Allen-Bradley 1757-FFLD User Manual

Foundation fieldbus linking device
Table of Contents

Quick Links

F
Fieldbus
OUNDATION
Linking Device
1757-FFLD
User Manual
AB Drives
Table of Contents
loading

Summary of Contents for Allen-Bradley 1757-FFLD

  • Page 1 Fieldbus OUNDATION Linking Device 1757-FFLD User Manual AB Drives...
  • Page 2 Solid state equipment has operational characteristics differing from those of Important User Information electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature) describes some important differences between solid state equipment and hard-wired electromechanical devices.
  • Page 3: Table Of Contents

    In This Chapter ......... . 3-1 1757-FFLD Function Blocks Parameter Attributes .
  • Page 4 Table of Contents BLOCK_ERR ........3-5 Parameters .
  • Page 5 Troubleshoot the Linking Device 1757-FFLD LED Indicators ....... A-1 Reset the Linking Device ........A-2 Reset Configuration .
  • Page 6: Table Of Contents

    Table of Contents Publication 1757-UM010A-EN-E - January 2006...
  • Page 7: Introduction

    Preface This publication provides information needed to use the 1757-FFLD, Introduction Fieldbus Linking Device. The linking device serves as a link OUNDATION between Fieldbus Foundation’s High Speed Ethernet (HSE) and H1 segments. It also serves as a link between EtherNet/IP and H1 segments. The linking...
  • Page 8: Conventions Used In This Manual

    Preface We use the following conventions in this manual: Conventions Used in This Manual Convention Meaning Example click Click left mouse button once. (Assumes cursor is positioned on Click Browse. object or selection.) double-click Click left mouse button twice in quick succession. (Assumes Double-click the H1 icon.
  • Page 9: In This Chapter

    Chapter Use RSLogix 5000 Software to Create a Linking Device In This Chapter See Page 1757-FFLD Example System Create a Project for the Controller Add the Communication Module, Linking Device and the Logix Blocks Launch RSFieldbus Software 1-12 Configure the Linking Device and...
  • Page 10: Create A Project For The Controller

    Use RSLogix 5000 Software to Create a Linking Device To configure and program a Logix5000 controller, use RSLogix 5000 software Create a Project for the to create and manage a project for the controller. Controller Project – The file on your workstation (or server) that stores the logic, configuration, data, and documentation for a controller.
  • Page 11: Create A Project

    Use RSLogix 5000 Software to Create a Linking Device Create a Project 1. Start RSLogix 5000 software. 2. Click the New button. 3. Specify the general configuration for the controller. Some items apply to certain controllers. a. Type of Controller b.
  • Page 12: Add The Communication Module, Linking Device

    Use RSLogix 5000 Software to Create a Linking Device To communicate with the controller, you add a bridge (local communication Add the Communication module), the linking device, and then the Logix blocks. Within the I/O Module, Linking Device Configuration folder, organize the modules into a hierarchy (tree/branch, and the Logix Blocks parent/child) Add the Bridge Module...
  • Page 13: Add The Linking Device

    Use RSLogix 5000 Software to Create a Linking Device 4. In the following screen, add a name for the module, identify the slot, add the IP address and then click OK. Add A Name Enter the IP Address Identify the Slot Click OK 5.
  • Page 14 Use RSLogix 5000 Software to Create a Linking Device 2. Select the 1757-FFLD Linking Device and click OK. 3. Add the IP Address and click OK. Publication 1757-UM010A-EN-E - January 2006...
  • Page 15: Add The Logix Blocks

    Use RSLogix 5000 Software to Create a Linking Device Add the Logix Blocks 1. Repeat the New Module procedure to add Logix Blocks to the linking device. The Logix block facilitates cascading control between a ControlLogix (CLX) environment and a fieldbus environment. The Logix block takes signals generated in either environment and sends them to the other.
  • Page 16: Configure The Linking Device And Logix Block Properties

    Use RSLogix 5000 Software to Create a Linking Device Configure the Linking Device and Logix Block Properties 1. Bring up the properties of the linking device. You see the General tab. In this tab, you can rename the linking device, add a description, set the IP address, and select the type of electronic keying you prefer.
  • Page 17 Use RSLogix 5000 Software to Create a Linking Device 3. Click on the Fieldbus tab. In this tab, you can launch RSFieldbus to configure and program your Fieldbus devices. 4. Click on the Module Info tab. In this tab, you can view the module’s identification information and module’s status.
  • Page 18 1-10 Use RSLogix 5000 Software to Create a Linking Device 5. Click on the Port Configuration tab. In this tab, you can view or set the module’s port configuration. You must be online for these details to appear. If you make any changes in this tab, you must reset the module to activate the changes.
  • Page 19 Use RSLogix 5000 Software to Create a Linking Device 1-11 1. Bring up the properties of a Logix block. You see the General tab. In this tab, you can rename the block, add a description and select the type of electronic keying you prefer. You can also enter a slot number for the block.
  • Page 20: Launch Rsfieldbus Software

    1-12 Use RSLogix 5000 Software to Create a Linking Device In the linking device properties, choose the Fieldbus tab and launch Launch RSFieldbus RSFieldbus to configure the linking device and program your field device. Software To configure and program your linking device and Foundation Fieldbus Configure the Linking devices, refer to the RSFieldbus Application Guide, publication Device and Your Field...
  • Page 21: In This Chapter

    Chapter Introduction to Function Blocks In This Chapter See Page Function Blocks Function Block Applications Function Block Parameters Function Block Links Mode Parameter (MODE_BLK) Function blocks are defined by their inputs, outputs, control parameters, and Function Blocks the algorithm that operates on these parameters. Function blocks represent the basic automation functions performed by the function block application.
  • Page 22: Function Block Parameters

    Introduction to Function Blocks Parameters define the inputs, outputs, and control data for a block. Function Block Parameters Parameter Types Parameters are defined for a specific purpose. Each is defined for use as an input, output, or control parameter. Control parameters are also referred to as contained parameters because they may not be linked with parameters in other blocks.
  • Page 23 Introduction to Function Blocks Output An output parameter is a parameter that may be linked to an input parameter of another function block. Output parameters contain status. The output status indicates the quality of the parameter value and the mode of the block when it was generated.
  • Page 24: Parameter Status

    Introduction to Function Blocks Parameter Status All input and output parameters are structures composed of status and value. Some contained parameter share that data type (for example, RCAS_IN, ROUT_IN, SP and PV). For Logix Block status codes, see Appendix C. The Status field is composed of three parts: Quality, Sub-Status, and Limits.
  • Page 25 Introduction to Function Blocks Composition of Status The Status has the following composition: Quality SubStatus Limits 43658 The quality, sub-status, and limit components of status are defined as follows: • Quality - The quality used is determined by the highest priority condition: 0 = Bad 1 = Uncertain...
  • Page 26 Introduction to Function Blocks Sub-status Values Quality Sub-status Hex Value Not In Cascade Forward Path Of Backward Path Cascade Of Cascade 0 = Non-specific 0x00 1 = Configuration Error 0x04 2 = Not Connected 0x08 3 = Device Failure 0x0C 4 = Sensor Failure 0x10 5 = No Communication, with last usable...
  • Page 27: Function Block Links

    Introduction to Function Blocks Each function block link indicates that an input parameter of one function Function Block Links block obtains its value from a specific output parameter of another function block. While function blocks pull their values from upstream blocks, which block controls the pulling depends on the characteristics of the underlying communication.
  • Page 28: Mode Types

    Introduction to Function Blocks • Supported mode - Each block type has a set of mode types supported, it means that the block definition specifies in which modes the block may operate. Mode Types These modes are found in the linking device’s function blocks: •...
  • Page 29: Mode Calculation

    Introduction to Function Blocks Mode Calculation The actual mode is calculated based on the following: Each mode type has some conditions that force the actual mode to be of higher priority than the target mode. Starting from the highest priority mode (OOS), the mode is analyzed by its corresponding conditions.
  • Page 30 2-10 Introduction to Function Blocks If the actual mode is different from the target mode, you may find the cause by analyzing corresponding conditions for the actual mode. The most frequent causes are shown below. Frequent Causes of Target Mode Deviation Mode Frequent Cause Check the resource block mode and all enumerated parameters...
  • Page 31: Chapter 3 In This Chapter

    Chapter 1757-FFLD Function Blocks The linking device supports two function blocks: resource and Logix. The In This Chapter resource block controls the linking device itself. The Logix block is used to move data between F Fieldbus devices on H1 segments and a OUNDATION Logix controller.
  • Page 32: Res - Resource Block

    1757-FFLD Function Blocks RES - Resource Block Description This block contains data specific to the linking device’s hardware. All data is modeled as contained, so there are no links to this block. The data is not processed in the way that a function block processes data, so there is no function schematic.
  • Page 33: Restart Parameter

    1757-FFLD Function Blocks RESTART Parameter The RESTART parameter allows degrees of initialization of the linking device. RESTART Parameter Values Value Reset Type Description Run is displayed while the linking device is operating normally. It returns to this value after the Restart is transmitted.
  • Page 34: Alert Notification

    1757-FFLD Function Blocks Alert Notification The MAX_NOTIFY parameter value is the maximum number of alert reports that this resource can send without getting a confirmation, corresponding to the amount of buffer space available for alert messages. The CONFIRM_TIME parameter is the time that the resource waits for 1/32 of a millisecond for confirmation of receipt of a report before trying again.
  • Page 35: Block_Err

    1757-FFLD Function Blocks BLOCK_ERR The BLOCK_ERR of the resource block indicates the following causes for the error: Device Fault State Set – When FAULT_STATE is active. Simulate Active – When the Simulate jumper is ON. Out of Service – When the block is in OOS mode.
  • Page 36 1757-FFLD Function Blocks RES Block Parameters Index Parameter Data Type Valid Range/ Default Units Edit Description (length) Options Value Mode DD_REV Unsigned8 Set by mfgr None Revision of the DD associated with the resource - used by an interface device to locate the DD file for the resource.
  • Page 37 1757-FFLD Function Blocks RES Block Parameters Index Parameter Data Type Valid Range/ Default Units Edit Description (length) Options Value Mode FAULT_STATE Unsigned8 0: Uninitialized Condition set by loss of communication to an 1: Clear output block, failure promoted to an output block 2: Active or a physical contact.
  • Page 38: Resource Function Block Options

    1757-FFLD Function Blocks Resource Function Block Options Function Block Options Meaning Description ALARM_SUM and ACK_OPTION Bits Writes have been enabled 1–6 Reserved Block alarm 8–15 Reserved CYCLE_SEL Bits Scheduled Block Execution Manufacturer Specific 3–15 Reserved CYCLE_TYPE Bits Scheduled (LSB) Completion of block execution Manufacturer specific 3–15...
  • Page 39 1757-FFLD Function Blocks Function Block Options Meaning Description Change of Bypass in an Automatic Mode If this feature is selected in FEATURE_SEL, it is allowed to write in BYPASS in an automatic mode, otherwise only in Man or OOS modes.
  • Page 40: Lgx - Logix Block

    3-10 1757-FFLD Function Blocks LGX - Logix Block Schematic 43754 Description The Logix block facilitates cascading control between a ControlLogix (CLX) environment and a fieldbus environment. The Logix block takes signals generated in either environment and sends them to the other.
  • Page 41: Block Use

    1757-FFLD Function Blocks 3-11 Block Use You can use the Logix block to send or receive 8 analog or 8 discrete signals per Logix block to or from a Logix controller. You can use up to 16 Logix blocks within a single linking device.
  • Page 42 3-12 1757-FFLD Function Blocks Examples of VCR Use Linking Device Devices VCRs Diagram 1 Subscriber 1 Publisher (internal links 2 total: 1 Publisher, Device 1 Linking Device use Link Objects rather 1 Subscriber than VCRs) FB 1 FB 2 43711...
  • Page 43 1757-FFLD Function Blocks 3-13 Examples of VCR Use Linking Device Devices VCRs Diagram 2 Publishers, 1 Publisher, 6 total: 3 Publisher, Device 1 Subscriber 2 Subscribers 3 Subscriber 43655 2 Publishers, 2 Publisher, 8 total: 4 Publisher, Linking Device 2 Subscribers...
  • Page 44: Supported Modes

    3-14 1757-FFLD Function Blocks Figure 3.1 Logix Blocks Add Extra Status in the ControlLogix Tag FF connection FF connection Value Value Status Fields in Value Value CLX Input Tag Quality WindupL Substatus WindupH InitPrimary WindupL Initializing WindupH InitPrimary InitiateFault State...
  • Page 45: Parameters

    1757-FFLD Function Blocks 3-15 Parameters See page 3-1 for parameter table descriptions. See Appendix B for data type and structure definitions LGX Block Parameters Index Parameter Data Type Valid Range/ Default Units Edit Description (length) Options Value Mode ST_REV Unsigned16...
  • Page 46 3-16 1757-FFLD Function Blocks Publication 1757-UM010A-EN-E - January 2006...
  • Page 47: Chapter 4 In This Chapter

    Chapter About the Linking Device’s Web Pages This chapter describes the Web pages and some of their basic functions. In This Chapter See Page Typical Applications Web Page Requirements Use of the Web Pages Manage the Administrator Account The linking device’s Web pages provide remote access to module data. Use the Typical Applications Web pages to: •...
  • Page 48: Web Page Requirements

    About the Linking Device’s Web Pages Web Page Requirements General Requirements Max. Number of Concurrent Users Min. Supported Display Size 1024 by 768 pixels Supported Internet Browser Internet Explorer 6.0 (with JavaScript enabled) Temporary Internet Files Settings Every visit to the page (under Tools ⇒...
  • Page 49: Use Of The Web Pages

    About the Linking Device’s Web Pages Access the Home Page of the Linking Device Use of the Web Pages In your Web browser, enter the IP address of the linking device. The Home page is displayed Navigate the Web Pages Navigate the Web pages using the navigation panel on the left of the screen.
  • Page 50 About the Linking Device’s Web Pages Tabs across the top organize specific information on each page. Select folders to open and close additional levels. Select a document to display a specific page. Select Minimize to close all folders. Select Expand to open all folders. Publication 1757-UM010A-EN-E - January 2006...
  • Page 51: Manage The Administrator Account

    About the Linking Device’s Web Pages The administrator account gives you access to the FFLD Reset, Date and Time Manage the Administrator Zone pages. These pages require the entry of a user name and password. Account Set the User Name and Password There is no default user name and password, so leaving them blank will allow others to set their own user name and password.
  • Page 52 About the Linking Device’s Web Pages The Username/Password page opens. 3. Enter the following: a. User Name b. Password (4 to 8 alphanumeric characters) c. Confirm Password 4. Click Submit or press Enter to submit the password information. The following message is displayed: Publication 1757-UM010A-EN-E - January 2006...
  • Page 53: Change The User Name And Password

    About the Linking Device’s Web Pages Change the User Name and Password To change your user name or password: 1. In your Web browser, enter the following address (where the IP address is the IP address of your linking device): The Password Warning opens.
  • Page 54: Reset The User Name And Password

    About the Linking Device’s Web Pages e. Confirm New Password 4. Click Submit or press Enter to submit the password information. The following message is displayed: Reset the User Name and Password If you forget your user name or password, you can reset them back to their default values (which are blank) by resetting the linking device to its factory defaults: See Appendix A for details on performing a reset.
  • Page 55: Chapter 5 In This Chapter

    Chapter Diagnostic Web Pages This chapter describes the diagnostic Web pages of the linking device. In This Chapter See Page H1 Live List VCR Pages Ethernet Pages Diagnostic Log Files The H1 Live List is a list of devices on the linking device’s network. Each port H1 Live List on the linking device is listed as a separate network and the linking device appears as a device on each network list.
  • Page 56 The device’s fieldbus address. Function The fieldbus function to which the device is set: • Bridge - The 1757-FFLD linking device • Link Master - A device should not appear as a link master. If one does, change it to Basic.
  • Page 57: Vcr Pages

    Diagnostic Web Pages VCR Pages VCR Overview For each H1 channel there is a maximum of 16 publisher and 16 subscriber VCRs. The VCR Overview page indicates this maximum number and also indicates how many of each are currently in use on the H1 channels. If you exceed the maximum number of VCRs, this page will IMPORTANT continue to show a total of 16 VCRs used.
  • Page 58: Hse And H1 Vcr Diagnostics

    Diagnostic Web Pages HSE and H1 VCR Diagnostics Rockwell Automation Technical Support can use the VCR Statistics pages to diagnose VCR issues in your fieldbus system. For information on specific VCR entries, refer to the F Fieldbus Specification, document FF-007. OUNDATION The HSE VCR Entry tab has a pull-down menu that displays the HSE VCRs that are in use.
  • Page 59: Ethernet Pages

    Diagnostic Web Pages Ethernet Pages Ethernet Network Settings The Ethernet Network Settings page provides a summary of the current Ethernet configuration of the linking device. This summary includes: • Ethernet address details • Ethernet network configuration Ethernet Network Settings Page Field Description Network Interface...
  • Page 60: Ethernet Statistics

    Diagnostic Web Pages Ethernet Statistics The Ethernet Statistics page provides a summary of the status of communication activity on the Ethernet network. This summary includes: • Ethernet network configuration • packets sent and received over the Ethernet network • frames sent and received over the Ethernet network You can set the refresh rate for the Ethernet Statistics at the bottom of the page.
  • Page 61 Diagnostic Web Pages Ethernet Statistics Page Field Description Ethernet Link Speed Indicates if the Ethernet port is operating at 10 Mbps or 100 Mbps Interface Counters In Octets Octets received on the Ethernet interface In Ucast Packets Unicast packets received on the Ethernet interface In NUcast Packets Non-unicast packets received on the Ethernet interface In Discards...
  • Page 62: Diagnostic Log Files

    Diagnostic Web Pages The Web Server Log provides a log of recent requests to the Web pages. It lists Diagnostic Log Files when the request was made, from which IP address the request came, and a description of what was requested. Publication 1757-UM010A-EN-E - January 2006...
  • Page 63 Diagnostic Web Pages The FFLD log provides a log of recent activities in the linking device. This information may be useful to Technical Support in order to diagnose issues in your linking device. It lists when the activity occurred and a description of the activity.
  • Page 64 5-10 Diagnostic Web Pages Publication 1757-UM010A-EN-E - January 2006...
  • Page 65: Chapter 6 In This Chapter

    Chapter Advanced Diagnostics and Hidden Web Pages This chapter describes the Advanced Diagnostics and Hidden Web pages of In This Chapter the linking device. See Page Advanced Diagnostics Hidden Pages Advanced Diagnostics The first time you access the Configure H1\HSE Captures IMPORTANT page you must have the linking device’s IP address listed as a Trusted/Safe site or your Internet Security level set to...
  • Page 66 Advanced Diagnostics and Hidden Web Pages The Configure H1\HSE Captures page is used to save H1 and HSE information from the linking device to a file. Rockwell Automation Technical Support can use this information to diagnose issues with your H1s and HSE. If you leave the Web page or close the browser, you will IMPORTANT stop the capture process and corrupt the captured data.
  • Page 67: H1 Captures

    Advanced Diagnostics and Hidden Web Pages H1 Captures An H1 capture is in 256k blocks and the file size increases by 256k. Also, an H1 capture saves the data of all 4 ports. To capture information about fieldbus communication on a linking device H1 port: 1.
  • Page 68 Advanced Diagnostics and Hidden Web Pages 5. Specify the time and size: a. To capture for a specific amount of time, enter a Capture Time and Size. If the file size is reached before the time elapses, the capture will stop. b.
  • Page 69: Hse Captures

    Advanced Diagnostics and Hidden Web Pages HSE Captures To capture information about the communications between the computer and the linking device, an additional driver must be installed. Refer to Knowledgebase Tech Note ID G128737547 at http://support.rockwellautomation.com/ for more information. HSE captures are in 5k blocks and the file size increases by 5k. Only one computer connection to the linking device at a time, is allowed for captures.
  • Page 70: Reset The Linking Device

    Advanced Diagnostics and Hidden Web Pages 2. Verify the Current Date and Time, and click Go to Home Page. If you configured these settings using the RSFieldbus IMPORTANT SNTP Time Server, they will override the date and time. The time zone settings will be maintained on the Web pages.
  • Page 71 Advanced Diagnostics and Hidden Web Pages To Reset Configuration: 1. Select Reset Configuration and click Submit. A Warning opens. 2. Click Continue if you still want to Reset Configuration. The linking device reboots and the browser closes. AB Drives Publication 1757-UM010A-EN-E - January 2006...
  • Page 72 Advanced Diagnostics and Hidden Web Pages To Reset to Factory Defaults: 1. Select Reset to Factory Defaults and click Submit. A Warning opens. You must assign the IP address after performing this reset. IMPORTANT For details on assigning the IP address, refer to publication 1757-IN021, Foudation Fieldbus Linking Device Installation Instructions.
  • Page 73 Appendix Troubleshoot the Linking Device In This Chapter See Page 1757-FFLD LED Indicators Reset the Linking Device 1757-FFLD LED Indicators State Description Recommended Action The linking device H1 channel Verify that the linking device is is inactive. connected to the H1 network.
  • Page 74: Reset The Linking Device

    Troubleshoot the Linking Device State Description Recommended Action NS (network Not Powered, Verify that power is supplied. status) No IP Address Assign an IP address. Flashing No Connections Verify that the linking device is Green connected to the fieldbus network. Green CIP Connections None...
  • Page 75: Reset Configuration

    Troubleshoot the Linking Device Reset Configuration The Reset Configuration removes power from the linking device’s battery, deleting all downloaded fieldbus configurations. The linking device retains its network configuration and Web page password information through this reset. To perform a Reset Configuration, follow the steps below: 1.
  • Page 76: Reset To Factory Default

    Troubleshoot the Linking Device Reset to Factory Default The factory-default reset sets the linking device’s network configuration to use BOOTP, erases Web page password information, and clears all downloaded fieldbus configurations. To complete a factory-default reset: 1. Verify that the linking device is powered up and in a running state (H1 LEDs are blinking).
  • Page 77: Appendix B Data Types

    Appendix Data Types and Data Structures This appendix defines data types and data structures used in the linking device function blocks. Data Types Data Type Description Unsigned8 1 byte Unsigned16 2 bytes Unsigned32 4 bytes FloatingPoint 4 bytes VisibleString 1 byte per character (includes the 7 bit ASCII character set) OctetString Octet strings are binary BitString...
  • Page 78: Data Structures

    Data Types and Data Structures Data Structures DS-65 - Value & Status (Floating Point Structure) This data structure consists of the value and status of floating point parameters that are Inputs or Outputs. Value & Status - Floating Point Structure - DS-65 Element Name Data Type Size (bytes)
  • Page 79: Ds-70 - Access Permissions

    Data Types and Data Structures DS-70 - Access Permissions This data structure consists of access control flags for access to block parameters. Access Permissions - DS-70 Element Name Data Type Size (bytes) Grant Bit String Deny Bit String DS-72 - Discrete Alarm Structure This data structure consists of data that describes discrete alarms.
  • Page 80: Ds-74 - Alarm Summary Structure

    Data Types and Data Structures DS-74 - Alarm Summary Structure This data structure consists of data that summarizes 16 alerts. Alarm Summary Structure - DS-74 Element Name Data Type Size (bytes) Current Bit String Unacknowledged Bit String Unreported Bit String Disabled Bit String DS-85 - Test Structure...
  • Page 81: Appendix C Input Parameters

    Appendix Fieldbus Status Codes for RSLogix 5000 Projects The status codes in this appendix are in the controller tags of an RSLogix 5000 project. Input Parameters FFLD1:0:I.In[0].xxxxxx Fieldbus Status Logix Status - FFLD1:0:I.In[0].xxxxxx Quality Sub-status Limits Quality Substatus WindupL WindupH Init Initializing Initiate...
  • Page 82 Fieldbus Status Codes for RSLogix 5000 Projects FFLD1:0:I.In[0].xxxxxx Fieldbus Status Logix Status - FFLD1:0:I.In[0].xxxxxx Quality Sub-status Limits Quality Substatus WindupL WindupH Init Initializing Initiate Primary Fault State No Comm with Not Limited (cont.) last usable value Low Limited High Limited Constant No Comm with no Not Limited...
  • Page 83 Fieldbus Status Codes for RSLogix 5000 Projects FFLD1:0:I.In[0].xxxxxx Fieldbus Status Logix Status - FFLD1:0:I.In[0].xxxxxx Quality Sub-status Limits Quality Substatus WindupL WindupH Init Initializing Initiate Primary Fault State Uncertain Initial Value Not Limited Low Limited High Limited Constant Sensor Not Limited Conversion not Low Limited Accurate...
  • Page 84 Fieldbus Status Codes for RSLogix 5000 Projects FFLD1:0:I.In[0].xxxxxx Fieldbus Status Logix Status - FFLD1:0:I.In[0].xxxxxx Quality Sub-status Limits Quality Substatus WindupL WindupH Init Initializing Initiate Primary Fault State Good Active Advisory Not Limited Non- Alarm Low Limited Cascade High Limited Constant Active Critical Not Limited Alarm...
  • Page 85 Fieldbus Status Codes for RSLogix 5000 Projects FFLD1:0:I.In[0].xxxxxx Fieldbus Status Logix Status - FFLD1:0:I.In[0].xxxxxx Quality Sub-status Limits Quality Substatus WindupL WindupH Init Initializing Initiate Primary Fault State Good Non-Specific Not Limited Cascade Low Limited High Limited Constant Initialization Not Limited Acknowledge Low Limited High Limited...
  • Page 86 Fieldbus Status Codes for RSLogix 5000 Projects FFLD1:0:I.In[0].xxxxxx Fieldbus Status Logix Status - FFLD1:0:I.In[0].xxxxxx Quality Sub-status Limits Quality Substatus WindupL WindupH Init Initializing Initiate Primary Fault State Good Fault State Active Not Limited Cascade Low Limited High Limited Constant Initiate Fault Not Limited State Low Limited...
  • Page 87: Output Parameters

    Fieldbus Status Codes for RSLogix 5000 Projects Output Parameters FFLD1:0:O.Out[0].xxxxxx Fieldbus Status Logix Status - FFLD1:0:O.Out[0].xxxxxx Quality Sub-status Limits WindupL WindupH Init Primary Initializing Initiate Fault State Fault State Good Non-Specific Not Limited Cascade Low Limited High Limited Constant Initialization Not Limited Acknowledge Low Limited...
  • Page 88 Fieldbus Status Codes for RSLogix 5000 Projects Publication 1757-UM010A-EN-E - January 2006...
  • Page 89 Glossary We use these terms and acronyms throughout the document. Term Definition AUTO Automatic Automatic Without Link block see function block block tag a character string name that uniquely identifies a block on a fieldbus network Cascade contained an internal parameter that can not be linked to other function blocks or devices (i.e., it does not parameter have a pin) deterministic...
  • Page 90 The linking device’s Web pages provide remote access to module data. Use the Web pages to access diagnostic information, monitor linking device data, or to view the VCRs and H1 Live List. 1757-FFLD Foundation Fieldbus Linking Device, or simply, linking device. An HSE node that connects either two or four H1 segments to an HSE network and to the EtherNet/IP network.
  • Page 91 Index Numerics 1756-ENBT capture 1757-FFLD 1-10 configure with field devices definition of example system definition of factory defaults change user name and password function blocks composition of status LED indicators configure controller purpose I/O module Web pages 1-12 linking device and field devices...
  • Page 92 Index Ethernet Network Settings page captures pages data Statistics page definition of Ethernet Statistics page diagnostics LED status event update structure Live List example refresh rate linking device system H1 field device Explorer files settings definition of H1/HSE Captures page hidden pages factory defaults fault state...
  • Page 93 Index linking device 1-12 configure with field devices name configure with logix block properties limitations factory defaults your Logix 5000 project LED indicators network purpose definition of Web pages network status LED links non-volatile parameters function block normal element of mode parameter definition of logical link definition of...
  • Page 94 Index RSLogix 5000 Software add devices quality add linking device values add the logix blocks create a project for the controller create your I/O configuration fieldbus status codes refresh rate related documentation remote cascade mode timeout requirements schematic Web page 3-10 logix block reset...
  • Page 95 Index values WDOG status sub-status Web pages 3-11 administrator account definition of date and time zone diagnostics definition of 3-11 examples of hidden maximum requests overview requirements pages use to reset the linking device Web server log write lock AB Drives Publication 1757-UM010A-EN-E - January 2006...
  • Page 96 Index Publication 1757-UM010A-EN-E - January 2006...
  • Page 97 ___No, there is no need to contact me ___Yes, please call me ___Yes, please email me at _______________________ ___Yes, please contact me via _____________________ Return this form to: Rockwell Automation Technical Communications, 1 Allen-Bradley Dr., Mayfield Hts., OH 44124-9705 AB Drives Fax: 440-646-3525 Email: [email protected]...
  • Page 98 PLEASE FASTEN HERE (DO NOT STAPLE) Other Comments PLEASE FOLD HERE NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES BUSINESS REPLY MAIL FIRST-CLASS MAIL PERMIT NO. 18235 CLEVELAND OH POSTAGE WILL BE PAID BY THE ADDRESSEE 1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705...
  • Page 99 AB Drives...
  • Page 100 Rockwell Automation provides technical information on the Web to assist you in using Rockwell Automation its products. At http://support.rockwellautomation.com, you can find technical Support manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.

Table of Contents