Honeywell P7640A Installation Instructions
Honeywell P7640A Installation Instructions

Honeywell P7640A Installation Instructions

Differential pressure sensors

Quick Links

P7640A,B
Differential Pressure Sensors
APPLICATION
The P7640A Panel Mount and P7640B Duct Mount
Differential Pressure Sensors provide reliable, accurate
measurement and control. Proper applications include
measurement of extremely low pressure applications such
as: building/room pressure, air flow, variable air volume,
filter status, and duct pressure. They are ideal for clean
rooms, hospitals, fume hoods, and computer rooms.
The P7640 Pressure Sensors are designed with field-
selectable 4-20 mA, 0-5 Vdc, or 0-10 Vdc output. The four
pressure ranges fall between 0–1 in. w.c./0–250 Pa or 0–
10 in. w.c./0–2500 Pa, depending on the model.
Accessory
32003169-001 Duct Pressure Pick-up Probe, 4 in.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check ratings given in instructions and on the
product to ensure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.
Mounting
Screw holes are accessed inside the enclosure (with the
cover removed) and are located in the upper left and
lower right corners.
Panel Mount
Run tubing from one (static) or both (differential) barb
fittings, making sure the typically higher pressure source
is connected to the port labeled HI, and the typically
lower pressure source is connected to the port labeled
LO.

INSTALLATION INSTRUCTIONS

Duct Mount
The units with the integral probe should typically be
mounted at the high pressure location when used for
differential control.
CONFIGURATION
Select the proper output, mode, and pressure range
using the switches and jumpers:
1. Select output using the output switch:
a. Current: mA (then skip to step 3), or
b. Voltage: Volt.
2. Select 0-10 Vdc or 0-5 Vdc using jumper J4.
3. Select bi- or uni-directional mode using jumper J5.
NOTE: Setting for 0 to 1 in. w.c. and bi-directional
will give output from -1.0 to 1.0 in. w.c.
4. Select inches w.c. or Pascal scale using jumper J7.
5. Select fast or standard response time using jumper
J8.
6. Select appropriate full-scale pressure range using
the rotary switch. Align arrow (not the slot) to the
desired range. See Table 2 for the range selection
guide.
NOTE: Note that either the 1 in. w.c. or 10 in. w.c.
scale is marked. This is the available
scale for that given model. When the
range is changed, the LCD models
momentarily indicate selected range.
7. Set output according to Table 1.
Table 1. Controller Compatibility
and Output Settings.
Controller
W7750, W7760, W7761
4-20 mA
W7750B, W7760C,
0-10 Vdc (default)
W7753, W7760
Non-Honeywell
0-5 Vdc
Required Sensor
L
S
ON
Output Setting
Setting
FilterPress or
P7610B
FilterPress or
P7610F, or voltage
n/a
62-0210-07
PEC
loading

Summary of Contents for Honeywell P7640A

  • Page 1: Installation Instructions

    INSTALLATION INSTRUCTIONS APPLICATION Duct Mount The units with the integral probe should typically be The P7640A Panel Mount and P7640B Duct Mount mounted at the high pressure location when used for Differential Pressure Sensors provide reliable, accurate differential control. measurement and control. Proper applications include...
  • Page 2 P7640A,B DIFFERENTIAL PRESSURE SENSORS WIRING (FIG. 1 THROUGH 3) CAUTION CAUTION Equipment Damage Hazard. Equipment Damage Hazard. Can damage the device beyond repair. Can damage the device beyond repair. Disconnect power supply before installation. Do not apply power to output terminal. Permanent equipment damage will result.
  • Page 3 P7640A,B DIFFERENTIAL PRESSURE SENSORS OPERATION Table 2. Range Selection Guide. IMPORTANT 1-in. Models 10-in. Models Rotary During the first few minutes of operation, read- Switch 0–1 0–250 0–10 0–2500 ings at zero pressure and lowest pressure Position in. w.c. Pascal in.
  • Page 4 Fig. 4. Wiring for voltage (Vdc) output. LonSpec™ is a trademark of Echelon® Corporation. By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’...