Installation Instructions
Kinetix 5500 Feedback Connector Kit
Catalog Number 2198-KITCON-DSL
About the Feedback Connector Kit
This feedback connector kit includes a two-pin connector plug that accepts feedback wires from
the 2090-CS M1DF- AA
connector housing with the connector plug wired and properly positioned. In addition, you must
align the cable shield and insulation. The housing cover includes a grounding plate, and when
mated with the bottom half, provides a high-frequency bond with the cable shield.
Refer to the Kinetix® 5500 Servo Drives User Manual, publication 2198-UM001, for more
information.
Install the Feedback Connector Kit
Connector
Plug
Mounting Screws (2)
Feedback Cable Preparation, mm (in.)
10
(0.39)
single motor cable. You must assemble the bottom half of the
Retention Rib
Connector Housing
(bottom half)
Position cable shield here for optimum
bond with grounding plate.
Position cable insulation here for proper strain relief.
EPWR+, Blue
25
EPWR-, White
8
(0.98)
(0.31)
Connector Plug
Removed
Follow these steps to assemble the connector kit.
1. Insert wires into plug (observe polarity).
2. Position connector plug as shown.
3. Align braided shield as shown to maximize contact
for high-frequency bond.
4. Align outer insulation of feedback cable as shown
for proper strain relief.
5. Fit cover tab into bottom-half mating feature,
keeping the plug pushed forward past retention rib
as the cover is closed.
6. Tighten cover screws to recommended torque.
Cover should close with no gaps.
Pressure on the end of connector plug should not
push plug back into connector housing.
Cover Tab
Housing
Cover
Grounding Plate