activate immediately except NAC. The delay of activation of user-programmed outputs can be programmed from 60 to 180 seconds.
Page 24
If the FC901 is configured as “Supervisory self restoring”, the system shall return to the “System Normal” status if the supervisory condition is restored unless there are additional events on the system. If the FC901 is not configured as “Supervisory self restoring”, the system reverts to standby condition only after the RESET button is pressed.
ADDITIONAL OPERATING PROCEDURES In addition to the basic fire alarm instructions above, several features are included to facilitate maintenance and increase the versatility of the system. The following are procedures used to initiate these functions. Lamp Test When selected, Lamp Test activates LCD, the buzzer and turns on all the LEDs on the user interface, then back to its previous state.
FC901 OPERATING INSTRUCTIONS Alarm Operation In case of alarm, the Alarm LED flashes, LCD displays alarm conditions and the panel buzzer sounds in a distinct alarm pattern. Local audible and visual signals and remote alarm signals operate. When an alarm occurs, proceed according to the established emergency plan. Assure that all personnel are accounted for, and notify the Fire Department to advise of the alarm and/or verify that an automatic signal has been received at the Fire Department.
FSD901 OPERATING INSTRUCTIONS Alarm Operation In case of alarm, the Alarm LED flashes, LCD displays alarm condition and the buzzer sounds. Local audible and visual signals and remote alarm signals operate. When an alarm occurs, proceed according to the established emergency plan. Assure that all personnel are accounted for, and notify the Fire Department to advise of the alarm and/or verify that an automatic signal has been received at the Fire Department.
CAUTIONS 1. Remove the printed circuit boards for any procedure that may cause dust, metal shavings, grease (or such matter that may affect the operation of the boards) to get in contact with the units. 2. Disconnect all sources of power prior to installing or removing modules, connecting or disconnecting wiring.
Page 31
There are two key-shaped cutouts on the top of the backbox. Make sure the end with the two key-shaped cutouts is on top when installing the backbox. The front door can be removed from the enclosure for more convenient installation. 2.
FC901 Installation Size 6-2 3/8” 1 61/64” 1 3/16” 1 1/32” 16” 1 7/16” Remove Knock-Outs Prepare the enclosure for electrical wiring by breaking out the appropriate conduit entry points. Segregation is required between power limited and non-power limited conductors. In order to maintain the minimum separation, follow the wire routing illustrated on page 31.
Power Supply Mounting Secure the power supply to the back of enclosure using the four provided #8-32 x 3/8 screws. AC Input terminals must be located at the right side of the enclosure.
Ground Wire Installation Install one end of the grounding cable on the enclosure back box. Enclosure back box Install the other end of the grounding cable on the enclosure outer door. Enclosure outer door...
Battery Installation Use the battery calculation chart to determine the battery size. Place the batteries in the space provided in the bottom of the backbox. Secure the battery bracket (if required) to the back of enclosure using the eight provided #8-32 x 3/8 screws. Recommended battery size : Length:5.94 inch, Width: 3.86 inch, Height:3.7 inch.
Optional City Tie Mounting Secure the city tie to the main board using the two provided #4-32 x 3/8 screws. Spacer Detail A 2 #4 screws City tie module Connect the city tie cable between city module and main board. From 1 to 4 TP1295,TP1294,TP1293,TP1292 From left to right:...
Main Board Assembly Installation Secure the main board assembly to the enclosure using the four provided #8-32 x 3/8 screws 4 #8 screws Earth Cable Installation Connect the earth cable to the backbox and connector at the upper left corner of the main board.
SYSTEM WIRING Before connecting the field wiring, check the wiring for opens, shorts, grounds and stray voltages. WARNING Damage may result if a high voltage insulation tester is used on wiring while connected to the control panel. Terminate the field wiring to the main board in accordance with the diagrams in System Wiring Section.
Control Panel Wiring Overview In compliance with NEC Article 760 and UL 864, all power limited fire protective signaling conductors must be separated a minimum of 1/4 inch from all of the following wiring located within a control panel: Electric light Power Class 1 or non-power limited fire protective signaling conductors To meet these requirements, the following guidelines must be observed when installing...
Wiring Separation All high voltage and non-power limited wiring must be kept separate from power limited wiring. A separation of at least 1/4 inch must be maintained with high voltage and non-power limited wiring running in separate conduit openings from power limited wiring. 7 Optional field wire knock-outs Relay-1 Dialer...
Power Supply and Battery Wiring Route all high voltage and non-power limited wiring together and away from power limited wiring. Use the battery calculation chart to determine battery size. AC connection is done on power supply. Non-Power Limited Earth GND Brownout Connect to Main board Neutral...
P2 device Auxiliary power Series Interface City tie and DACT Status Relays circuit output Circuit lease line Power limited Non power limited Wiring terminals located on top of main board Status Relays Four relays with dry contacts are provided at the upper right corner of the main board. One relay is programmable and the trouble relay, supervisory relay and alarm relay are non- programmable.
NAC Wiring Two individual NACs are provided and the polarity shown is when the NAC is activated. Power Limited Supervised Current Draw Maximum Line Resistance 2.5A 3.2Ω 2.0A 4.0Ω 1.5A 5.3Ω 1.0A 8.0Ω 0.5A 16.0Ω Alarm voltage: 16 to 32VDC Maximum ripple: 0.1VAC Used for special application only Two Style Y/Class B or one Style Z/Class A...
Serial Interface Circuit (UFP) The serial interface circuit can address up to 8 devices, which include annunciators and printer modules. Up to 2 printers can be addressed. Devices on the circuit may be connected up to 4000 feet from the control panel. Serial Interface Circuit (UFP) (PR_A, PR_B) RS-485 levels Wire Type-Twisted Pair For Data...
Serial Remote Device Wiring Overview When connecting devices on the Serial Interface Circuit (UFP), the data wires must be daisy chained and with no T-taps to preserve the integrity of the data. The following diagrams show the proper wiring. Class B Style 4 Annunciator Annunciator PR_A/B...
SLC Addressable Device Circuit These devices are polled by the control panel every few seconds and input or output functions communicated to determine device status or function. The control panel monitors all device addresses for alarm and trouble conditions. Addressable Device Circuit Style 4 (Class B) or Style 6 (Class A) Operation Max.
AS PORT-A NOTE: Siemens SLC Devices: Detectors, Monitor Modules, or Control Modules up to a maximum of 50 devices (include both PORT-A and PORT-B). A Maximum of 20 devices recommended per Isolator Module. A Maximum of 15 Isolator Modules per addressable device circuit.
Page 50
MODULE NOTE NOTE: Siemens SLC Devices: Detectors, Monitor Modules, or Control Modules up to a maximum of 50 devices. A Maximum of 20 devices recommended between Isolator Modules. A Maximum of 15 Isolator Modules per addressable device circuit. NOTE: If more than one HCP is used on a SLC device loop, the loop must be wired Class A or the riser conductors must be installed in accordance with the Survivability From Attack By Fire requirements in the National Fire Alarm Code, NFPA 72.
Optional City Tie/Leased Line FC901 provides one city tie or two leased lines to connect with local energy and polarity reversal. City tie and Leased line Supervised, Power Limited City tie CT_P Master Box CT_N LL_SP LL_SN Leased line leased line CT_P alarm/trouble detection circuit...
This is the recommended method to program the panel. The Siemens FXS901-U3 software is available to allow programming the control panel by connection to a Personal Computer (PC) with an USB port. This allows ease of operation by preparing the program in advance and downloading to the control panel in a simple, rapid operation.
MAINTENANCE GENERAL The FC901 provides maintenance functions to allow for the setting and controlling of various features in the system. The maintenance functions are protected by a four digit password. To access the maintenance features press the “MENU” button and select Login item in the View menu, enter the four digit code when prompted and then press “OK”.
QUICK TEST The Quick Test mode makes it fast and easy to test a system by eliminating the need to disconnect panel from remote connections to the Fire Department or other monitoring stations. In this way, operator can test all devices locally without annunciating any condition to remote connections.
Total loop resistance - 50 ohm maximum with 50 devices Total loop capacitance - 0.5uF max line to line per km and 1.0uF max line to shield per km The terminal blocks of Siemens SLC devices are rated for a maximum of 14AWG wire.
BATTERY SIZE CALCULATIONS System Current Draw Break down System Current Draw Components Standby(A) Alarm(A) Main board 0.1590 0.1864 Auxiliary power City tie module 0.0017 0.0158 SLC Current Draw Break down SLC Current Draw Components Standby(A) Alarm(A) HFP-11 / 8713 0.00140 0.00140 HFPO-11 / 8710 0.00140...
Battery Size Total Standby Hours of Standby AH for Current Required per NFPA 72 Standby (from above) Standard (4, 24 or 90) Hours Total Alarm 5 Minutes of Alarm AH for Alarm Current Operation (from above) per NFPA 72 Standard Hours A.H.
Air Duct Housing Notes: Siemens SLC devices, detectors and modules, up to a maximum of 50 addresses may be used. For specific wiring and installation information, read the instructions provided with each device. If more than one HCP is used on a SLC device loop, the loop must be wired Class A or the riser conductors must be installed in accordance with the Survivability From Attack By Fire requirements in the National Fire Alarm Code, NFPA 72.
FC901 support OOHC941 CO function. CO channel can be configured as automatic alarm event and supervisory event in the detection tree of FC901. But it does not comply with UL 2017 standard when CO channel was configured to automatic alarm event. It does comply with UL 864. UFP devices Siemens Description Cat. No. FT2007-U1...
APPENDIX-C: TROUBLESHOOTING DEFINITIONS FOR EVENT HISTORY ENTRIES A. General ENTRY INDICATES Disabled The device has been disabled Ground The device is in ground fault Open The device is in open trouble Short The device is in short trouble Overload The SLC line is overloaded GeneralTrouble The device reports general trouble Unconfig...
APPENDIX-D: ALARM VERIFICATION A - Smoke detector goes into alarm. (LED on device turns to red) AB - Retard Period, FACP senses detector in alarm and delays alarm signal for 50s. In this period, no alarm event reports on FACP. BC - Confirmation Period, Detector is operational for alarm at point B.
APPENDIX-E: APPLICATION SPECIFIC DETECTION Application Specific Detection (ASD) allows the system designer to program a detector’s sensitivity, pre-alarm threshold, and other alarm-related parameters using English descriptions of the detector's environment (application). This eliminates the need for detailed knowledge of smoke detector terminology and operation. The designer can set all of the critical detector parameters by simply selecting an application description that closely fits the one where the detector is to be installed.
APPENDIX-F: TESTING/MAINTENANCE If the system is connected to the fire department, etc., or actuates an internal system, disarm the appropriate outputs before servicing to prevent actuation. Notify the fire department and personnel at your facility that a System test is being performed so that any alarm sounding can be ignored during the test.
APPENDIX-G: LCD, CONTROLS AND INDICATORS The FC901 has a buzzer, 7 LEDs, 4 navigational push buttons, 4 dedicated push buttons, alphanumeric keypad, 3 menu control buttons (menu, cancel, ok) and a communication port connector. Communication Port Connector The communication port is connected to the USB port of the computer that has the FXS901-U3 programming tool.
Page 67
This indicates that there is no supervisory event in system. This indicates that there are supervisory events Flashing in system, but some of them have not been acknowledged. This indicates that there are Ground Fault Steady ON events in system. This indicates that there is no Ground Fault Ground Fault Yellow...
Page 68
The buttons operates as follows: Silences all silenceable devices in system. This will cause all activated Alarm Silence Press silenceable devices to become silenced. Acknowledge Press Acknowledges all unacknowledged events in system. Clears all obsolete events and resets all devices, except those disabled ones Reset Press and hold-through-reset devices in system.
LCD Display The LCD operates as follows: Trouble 02/13 12:12 V AutoAlarm Zone 1 10-30-2010 12:00:01 V Open Line 1 10-30-2010 12:00:00 Line 1 – Index and Category of current selected event, User level, current time Line 2 – Acknowledged status, Event Type Line 3 –...
APPENDIX-H: OUTPUT FEATURES Output Activation- and Deactivation- Delays Each output device has a selection for Activation delay and Deactivation delay when it is installed in the configuration. The Activation delay refers to the delay in which the output will activate after the reception of its activation command. If the Activation delay is set to 0 (default setting), the output immediately activates.
APPENDIX-I: PAS / PRE-SIGNAL PAS (Positive Alarm Sequence) and Pre-Signal features allow the user to delay the activation of the audibles, strobes and other output devices when an initial alarm is detected. Output can be interlocked by zones. When an initial alarm is detected, all outputs except remote devices (off-premises devices like general relays and city tie) associated with PAS Zone (Zone configured with PAS feature) will be activated immediately.
Pre-Signal When an alarm causing device in a Pre-Signal input group is initiated, the alarm condition is reported at the panel. Its associated NACs are not activated until the programmed investigation delay has relapsed or 2 Alarm is initiated anytime during the Pre-Signal delay time (see figure below).
APPENDIX-J: DACT INFORMATION OVERVIEW The DACT (Digital Alarm Communicator Transmitter) is an optional module for the FC901 control panel that allows transmission of event information to a remote receiver at a monitoring station using a dial-up modem connection. These events are transmitted in one of the following formats: ...
Page 74
To configure an event to be reported to Account 1 and Account 2, set it to Must report on both. If the event needs to be reported to either Account 1 or Account 2, set it to Can report on both. If it has to be reported to Account 1, but only needs to be reported on Account 2 if Account 1 is temporarily out-of-order, set the event to Must Report on Account 1 and Can Report on Account 2.
Page 75
Scenario 2 – Must/Can Alarm Event is set to Must Report on Account 1 and Can Report on Account 2. Panel fails on Account 1 the first time. Step 1: Panel goes into alarm. Account 1 Step 2: Panel tries to send event to Account 1, but is unsuccessful.
Page 76
Scenario 3 – Must/Can Alarm Event is set to Must Report on Account 1 and Can Report on Account 2. Panel succeeds on Account 1 the first time. Step 1: Panel goes into alarm. Account 1 Step 2: Panel tries to send event to Account 1 successful.
Page 77
Scenario 4 – Can/Can Alarm Event is set to Can Report on Account 1 and Account 2. Panel succeeds on Account 2 before Account Step 1: Panel goes into alarm. Account 1 Step 2: Panel tries to send event to Account 1, but is unsuccessful.
Page 78
DACT Compatible Alarm Communicators The FC901-U3/-R3 DACT is also compatible with Alarm communicators that utilized different communication technologies (IP and GSM technologies) to connect to compatible Receivers using compatible protocol listed within this documentation. COMPATIBLE ALARM COMMUNICATORS Installation Manufacturer Model...
APPENDIX-K: DRIFT COMPENSATION The H-Series/8700 optical detector cannot implement drift compensation on its own. Drift compensation is the panel’s responsibility. While the system is running, the detector sends its chamber real-time values to the panel periodically and does not do compensation by itself. For the first hour after a panel startup, the panel will check the detector chamber values every 10 minutes.
APPENDIX-L: GLOSSARY AC Power Fail. Refers to a condition in which AC power loss is detected by the system. Alarm Signal. A signal indicating an emergency requiring immediate action, such as an alarm for fire from a manual station, a waterflow alarm, or an automatic smoke detector. Alarm Silence Inhibit.
Page 81
fan restart usage has higher priority than the OFF time delay and will therefore immediately deactivate the hold-thru reset outputs. Initiating Device. A manually or automatically operated device such as a manual pull station, smoke detector, heat detector, waterflow switch or tamper switch. Initiating Device Circuit (IDC).
Page 82
Waterflow Switch. An assembly approved for service and so constructed and installed that any flow of water from a sprinkler system equal to or greater than that from a single automatic sprinkler head will result in activation of this switch and subsequent indication of an alarm condition.