10.4 RAMPS & BRAKES SETUP (CONTROL PANEL: MENU PAR -> P4)
4.1
R
AMP SHAPE
4.10
R
S
AMP
HAPE
The start and end of the acceleration and deceleration ramp can be smoothed
with this parameter. Setting value 0 gives a linear ramp shape which causes
acceleration and deceleration to act immediately to the changes in the refer-
ence signal.
Setting value 0.1...10 seconds for this parameter produces an S-shaped ac-
celeration/deceleration. The acceleration and deceleration times are deter-
mined with parameters 4.2 and 4.3.
[Hz]
P4.2, 4.3
Figure 10.6: S-shaped acceleration/deceleration
4.2
A
CCELERATION
4.3
D
ECELERATION
4.11
A
CCELERATION
4.12
D
ECELERATION
These limits correspond to the time required for the output frequency to accel-
erate from the zero frequency to the set maximum frequency, or to decelerate
from the set maximum frequency to zero frequency.
The user can set two different acceleration/deceleration time sets for one ap-
plication. The active set can be selected with the selected digital input (par.
5.13).
Parameter Descriptions
2
P4.1
P4.1
T
IME
T
IME
T
2
IME
T
2
IME
63