Step 2: Replacing The Control Panel And Changing Over To Fdnet Protocol; Replacing The Control Panel Or Installing A Line Card - Siemens FDOOT241-9 Technical Manual

Modernizing fire detection installations with multiple protocol detectors
Hide thumbs Also See for FDOOT241-9:
Table of Contents
4
Undertaking modernization

Step 2: Replacing the control panel and changing over to FDnet protocol

4.2 Step 2: Replacing the control panel and changing
4.2.1
26
Building Technologies
Fire Safety
Collective detector lines
On a collective detector line, the detector is not set to test mode if the detector
group is switched to 'Test' on the control panel.
Detectors on a collective detector line are switched to test mode for 3 minutes in
the following cases:
Starting up and resetting the detector line.
l
Inserting the detector.
l
Removing the detector from the detector line and re-inserting it.
l
To trigger a detector using test gas, normally 2...4 gas discharges at intervals of
approx. 2 seconds are required. When the detector is in test mode, activation
takes place after approximately 10 seconds.
MS8/PMT and AnalogPLUS detector lines
On an MS8/PMT or AnalogPLUS detector line, the detector is not set to test mode
if the detector or the detector group is switched to 'Test' on the control panel.
Unlike on a collective detector line, the detector must not be removed from the
detector line for a short time and re-inserted. Testing without a detector exchanger
and tester is therefore difficult, especially with smoke detectors.
In AnalogPLUS mode, you can use the detector exchanger and tester to select
parameter set 12, which has a short response time.
See also
2 Test methods [➙ 25]
2 'SIGMALOOP' detector family [➙ 23]
over to FDnet protocol

Replacing the control panel or installing a line card

During modernization we would recommend replacing the existing fire control panel
with a Sinteso FC20xx control panel.
In the case of the 'AlgoRex' and 'SIGMASYS' product lines, a line card (FDnet) can
be fitted in the existing fire control panel (E3M141, FDC).
Control panel
AlgoRex
SIGMASYS
Line card
E3M141
FDC
Order number
S54405-A9-A1
S54230-B150-A2
A6V10323158_d_en_--
2015-04-09
Table of Contents
loading

This manual is also suitable for:

Fdoot241-8Fdoot241-a4Fdoot241-a3Fdoot241-a5Fdoot241a9

Table of Contents