Siemens DXR2.E10PL-102BK Installation Instruction
Siemens DXR2.E10PL-102BK Installation Instruction

Siemens DXR2.E10PL-102BK Installation Instruction

Smoke control compliant actuating dxr

Quick Links

s
Product Numbers
985-124
Accessories
Smoke Control Compliance
Parts for Smoke Control Compliance
Smoke Control Listed Small Equipment
Controller Enclosure
Smoke Control Listed Large Equipment
Controller Enclosure
UL Listed Class 2 transformer with
120Vac 50/60 HZ 0.5A primary with hub
and 24 Vac 96VA
Smoke Control Compliance
The following instructions and information apply if used for
smoke control sequence.
1
Install Smoke Control Listed products, enclosure and trans-
former (see Parts for Smoke Control Compliance section for
more information).
2
Input Rating:
- 24V 60 HZ 72 VA
3
Digital Output (DO) are the only I/O suitable for smoke con-
trol application. Digital Output (DO) Electrical Ratings:
24 Vac, 6VA per DO/maximum 40 VA total.
4
Connection from the DXR2 to the field panel is a maximum
4000 feet, 24 AWG minimum.
Siemens Industry, Inc.
499 OHM Resistor Assembly Kit
540-155K ,
540-155D
550-002K
TR100VA004
A6V11416604
Smoke Control Compliant
Actuating DXR
DXR2.E10PL-102BK
DXR2.E10PLX-102BK
DXR2.M10PL-102BK
DXR2.M10PLX-102BK
Installation Instruction
5
Wiring Range:
- Transformer: primary 14 AWG
- 24 Vac Input Power: 14 to 18 AWG
- DO: AI: 18 to 20 AWG
- DI: 18 AWG
- LAN: 20 to 24 AWG
6
KNX port (11 and 12) not used or connected for smoke
control application
All circuits are power limited; FLN is RS-485 or
Ethernet.
See the following documents for more information on
configuring smoke control applications:
Smoke Control Systems Application and Engi-
neering Manual (125-1806)
Smoke Control System Application Guide
(125-1816)
NFPA and UL Standards Relevant to Smoke
Control System Application Guide (125-1817)
NOTE:
The 24 Vac relay module is not
applicable for smoke control
application.
A6V11416604
2018-07-11 1 / 4
loading

Summary of Contents for Siemens DXR2.E10PL-102BK

  • Page 1 24 Vac, 6VA per DO/maximum 40 VA total. The 24 Vac relay module is not applicable for smoke control application. Connection from the DXR2 to the field panel is a maximum 4000 feet, 24 AWG minimum. Siemens Industry, Inc. A6V11416604 2018-07-11 1 / 4...
  • Page 2 Dimension 2 / 4 2018-07-11 A6V11416604 Siemens Industy, Inc.
  • Page 3 Hollow metal shafts: use provided insert Determine damper blade rotation. Attach mounting bracket. Using the manual override switch, move the adjustment le- ver to the proper position.  Clockwise = left  Counterclockwise = right Siemens Industry, Inc. A6V11416604 2018-07-11 3 / 4...
  • Page 4 Wiring MS/TP 4 / 4 2018-07-11 A6V11416604 Siemens Industy, Inc.

This manual is also suitable for:

Dxr2.e10plx-102bkDxr2.m10pl-102bkDxr2.m10plx-102bk