en | Planning Information
zones associated with the address. If either the D7030X-S2 or the D7030X-S8 is used instead
of a D7030X on an address, the user is responsible to program the first two or eight zones for
that address to Supervisory zones.
The Power and Trouble LEDs on a D7030X copy the status of the corresponding LEDs on the
panel keypad.
See also
3.4.2

SLC Address Assignment

The standard control panel supports one Signaling Line Circuit (SLC) for up to 254 detectors
and modules, or up to 127 analog sounder bases in combination with a suitable detector, for a
total of 254 addressable device capacity per SLC.
For a list of permitted address ranges for SLCs, see the following table.
Device Category
Detector
Contact Monitor
Module
Relay Module
2017.11 | 2.0 | F.01U.173.607
Modules, page 16
Device Group Type
SMOKE-M
SMOKE-P
HEAT
SMOKE-I
SMOKE-D
CONT‑MOD
RELAY-MOD
Installation and Operation Guide
Type Number
FAP-440-T
FAP-440-TC
FAP-440-DT
FAP-440-DTC
FAP-325
FAP-325-V2F
FAP-440
FAP-440-D
FAH-325
FAH-440
FAI-325
FAD-325-DH
FAD-325-V2F-DH
FLM-325-2I4
FLM-325-IM
FLM-325-I4
FLM-325-I4-A
FLM-325-I4-AI
D328A
FLM-325-2R4-2A
FLM-325-2R4-2AI
FLM-325-2R4-8A
FLM-325-2R4-8AI
Analog fire panels
Address Range
1-254
1-254
1-254
1-254
1-127
1-254
1-254
1-254
1-127
1-254
1-127
1-127
1-254
1-127
1-254
1-127
1-254
1-254
1-127
1-254
1-254
1-254
1-254
Bosch Security Systems, Inc.
Table of Contents
loading

This manual is also suitable for:

Fpa-1000-v2

Table of Contents