Siemens CDC-4 Installation Instructions Manual
Siemens CDC-4 Installation Instructions Manual

Siemens CDC-4 Installation Instructions Manual

Conventional detector card

Installation Instructions

Model CDC-4
Conventional Detector Card
INTRODUCTION
OPERATION
P/N 315-034200-9
The Model CDC-4 from Siemens Industry, Inc., is a card that
allows conventional detectors to be used on the FireFinder-XLS
system. It provides four Class A or Class B conventional detec-
tion zones. Each zone can support two-wire photoelectric or
ionization compatible smoke detectors and an unlimited number
of normally open circuit closure devices. The module also
supports Siemens Fire Safety flame and beam detectors. The
relay base, remote lamp and audible base may also be used with
the CDC-4. The CDC-4 uses one network address on the
FireFinder-XLS system. It has diagnostic LED indicators showing
module status and the status of each zone.
Activation of any device on the circuit initiates a zone alarm and
causes any previously programmed functions to operate. Any
circuit in an alarm or trouble condition is displayed on the PMI/
PMI-2/PMI-3.
The CDC-4 is designed to function in a local degrade mode
during failure of the FireFinder-XLS main processor or during
the loss of the system communication network. While in the
degrade mode, the CDC-4 can report both alarm and trouble
conditions and can activate local outputs on other modules
within the same enclosure.
The maximum zone alarm current can be set to either 175mA
or 100mA and is set in pairs for zones 1/2 and 3/4. When a
compatible detector is selected in the Zeus Programming Tool,
the maximum zone alarm current is automatically set by the
CDC-4. Detectors requiring the 100mA zone current limit (see
table on page 11) cannot be used on the same zone pair as
detectors requiring the 175mA zone current limit (see table on
pages 7-11).
CDC-4 zones may be configured either as alarm-causing or
supervisory-causing, if allowed by the local Authority Having
Jurisdiciton.
Do not use shorting devices on circuits with accessories on them. The shorting
devices will lower the zone voltage to a point where the accessories will not operate.
Figure 1
CDC-4 Conventional
Detector Card
Siemens
Siemens Industry
Siemens
Industry
Industry, , , , , Inc.
Siemens
Siemens
Industry
Building
Building
Building
Building T T T T T ec
Building
ec
ec
ec
echnologies Di
hnologies Division
hnologies Di
hnologies Di
hnologies Di
Industry
Inc.
Inc.
Inc.
Inc.
vision
vision
vision
vision
Table of Contents
loading

Summary of Contents for Siemens CDC-4

  • Page 1: Installation Instructions

    Model CDC-4 Conventional Detector Card INTRODUCTION The Model CDC-4 from Siemens Industry, Inc., is a card that allows conventional detectors to be used on the FireFinder-XLS system. It provides four Class A or Class B conventional detec- tion zones. Each zone can support two-wire photoelectric or ionization compatible smoke detectors and an unlimited number of normally open circuit closure devices.
  • Page 2 Version 2.0 and above firmware are only compatible with PC board P/N 580-034888. If version 2.0 or above firmware is uploaded into the older version of the CDC-4, the PMI/PMI-2/PMI-3 displays “ROM SW Version Error” . The PC board revision number is printed on the back of the CDC-4 board.
  • Page 3 HUNDREDS front panel. (Refer to Figure 1 for the location of the switches.) The address for the CDC-4 must be the same as the address selected for it in the Zeus Programming TENS Tool. To set the address, turn the pointers on each of the three dials to the numbers ONES for the selected address.
  • Page 4 Remove all system power before installation, first battery, then AC. (To power up, connect the AC first, then the battery.) All device field wiring to the CDC-4 is connected to the terminal blocks of the CC-5 card cage slot in which it is installed.
  • Page 5 1. All circuits can be Class A or 9. Only one device accessory Class B. per circuit is guaranteed to activate on the CDC-4. 2. All circuits are power limited to NFPA 70 per NEC 760. 10. When mixing different model detectors on a zone, 3.
  • Page 6: Installation

    INSTALLATION The CDC-4 plugs perpendicularly into one slot in the CC-5 card-cage via two 96-pin DIN connectors and can occupy any slot in the card cage. (Refer to Figure 4.) Insert the CDC-4 card into the card guides rightside up (lettering on the front panel is legible).
  • Page 7: Electrical Ratings

    ELECTRICAL RATINGS i t i a t l Siemens Industry, Inc. P/N 315-034200-9 Building Technologies Division...
  • Page 8 UL COMPATIBLE TWO-WIRE DETECTORS The detectors listed in the following tables are compatible with the CDC-4 (UL identifier CDC). The CDC-4 and all Siemens detectors shown below are ULC listed. Contact the manufacturer for listing information on models other than Siemens.
  • Page 9 Siemens Industry, Inc. P/N 315-034200-9 Building Technologies Division...
  • Page 10 Siemens Industry, Inc. P/N 315-034200-9 Building Technologies Division...
  • Page 11 Siemens Industry, Inc. P/N 315-034200-9 Building Technologies Division...
  • Page 12 Siemens Industry, Inc. P/N 315-034200-9 Building Technologies Division...
  • Page 13: Cyber Security Disclaimer

    CYBER SECURITY DISCLAIMER Siemens products and solutions provide security functions to ensure the secure operation of building comfort, fire safety, security management and physical security systems. The security functions on these products and solutions are important components of a comprehensive security concept.
  • Page 14 Siemens Industry, Inc. Siemens Canada, Ltd. Document ID A6V10239127 P/N 315-034200-9 Building Technologies Division 1577 North Service Road East Florham Park, NJ Oakville, Ontario L6H 0H6 Canada...

Table of Contents