Gv3 Series Ground Fault Specifications; Locking The Reset Pin - Bosch D9412GV3 Installation Instructions Manual

Hide thumbs Also See for D9412GV3:
Table of Contents
Control Panels
1.5.4

GV3 Series Ground Fault Specifications

Table 1.1, Page 7 provides the impedance specifications for detecting ground faults when any
terminal or field wiring is shorted to ground.
Impedance
≤ 300 Ω
300 Ω to 200 k Ω
≥ 200 k Ω
Table 1.1 Ground Fault Impedance Specifications
1.5.5

Locking the Reset Pin

Locking the reset pin disables the control panel (refer to Figure 1.3, Page 7). When the control
panel is disabled, the system ignores the keypads and points. CALL FOR SERVICE appears in
keypad displays when the pin is locked down.
On-board relays (Terminals 6 and 7) and off-board relays deactivate when the control panel is
reset. Terminal 8 has power when the relay is deactivated. Activation interrupts power at that
terminal. The on-board relay (Terminal 8) remains deactivated when the reset pin is locked in
the disable position.
Releasing the reset pin from the closed position resets the control panel. The control panel
resets all its timers, counters, indexes, and buffers. Any points that restore after a reset do
not generate Restoral Reports.
If the reset pin is placed in the disable position when all areas are armed, there must be an
entry in the Answer Armed program item. Refer to RPS Parameters in the D9412GV3/
D7412GV3 Program Entry Guide (P/N: F01U170807) or the D7212GV3 Program Entry Guide (P/
N: F01U170808).
Locking the pin in the disable position applies power to the control panel and charges the
battery while the detection devices and keypads are installed.
When the Reset Switch (labeled S1) is closed, the communication module at SDI Address 92
is disabled. While in this mode, remote programming communication is only supported by the
communication module at SDI Address 88.
Figure 1.3 Reset Pin
Callout
Description
1
Reset pin locked (closed)
2
Reset pin normal (open)
Bosch Security Systems, Inc.
Control Panel Detects Ground Fault
Yes
Detection depends upon the terminal
No
UL Installation Instructions
Installation | en
7
F.01U.167.105 | 02 | 2010.11