Vacon NXP User Manual

Vacon NXP User Manual

Frequency converters, shaft synchronization
Hide thumbs Also See for NXP:
Table of Contents
nx frequency converters
shaft synchronization
application apfiff11
user's manual
Table of Contents
loading

Summary of Contents for Vacon NXP

  • Page 1 nx frequency converters shaft synchronization application apfiff11 user's manual...
  • Page 2 2 • vacon ABOUT THE SHAFT SYNCHRONIZATION APPLICATION MANUAL Congratulations for choosing the Smooth Control provided by Vacon NX Frequency Converters! This manual is available in both paper and electronic editions. We recommend you to use the elec- tronic version if possible. If you have the electronic version at your disposal you will be able to bene-...
  • Page 3: Table Of Contents

    Keypad control (Control keypad: Menu M3)................31 6.12.1 System menu (Control keypad: Menu M6)..............31 6.12.2 Expander boards (Control keypad: Menu M7) ............31 Description of parameters ....................32 Keypad control parameters...................... 85 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 4 4 • vacon shaft synchronization application Application specific variables in the monitor menu and fieldbus interface ......86 Shaft Synchronization operation ..................87 Shaft Synchronization fieldbus interface ................. 90 Appendices........................91 Closed loop parameters (ID’s 612 to 621) ................91 9.1.1...
  • Page 5: Introduction

    NOTE: The Shaft Synchronization application creates a rigid electrical coupling between master and follower(s) axis. The application is not suitable if there is a rigid mechanical coupling between master and follower(s). 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 6: Requirements

    Trial time is very useful for test and evaluation. If FC has to be replaced during a weekend there is 2 weeks trial time for free and during that time a new license can be ordered from Vacon. After loading the application it will be possible to run in Shaft synchronization mode without license...
  • Page 7: Control I/O

    More information in the product's User's Manual. CMB connected to GND CMA connected to GND CMB isolated from GND CMA isolated from GND CMB and CMA internally connected together, isolated from GND = Factory default 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 8: Connection Of Signals Between Master And Follower Drive (Opt-A7)

    8 • vacon connection of signals between master and follower CONNECTION OF SIGNALS BETWEEN MASTER AND FOLLOWER DRIVE (OPT-A7) NOTE: To eliminate the risk of electrical noise, use only double shielded twisted pair cable for connections. Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205...
  • Page 9: Jumper Setting On The Opt-A7 Board

    OPT-A7 board (or OPT-BC if resolver board is used). Pulses per revolution for follower channel 2 (P7.3.1.4 Enc 2 Pulse/rev for OPT-A7) should normally be set equals to Master encoder pulses/rev. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 10: Terminal To Function" (Ttf) Programming Principle

    The programming principle of the input and output signals in the Multipurpose Control Application as well as in the Pump and Fan Control Application (and partly in the other applications) is differ- ent compared to the conventional method used in other Vacon NX applications. In the conventional programming method, Function to Terminal Programming Method (FTT), have a fixed input or output that you define a certain function for.
  • Page 11: Defining A Terminal For A Certain Function With Ncdrive Programming Tool

    Be ABSOLUTELY sure not to connect two functions to one and same output in order to avoid function overruns and to ensure flawless operation. WARNING inputs outputs Note: The , unlike the , cannot be changed in RUN state. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 12: Defining Unused Inputs/Outputs

    12 • vacon "terminal to function" (ttf) programming principle Defining unused inputs/outputs All unused inputs and outputs must be given the board slot value 0 and the value 1 also for the ter- minal number. The value 0.1 is also the default value for most of the functions. However, if you want to use the values of a digital input signal for e.g.
  • Page 13: Shaft Synchronization Application - Parameter Lists

    Trial time left Displays accumulated position V1.24 Accum Space Error 1803 error when follower not running in synch. mode. Displays three selectable G1.25 Multimonitoring items monitoring values Table 2. Monitoring values 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 14: Basic Parameters (Control Keypad: Menu M2 G2.1)

    14 • vacon shaft synchronization application – parameter lists Basic parameters (Control keypad: Menu M2 G2.1) Code Parameter Unit Default Cust Note NOTE: If f > than the motor synchronous speed, P2.1.1 Max frequency Par. 2.1.1 320,00 50,00 check suitability for motor and drive system P2.1.2...
  • Page 15: Input Signals

    20,00 0,00 hysteresis P2.2.2.9 AI1 joystick offset -50,00 50,00 0,00 Table 5. Analogue input 1 parameters, G2.2.2 *Remember to place jumpers of block X2 accordingly. See NX User's Manual, chapter 6.2.2.2 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 16: Analogue Input 2 (Control Keypad: Menu M2 G2.2.3)

    16 • vacon shaft synchronization application – parameter lists 6.3.3 Analogue input 2 (Control keypad: Menu M2 G2.2.3) Code Parameter Unit Default Cust Note P2.2.3.1 AI2 signal selection P2.2.3.2 AI2 filter time 0,00 10,00 0,10 0=No filtering 0=0…100%* 1=20…100%* P2.2.3.3 AI2 signal range 2= -10V…+10V*...
  • Page 17: Digital Inputs (Control Keypad: Menu M2 G2.2.5)

    Synch. trim - 1714 ratio in run mode Hardware feedback from P2.2.5.24 Brake Opened Ack 1602 mechanical brake. Table 8. Digital input signals, G2.2.4 cc = closing contact oc = opening contact 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 18: Output Signals

    18 • vacon shaft synchronization application – parameter lists Output signals 6.4.1 Delayed digital output 1 (Keypad: Menu M2 G2.3.1) Code Parameter Unit Default Cust Note Digital output 1 P2.3.1.1 signal selection 0=Not used 1=Ready 2=Run 3=Fault 4=Fault inverted 5=FC overheat warning 6=Ext.
  • Page 19: Digital Output Signals (Control Keypad: Menu M2 G2.3.3)

    Table 11. Digital output signals, G2.3.3 Be ABSOLUTELY sure not to connect two functions to one and same output in order to avoid function overruns and to ensure flawless operation. WARNING 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 20: Limit Settings (Control Keypad: Menu M2 G2.3.4)

    20 • vacon shaft synchronization application – parameter lists 6.4.4 Limit settings (Control keypad: Menu M2 G2.3.4) Code Parameter Unit Default Cust Note 0=No limit Output frequency 1=Low limit supervision P2.3.4.1 limit 1 supervision 2=High limit supervision 3=Brake-on control Output frequency P2.3.4.2...
  • Page 21: Analogue Output 1 (Control Keypad: Menu M2 G2.3.5)

    1=Inverted Analogue output 2 0=0 mA P2.3.6.5 minimum 1=4 mA Analogue output 2 P2.3.6.6 1000 scale Analogue output 2 P2.3.6.7 -100,00 100,00 0,00 offset Table 14. Analogue output 2 parameters, G2.3.6 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 22: Analogue Output 3 (Control Keypad: Menu M2 G2.3.7)

    22 • vacon shaft synchronization application – parameter lists 6.4.7 Analogue output 3 (Control keypad: Menu M2 G2.3.7) Code Parameter Unit Default Cust Note Analogue output 3 P2.3.7.1 signal selection Analogue output 3 P2.3.7.2 See par. 2.3.5.2 function Analogue output 3 P2.3.7.3...
  • Page 23: Drive Control Parameters (Control Keypad: Menu M2 G2.4)

    600,00 0,00 0=DC brake is off at start at start 0=Off P2.4.12 Flux brake 1=On P2.4.13 Flux braking current 0,4 x I 2 x I Table 17. Drive control parameters, G2.4 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 24: Motor Control Parameters (Control Keypad: Menu M2 G2.5)

    24 • vacon shaft synchronization application – parameter lists Motor control parameters (Control keypad: Menu M2 G2.5) Code Parameter Unit Default Cust Note 0=Frequency control 1=Speed control 2=Torque control 3=Closed loop speed ctrl Motor control P2.5.1 4=Closed loop torque ctrl mode 5=Adv.
  • Page 25: Pmsm Settings (Control Keypad: Menu M2 G2.5.19)

    0 position Enable Rs identification P2.5.19.5 EnableRsIdentific during DC brake at start Modulaton index limit at P2.5.19.6 ModIndexLimit field weakening point Table 19. Parameters for permanent magnet synchronous motor, G2.5.19 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 26: Protections (Control Keypad: Menu M2 G2.6)

    26 • vacon shaft synchronization application – parameter lists Protections (Control keypad: Menu M2 G2.6) Code Parameter Unit Default Cust Note 0=No response 1=Warning Response to 4mA 2=Warning+Prev. Freq. P2.6.1 reference fault 3=Wrng+PresetFreq 2.7.2 4=Fault,stop acc. to 2.4.7 5=Fault,stop by coasting 4mA reference fault P2.6.2...
  • Page 27 Only for Vacon personnel. Possibility to change P2.6.27 Disable stop lock 1086 parameters in run state when this parameter is set to 1. Table 20. Protections, G2.6 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 28: Fieldbus Parameters (Control Keypad: Menu M2 G2.7)

    28 • vacon shaft synchronization application – parameter lists Fieldbus parameters (Control Keypad: Menu M2 G2.7) Code Parameter Unit Default Cust Note Fieldbus data out 1 Choose monitoring data P2.7.1 10000 selection with parameter ID Fieldbus data out 2 Choose monitoring data P2.7.2...
  • Page 29: Torque Control Parameters (Control Keypad: Menu M2 G2.8)

    2=Preset speed 7 Minimum frequency P2.8.8 for open loop 0,00 par.2.1.1 3,00 torque control Torque controller P2.8.9 32000 P gain Torque controller P2.8.10 32000 I gain Table 22. Torque control parameters, G2.8 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 30: Shaft Synchronization Parameters (Control Keypad: Menu M2 G2.9)

    30 • vacon shaft synchronization application – parameter lists 6.10 Shaft synchronization parameters (Control keypad: Menu M2 G2.9) Code Parameter Unit Default Cust Note MASTER settings group 2.9.1 (See separate section)ettings Master distance in user P2.9.1.1 Master distance 32767 1750...
  • Page 31: License Key (Control Keypad: Menu M2 G2.10)

    Expander boards (Control keypad: Menu M7) The M7 menu shows the expander and option boards attached to the control board and board- related information. For more information, see the product's User's Manual. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 32: Description Of Parameters

    32 • vacon shaft synchronization application DESCRIPTION OF PARAMETERS On the following pages you will find the parameter descriptions arranged according to the individual ID number of the parameter. A shaded parameter ID number (e.g. 418 Motor potentiometer UP TTF programming method...
  • Page 33 The frequency converter starts to search for the minimum motor current in order to save energy, lower the disturbance level and the noise. This function can be used in applications with constant motor load, such as fans, pumps etc. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 34 34 • vacon description of parameters U/f optimisation (2.5.2) Automatic The voltage to the motor changes automatically which makes the motor torque boost produce sufficient torque to start and run at low frequencies. The voltage increase depends on the motor type and power. Automatic torque boost can be used in applications where starting torque due to starting friction is high, e.g.
  • Page 35 Applic. Sel. Analogue volt.ref. Terminals 2–3 Analogue curr.ref. Terminals 4–5 AI1+AI2 AI1–AI2 AI2–AI1 AI1*AI2 AI1 joystick AI2 joystick Keypad reference (Menu M3) Fieldbus reference* Table 28. Selections for parameter ID121 *FBSpeedReference 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 36 36 • vacon description of parameters Fieldbus frequency reference selection (2.1.12) Defines which frequency reference source is selected when controlled from the fieldbus. For selections in different applications, see ID121. Jogging speed reference (2.1.13) Defines the jogging speed selected with the DIN3 digital input which can be programmed for Jogging speed.
  • Page 37 Note: This will not, however, change the reference scaling. Reset Press button to change the parameter value back to 0,00%. AI2 joystick offset (2.2.3.9) See par. ID165. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 38 38 • vacon description of parameters Fieldbus input data 4 (FBFixedControlWord, bit 6) (2.3.3.26) Fieldbus input data 5 (FBFixedControlWord, bit 7) (2.3.3.27) The data from the fieldbus (FBFixedControlWord) can be led to frequency converter digital outputs. Start/Stop logic selection (2.2.1.1)
  • Page 39 Run Enable (Run Enable = False) or when the control place is changed. The Start/Stop contact must be opened before the motor can be started. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 40 40 • vacon description of parameters 4 DIN1: closed contact = start forward DIN2: closed contact = reference increases (motor potentiometer reference; this parameter is automatically set to 4 if par. ID117 is set to 3 or 4). 5 DIN1: closed contact = start forward (Rising edge required to start)
  • Page 41 Defines the signal minimum to either 0 mA or 4 mA (living zero). Note the difference in analogue output scaling in parameter ID311 (Figure 8-15). 0 Set minimum value to 0 mA 1 Set minimum value to 4 mA 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 42 3 = Fault A fault trip has occurred 4 = Fault inverted A fault trip not occurred 5 = Vacon overheat warning The heat-sink temperature exceeds +70°C 6 = External fault or warning Fault or warning depending on par. ID701 Fault or warning depending on par.
  • Page 43 Selects the frequency value supervised by parameter ID315. See Figure 11. f[Hz] ID315 = 2 ID316 Example: 21 RO1 21 RO1 21 RO1 22 RO1 22 RO1 22 RO1 23 RO1 23 RO1 23 RO1 NX12K19 Figure 11. Output frequency supervision 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 44 44 • vacon description of parameters AI1 signal range (2.2.2.3) Applic. ASFIFF06 Sel. 0…100% 20…100% –10…+10V Customised Table 33. Selections for parameter ID320 For selection 'Customised', see parameters ID321 and ID322. AI1 custom setting minimum (2.2.2.4) AI1 custom setting maximum (2.2.2.5)
  • Page 45 2) depending on to which output the supervision signals (par. ID447 and ID448) are connected (applications 6 and 7). Output frequency limit 2 supervision value (2.3.4.4) Selects the frequency value supervised by parameter ID346. See Figure 11. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 46 46 • vacon description of parameters Torque limit, supervision function (2.3.4.5) 0 = No supervision 1 = Low limit supervision 2 = High limit supervision 3 = Brake-off control (See chapter Error! Reference source not found. on page Error! Bookmark not defined.)
  • Page 47 AI1 signal selection (2.2.2.1) Connect the AI1 signal to the analogue input of your choice with this parameter. For more information about the TTF programming method, see chapter 5 on page 10. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 48 48 • vacon description of parameters AI1 joystick hysteresis (2.2.2.8) This parameter defines the joystick hysteresis between 0 and 20 %. When the joystick or potentiometer control is turned from reverse to forward, the output frequency falls linearly to the selected minimum frequency (joystick/potentiometer in middle position) and stays there until the joystick/potentiometer is turned towards the forward command.
  • Page 49 (2.2.4.1) 0 = Not used 1 = AI1 2 = AI2 3 = Fieldbus This signal will adjust the maximum motor current between 0 and max. limit set with parameter ID107. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 50 50 • vacon description of parameters Start signal 1 (2.2.5.1) Signal selection 1 for the start/stop logic. Default programming A.1. Start signal 2 (2.2.5.2) Signal selection 2 for the start/stop logic. Default programming A.2. External fault (close) (2.2.5.11) Contact closed: Fault is displayed and motor stopped.
  • Page 51 Acceleration/Deceleration prohibited (2.2.5.14) Contact closed: No acceleration or deceleration possible until the contact is opened. DC-braking (2.2.5.15) Contact closed: In STOP mode, the DC braking operates until the contact is opened. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 52 52 • vacon description of parameters Motor potentiometer DOWN (2.2.5.8) Contact closed: Motor potentiometer reference DECREASES until the contact is opened. Motor potentiometer UP (2.2.5.9) Contact closed: Motor potentiometer reference INCREASES until the contact is opened. Preset speed 1 (2.2.5.5) Preset speed 2 (2.2.5.6)
  • Page 53 (2.3.3.21) Motor thermistor initiates a overtemperature signal which can be led to a digital output. NOTE: This parameter will not work unless you have Vacon OPT-A3 or OPT-B2 (thermistor relay board) connected. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 54 54 • vacon description of parameters Motor regulator activation (2.3.3.22) Overvoltage or overcurrent regulator has been activated. Fieldbus input data 1 (FBFixedControlWord, bit 3) (2.3.3.23) Fieldbus input data 2 (FBFixedControlWord, bit 4) (2.3.3.24) Fieldbus input data 3 (FBFixedControlWord, bit 5) (2.3.3.25)
  • Page 55 Figure 17. Digital outputs 1 and 2, on- and off-delays Digital output 2 signal selection (2.3.2.1) See ID486. Digital output 2 function (2.3.2.2) See ID312. Digital output 2 on-delay (2.3.2.3) See ID487. Digital output 2 off-delay (2.3.2.4) See ID488. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 56 56 • vacon description of parameters Acceleration/Deceleration ramp 1 shape (2.4.1) Acceleration/Deceleration ramp 2 shape (2.4.2) The start and end of acceleration and deceleration ramps can be smoothed with these parameters. Setting value 0 gives a linear ramp shape which causes acceleration and deceleration to act immediately to the changes in the reference signal.
  • Page 57 If the regenerated energy is high it may be necessary to use an external braking resistor for faster deceleration. DC-braking current (2.4.8) Defines the current injected into the motor during DC-braking. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 58 58 • vacon description of parameters DC-braking time at stop (2.4.9) Determines if braking is ON or OFF and the braking time of the DC-brake when the motor is stopping. The function of the DC-brake depends on the stop function, parameter ID506.
  • Page 59 (parameters ID509 and ID510). The ramping speed (selected acceleration/ deceleration time 1 or 2) is multiplied with this factor. E.g. value 0.1 makes the acceleration time 10 times shorter than outside the prohibit frequency range limits. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 60 60 • vacon description of parameters fout [Hz] Par. ID518 = 0,2 Par. ID510 (ID512; ID514) Par. ID509 Par. ID518 = 1,2 (ID511; ID513) Time [s] NX12k81 Figure 22. Ramp speed scaling between prohibit frequencies Flux braking current (2.4.13) Defines the flux braking current value. This value can be set between 0.4*I and the Current limit.
  • Page 61 0041—0062 NX_6 0144—0208 NX_6 Table 35. Size-dependent switching frequencies Field weakening point (2.5.4) The field weakening point is the output frequency at which the output voltage reaches the set (ID603) maximum value. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 62 62 • vacon description of parameters Voltage at field weakening point (2.5.5) Above the frequency at the field weakening point, the output voltage remains at the set maximum value. Below the frequency at the field weakening point, the output voltage depends on the setting of the U/f curve parameters.
  • Page 63 See chapter 9.1. Load drooping (2.5.15) The drooping function enables speed drop as a function of load. This parameter sets that amount corresponding to the nominal torque of the motor. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 64 64 • vacon description of parameters CL: Startup torque (2.6.18.11) Choose here the startup torque. Torque Memory is used in crane applications. Startup Torque FWD/REV can be used in other applications to help the speed controller. See chapter 9.1. 0 = Not Used...
  • Page 65 Defines the I gain for the speed controlled in Open Loop control mode. Torque controller P gain (2.8.9) Defines the P gain of the torque controller. Torque controller I gain 2.8.10) Defines the I gain of the torque controller. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 66 66 • vacon description of parameters Torque reference selection (2.8.4) Defines the source for torque reference. 0 Not used 1 Analogue input 1 2 Analogue input 2 3 Analogue input 3 4 Analogue input 4 5 Analogue input 1 (joystick) 6 Analogue input 2 (joystick) 7 From keypad, parameter R3.5...
  • Page 67 If tripping is selected the drive will stop and activate the fault stage. Deactivating the protection, i.e. setting parameter to 0, will reset the thermal stage of the motor to 0%. See chapter 9.2. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 68 68 • vacon description of parameters Motor thermal protection: Motor ambient temp. factor (2.6.9) The factor can be set between -100.0%—100.0%. See chapter 9.2. Motor thermal protection: Motor cooling factor at zero speed (2.6.10) The current can be set between 0—150.0% x I .
  • Page 69 Nominal current of motor is changed, this Stall area parameter is automatically restored to the default value (I ). See chapter 9.3. Par. ID710 Par. ID712 NX12k63 Figure 25. Stall characteristics settings 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 70 70 • vacon description of parameters Stall time (2.6.15) Stall time counter This time can be set between 1.0 and 120.0s. Trip area This is the maximum time allowed for a Par. ID711 stall stage. The stall time is counted by an Trip/warning internal up/down counter.
  • Page 71 ID718. = No automatic restart after reference fault trip >0 = Number of automatic restarts after the analogue current signal (4…20mA) has returned to the normal level (>4mA) 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 72 (2.20) The Automatic restart is taken into use with this parameter. 0 = Disabled 1 = Enabled The function resets the following faults (max. three times) (see Vacon NX User’s Manual, Chapter 9): • Overcurrent (F1) • Overvoltage (F2) • Undervoltage (F9) •...
  • Page 73 If you have a PT100 input board installed in your frequency converter you can choose here the number of PT100 inputs in use. See also the Vacon I/O boards manual. Note: If the selected value is greater than the actual number of used PT100 inputs, the display will read 200ºC.
  • Page 74 74 • vacon description of parameters Fieldbus reference minimum scaling (2.9.1) Fieldbus reference maximum scaling (2.9.2) Use these two parameters to scale the fieldbus reference signal. ≤ ≤ ≤ Setting value limits: 0 par. ID850 ID851 ID102. If par. ID851 = 0 custom scaling is not used and the minimum and maximum frequencies are used for scaling.
  • Page 75 Motor control status word Monitor variables Output frequency 0.01 Hz Frequency reference 0.01 Hz Motor speed 1 rpm Filtered motor current Size dependent Filtered motor torque 0.1% of motor nominal torque 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 76 76 • vacon description of parameters Motor power 0.1% of motor nominal power Motor voltage 0.1 V DC link voltage Unit temperature 1 ° C Motor temperature 1 % of nominal overtemperature Analogue input 1 1 count = 1/10000 of...
  • Page 77 P2.10.1. (Possible to run in Shaft Synchronization mode 2 weeks without license key during Trial Time) Please request the appropriate key of your Vacon representative according to your license agreement. The data you shall specify to obtain your key are −...
  • Page 78 78 • vacon description of parameters Parameters for mechanical brake control 1535 Freq Limit brake open, OL (2.3.8.3) Frequency limit for brake open in open loop control. Frequency reference is also limited to this value until brake is opened 1539 Close Freq Limit (2.3.8.7)
  • Page 79 P2.3.8.6 is used for releasing of reference if this input is not used. 1680 Torque reference selection (2.7.12) Selector that maps the Torque reference to one process data input channel. Values the same as in ID1742. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 80 80 • vacon description of parameters 1681 Free signal selection (2.7.13) Selector that maps “Free analog input” to one process data input channel. Use of “Free analogue input” is determined by parameters ID399 and ID485. Values the same as in ID1742.
  • Page 81 The actual position of the follower drive is monitored with a symmetrical error band of +/- P2.6.21 around the reference position. 1732 Power unit temperature sensor supervision The temperature supervision of the power unit can be disabled by setting this parameter to 1. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 82 82 • vacon description of parameters 1733 Encoder supervision (2.6.23) Encoder fault software mode supervision 0= Enabled 1= Disabled Encoder fault supervision is based on hardware detection of missing individual signals plus a software supervision that can detect if a cable is disconnected. Software super- vision may cause nuisance trips if the drive runs against the current limit at standstill.
  • Page 83 (2.9.2.3) Number of motor shaft turns corresponding to the distance specified in engineering units [u] by ID1757 and ID1758 for the follower drive. Integer part. 1760 Follower TurnsFrac * 2^16 (2.9.2.4) 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 84 84 • vacon description of parameters Number of motor shaft turns corresponding to the distance specified in engineering units [u] by ID1757 and ID1758 for the follower drive. Fractional part x 2 1761 Follower speed filter TI (2.9.2.5) Time constant [s] of the 1st order low-pass filter on follower speed measurement.
  • Page 85: Keypad Control Parameters

    3 seconds when you are on any of the pages of menu For more information, see the product's User's Manual. R3.5 Torque reference (3.5) Define here the torque reference within 0.0…100.0%. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 86: Application Specific Variables In The Monitor Menu And Fieldbus Interface

    86 • vacon description of parameters Application specific variables in the monitor menu and fieldbus interface 1700 Monitoring value: ActualRatio * 2^16 (V1.17) Actual value of ratio after the ramp. 65536 counts = unity ratio. 1701 Monitoring value: Position error (V1.18)
  • Page 87: Shaft Synchronization Operation

    In general: The gear ratio between Master and Follower can be changed during running in synchronization mode with par. ID1765 or by the register in the Fieldbus control Figure 30. Ratio control (in Run mode) 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 88 88 • vacon shaft synchronization operation M a s t e r s p e e d S l a v e s p e e d S y n c e n g a g e d o u t p u t...
  • Page 89 The maximum frequency is the speed limit during phasing. Acceleration/Deceleration during phasing command is same as for engage/release synchronization See P2.9.2.8 Sync Acceleration. Velocity phase velocity master velocity time Position Master pos “seen” by follower Phasing distance time 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 90: Shaft Synchronization Fieldbus Interface

    90 • vacon shaft synchronization operation Change of gear ratio during run: The ratio of the follower to the master speed and position can be dynamically changed by a ramped, high resolution ratio control. Ratio can be changed by P2.9.2.9 from keypad.
  • Page 91: Appendices

    Thus, the squirrel cage induction machine can be controlled in a fashion of a separately excited DC motor. Note: These parameters can be used with Vacon NXP drive only. EXAMPLE:...
  • Page 92: Parameters Of Motor Thermal Protection (Id's 704 To 708)

    Parameters of motor thermal protection (ID’s 704 to 708): General The motor thermal protection is to protect the motor from overheating. The Vacon drive is capable of supplying higher than nominal current to the motor. If the load requires this high current there is a risk that the motor will be thermally overloaded.
  • Page 93: 10. Shaft Synchronization Application Specific Fault Codes

    CH2. 12. Set parameters for mechanical brake in G2.3.8 If mechanical brake is used. Also program a digital output ID445/ID446 for controlling the brake and eventual input, ID1602 for hardware acknowledgement. 24-hour support +358 (0)40 837 1150 • Email: [email protected]...
  • Page 94 Vaasa Helsinki Vacon Traction Oy Vacon Oyj (Headquarters and Production) Vacon Oyj Vehnämyllynkatu 18, 33560 Tampere Runsorintie 7, 65380 Vaasa Äyritie 12, 01510 Vantaa tel. +358 (0)201 2121 [email protected] tel. +358 (0)201 212 600 fax: +358 (0)201 212 710 tel. +358 (0) 201 2121...

Table of Contents