To Connect The Main Power Supply; To Connect The Backup Heater Power Supply - Daikin Altherma EPGA14DAV3 Installer's Reference Manual

Low temperature split
Hide thumbs Also See for Altherma EPGA14DAV3:
Table of Contents
7.6.8

To connect the main power supply

1 Connect the main power supply.
In case of normal kWh rate power supply
1 2 3
1 2 3
a
1 2 3
X11YA
X1M
X11YB
X11Y
X1A
Legend: see illustration below.
In case of preferential kWh rate power supply
Connect X11Y to X11YB.
1 2 3
N L
1
2 3
N L
a
b
c
1 2 3
5
6
X11YB
X1M
X11YA
X11Y
X1A
a
Interconnection cable (=main power supply)
b
Normal kWh rate power supply
c
Preferential power supply contact
2 Fix the cables with cable ties to the cable tie mountings.
INFORMATION
In case of preferential kWh rate power supply, connect
X11Y to X11YB. The necessity of separate normal kWh
rate power supply to indoor unit (b) X2M/5+6 depends on
the type of preferential kWh rate power supply.
Separate connection to the indoor unit is required:
▪ if preferential kWh rate power supply is interrupted
when active, OR
▪ if no power consumption of the indoor unit is allowed at
the preferential kWh rate power supply when active.
INFORMATION
The preferential kWh rate power supply contact is
connected to the same terminals (X5M/9+10) as the safety
thermostat. It is only possible for the system to have
EITHER preferential kWh rate power supply OR a safety
thermostat.
EPGA11~16DAV3 + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556070-1 – 2018.10
X2M
X5M
S1S
X2M
9 10
X5M
7.6.9
To connect the backup heater power
supply
WARNING
The backup heater MUST have a dedicated power supply
and MUST be protected by the safety devices required by
the applicable legislation.
CAUTION
To guarantee the unit is completely earthed, always
connect the backup heater power supply and the earth
cable.
The backup heater capacity can vary, depending on the indoor unit
model. Make sure that the power supply is in accordance with the
backup heater capacity, as listed in the table below.
Backup
Backup
heater type
heater
supply
capacity
*6V
2 kW
1N~ 230 V
4 kW
1N~ 230 V
6 kW
1N~ 230 V
2 kW
3~ 230 V
4 kW
3~ 230 V
6 kW
3~ 230 V
*9W
3 kW
3N~ 400 V
6 kW
3N~ 400 V
9 kW
3N~ 400 V
(a)
Equipment complying with EN/IEC 61000-3-12 (European/
International Technical Standard setting the limits for
harmonic currents produced by equipment connected to
public low-voltage systems with input current >16 A and
≤75 A per phase.).
(b)
This equipment complies with EN/IEC 61000‑3‑11
(European/International Technical Standard setting the
limits for voltage changes, voltage fluctuations and flicker in
public low-voltage supply systems for equipment with rated
current ≤75 A) provided that the system impedance Z
less than or equal to Z
user's supply and the public system. It is the responsibility
of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if
necessary, that the equipment is connected only to a
supply with a system impedance Z
Z
.
max
(c)
(6V)
(d)
(6T1)
Connect the backup heater power supply as follows:
a
X6M
F1B
b
Q1DI
a
Factory-mounted cable connected to the backup heater
contactor inside the switch box (K5M)
b
Field wiring (see table below)
7 Installation
Power
Maximum
Z
max
running
current
(c)
9 A
(c)
(a)(b)
17 A
0.22 Ω
(c)
(a)(b)
26 A
0.22 Ω
(d)
5 A
(d)
10 A
(d)
15 A
4 A
9 A
13 A
sys
at the interface point between the
max
less than or equal to
sys
Installer reference guide
is
37

Hide quick links:

Table of Contents
loading

Table of Contents