Swegon PARASOL Zenith 1200 Quick Manual

Swegon PARASOL Zenith 1200 Quick Manual

Hide thumbs Also See for PARASOL Zenith 1200:

Quick Links

PARASOL Zenith
Integrated comfort module
QUICK GUIDE
High performance 4-way distribution comfort module
with cooling, heating and ventilation
Large span between the lowest and highest air flow
Few variants serve many needs
Optimised for low energy consumption
Manages high air flow at low driving pressure
Low noise level
Easy installation on account of low weight, compact
dimensions and optional air connections on short or
long sides
Stylish design with optional perforation pattern
Fold-out coil as an optional extra when stringent
cleaning demands are stipulated
Quick bracket
Can be integrated in the WISE system with the help of
the factory mounted WISE IORE
Variant
Supply air
Size
Air
Pa*
l/s
connection
1200
Ø160
50
20
1200
Ø160
50
40
1200
Ø160
50
60
1200
Ø160
75
20
1200
Ø160
75
40
1200
Ø160
75
60
1800
Ø160
50
20
1800
Ø160
50
50
1800
Ø160
50
80
1800
Ø160
75
20
1800
Ø160
75
50
1800
Ø160
75
80
*Total pressure (Pa)
**Air: ∆T
=7K / Water: ∆T
=8.5K, q
l
mk
Performance
m
/h
Total cooling
Sound level
3
capacity (W)**
(dB(A))
72
763
144
1123
216
1329
72
835
144
1243
216
1482
72
884
180
1463
288
1732
72
1002
180
1613
288
1958
=0.07 l/s, t
=14°C
k
in
<20
22
26
21
25
28
<20
24
31
21
27
34
Table of Contents
loading

Summary of Contents for Swegon PARASOL Zenith 1200

  • Page 1 PARASOL Zenith Integrated comfort module QUICK GUIDE Variant Supply air Performance ○ High performance 4-way distribution comfort module Size Total cooling Sound level connection capacity (W)** (dB(A)) with cooling, heating and ventilation 1200 Ø160 <20 ○ Large span between the lowest and highest air flow 1200 Ø160 1123...
  • Page 2: Table Of Contents

    Factory-fitted ............21 Loose items .............. 23 Dimensions and weights ........25 PARASOL Zenith 1200, long-side connection (2 or 4) .. 26 PARASOL Zenith 1200, long-side connection (1 or 3) .. 27 PARASOL Zenith 1800, long-side connection (2 or 4) .. 28 PARASOL Zenith 1800, long-side connection (1 or 3) ..
  • Page 3: Advantages With Parasol Zenith

    • Space efficient – Takes up very little ceiling space • ADC air deflector - Change the air flow pattern as • Different perforation to choose from required • Very low sound levels • Numerous options with different colours 20180420 Swegon reserves the right to alter specifications.
  • Page 4: Technical Description

    PARAGON Zenith is available in the following variants: Figure 1. Product image (PARASOL Zenith 1200) Variant A: Supply air and waterborne cooling, (1200 and 1800)
  • Page 5 No matter which scenario you imagine, Parasol Zenith gives you the possibility to find the right solution. 20180420 Swegon reserves the right to alter specifications.
  • Page 6: Large Operation Range

    = 75 Pa; ∆T Supply air: 12 m 10 m Cooling water: t = 14°C; t =17°C 30 l/s 60 l/s Room: = 24°C 700-1000 W cooling load 900-1150 W cooling load room Swegon reserves the right to alter specifications. 20180420...
  • Page 7: Comfort Guarantee

    The sound level and the static pressure are not at all affected by the ADC. Figure 8. Parasol Zenith with examples of different ADC settings 20180420 Swegon reserves the right to alter specifications.
  • Page 8: Change Of Layout - Example

    Change of layout - Example The direction and rate of the air flow can be easily opti- mised using the Swegon ProSelect sizing program avail- Figure 9 shows an example of the floor plan of a build- able at www.swegon.com. You can then easily export ing with offices and a conference room.
  • Page 9: Design

    Figure 15. PE face plate Square holes arranged in a square pat- tern with a graduated border Figure 16. PX face plate Circular holes arranged in a square pat- tern - field perforated rectangular paths. 20180420 Swegon reserves the right to alter specifications.
  • Page 10: Rooms With Elevated Hygiene Demands

    Note! requires the product to be ordered with the accessory, fold- out coil, and that flexible connection hoses are used on the water side. Swegon reserves the right to alter specifications. 20180420...
  • Page 11: Alternative Air Connections

    Figure 24. Parasol Zenith with short-side connection and long side connection. Irrespective of the connection, the water connection is placed in the same easily accessible position. 20180420 Swegon reserves the right to alter specifications.
  • Page 12: Installation - Details

    (Figure 28) 5 0 m m Figure 27. Suspension with quick brackets, PARASOL Z QUICK SUSPENSION KIT Figure 28. Centring kit SYST CENTRINGKIT PARASOL Swegon reserves the right to alter specifications. 20180420...
  • Page 13: Connection Sizes

    Do not use solder couplings to connect the water pipes. High temperatures can damage the unit’s existing soldered joints. Flexible connection hoses for water may be ordered sepa- rately. 20180420 Swegon reserves the right to alter specifications.
  • Page 14: Technical Data

    Temperature differences are always expressed in Kelvin (K). Supply flow temperature Cooling water Heating water, max. 60 ºC ** Cooling water must always be kept at a level that ensures that no condensation is formed. Swegon reserves the right to alter specifications. 20180420...
  • Page 15: Cooling

    ** Locked ∆T 4°C on the water side. Temperature inlet flow +14°C, return flow +18°C. The specified sound level applies to straight connection without damper or with fully open damper. Room attenuation = 4 dB 20180420 Swegon reserves the right to alter specifications.
  • Page 16 PARASOL Zenith 1800 0,0133 A2 = Cooling and supply air, serial connected double row coil B2 = Cooling, heating and supply air, serial connected double row coil -values for the water flow 0.05l/s. Swegon reserves the right to alter specifications. 20180420...
  • Page 17: Heating

    Dif- ferent operating scenarios can be simulated easily using the Swegon ESBO software to calculate the heat balance where both the room air temperature and operative tem- perature are specified.
  • Page 18 Tabell 9. Pressure drop constant - water, K Function Unit (mm) heating* heating* PARASOL Zenith 1200 0,0287 PARASOL Zenith 1800 B2 = Cooling, heating and supply air, serial connected double row coil -values for the water flow 0,03l/s. Swegon reserves the right to alter specifications. 20180420...
  • Page 19: Acoustics

    By correcting L with the correction fac- Wtot tors from Table 14, the sound power level for each octave band (L ) can be obtained. wtot 20180420 Swegon reserves the right to alter specifications.
  • Page 20 Table 11. Natural attenuation ∆L (dB) PARASOL Zenith 1200 Ø160 Nozzle Octave band (Hz) setting 125 250 500 Table 12. Natural attenuation ∆L (dB) PARASOL Zenith 1800 Ø160 Nozzle Octave band (Hz) setting 125 250 500 Swegon reserves the right to alter specifications. 20180420...
  • Page 21: Accessories

    A ceiling containing different types of perforation patterns can be experienced as disturbing to the eye. Other patterns are of course available on special order. For further details, get in touch with your nearest Swegon representative. A. Standard face plate Circular holes arranged in a square pattern.
  • Page 22 PARASOL Zenith with fold-out coil is well suited for use in rooms where stringent demands are made on hygiene. The accessory requires the use of flexible hose connections on the water side. Swegon reserves the right to alter specifications. 20180420...
  • Page 23: Loose Items

    0. Nipple connection with seals at both ends. Dimensions: Ø125 and 160 mm Bleed nipple SYST AR-12 Nipple for venting the water circuit. Equipped with push-on connector adapted for installation with flexible connection hose F20 and F30. 20180420 Swegon reserves the right to alter specifications.
  • Page 24 Available in a circular or rectangular model and is always supplied with both mounting frame for the most common existing electrical connection boxes as well as a protruding frame for surface mounting. Transformer, SYST TS-1 72 VA Double-insulated protective transformer, 230V AC/24 V AC See separate product datasheet at www.swegon.com.
  • Page 25: Dimensions And Weights

    Dimensions and weights Table 15. Length and width Table 16. Weight - Variant A, cooling PARASOL Zenith 1200 PARASOL Zenith 1800 PARASOL Zenith Dry weight (kg) Water volume (l) Length L Width W Length L Width W Cooling Cooling (mm)
  • Page 26: Parasol Zenith 1200, Long-Side Connection (2 Or 4)

    PARASOL Zenith PARASOL Zenith 1200, long-side connection (2 or 4) c/c 508 + 20 Figure 31. Dimensional drawing, end-view with water connections. Air connection on the long side - pos 2. A1 = Supply cooling water ø12x1.0 mm (Cu) A2 = Return cooling water ø12x1.0 mm (Cu) B1 = Supply heating water ø12x1.0 mm (Cu)
  • Page 27: Parasol Zenith 1200, Long-Side Connection (1 Or 3)

    PARASOL Zenith PARASOL Zenith 1200, long-side connection (1 or 3) c/c 508 + 20 Figure 34. Dimensional drawing, end-view with water connections. Air connection on the short side - pos 1. * = Dimensions at air connection 160 A1 = Supply cooling water ø12x1.0 mm (Cu) A2 = Return cooling water ø12x1.0 mm (Cu)
  • Page 28: Parasol Zenith 1800, Long-Side Connection (2 Or 4)

    Figure 38. Dimensional drawing, view from above. Air connection on the long side - pos 2. Ø160 Figure 39. Dimensional drawing, side view. Air connection on the long side - pos 2. Swegon reserves the right to alter specifications. 20180420...
  • Page 29: Parasol Zenith 1800, Long-Side Connection (1 Or 3)

    Figure 41. Dimensional drawing, view from above. Air connection on the short side - pos 1. Ø160 Figure 42. Dimensional drawing, side view. Air connection on the short side - pos 1. 20180420 Swegon reserves the right to alter specifications.
  • Page 30: Parasol Zenith With Damper Or Bend

    Figure 44. Dimensional drawing, short side connection with the commissioning damper fitted SYST CRPc 9-125/160 124/159* 507/547* 127/167* Figure 45. Dimensional drawing, long side connection with bend Ø125/160 *= Ø160 124/159* 808/848* 127/167* Figure 46. Dimensional drawing, short side connection with bend Ø125/160 *= Ø160 Swegon reserves the right to alter specifications. 20180420...
  • Page 31: Specification

    Double module unit: Contractor demarcation 1184 x 584 mm 1192 x 592 mm Swegon’s delivery ends at the connection points for water and air and the connection of any factory-fitted actuators. 1198 x 598 mm (See Figures 31-46). 1213 x 603 mm •...
  • Page 32: Ordering Key - Product

    4 = Long side, left side of the water connection 2 = Long side, right side of the water connection 3 = Short side, opposite side as the water connection 4 = Long side, left side of the water connection Swegon reserves the right to alter specifications. 20180420...
  • Page 33: Specification Text

    Alternatively - External thread DN ½" (applies to factory-fitted valves) Air connection: Sleeve Ø125, Ø160 mm Optional short side or long side Product: Parasol Z a aaaa-B-ccc-ddd X pcs. Nozzle setting: XXXX 20180420 Swegon reserves the right to alter specifications.
  • Page 34: Swegon Reserves The Right To Alter Specifications

    Tools to facilitate adjustment of nozzle strips. SYST CENTRING KIT PARASOL X pcs. Kit consisting of 6 centring rails that can be used to centre the product in specific suspended ceiling systems. Swegon reserves the right to alter specifications. 20180420...
  • Page 35 Alternatively - External thread DN ½" (applies to fac- tory-fitted valves) Air connection: Sleeve Ø125, Ø160 mm Optional short side or long side Product: Parasol Z a aaaa-A-ccc-ddd X pcs. Nozzle setting: XXXX 20180420 Swegon reserves the right to alter specifications.
  • Page 36 Tools to facilitate adjustment of nozzle strips. SYST CENTRING KIT PARASOL X pcs. Kit consisting of 6 centring rails that can be used to centre the product in specific suspended ceiling systems. Swegon reserves the right to alter specifications. 20180420...

This manual is also suitable for:

Parasol zenith 1800

Table of Contents