Commissioning
7.3 Initial configuration of an Open Controller
Establish HMI connection
1. Right-click the WinCC RT Advanced in the device view.
2. Start the HMI device wizard.
3. Apply all default settings.
The wizard creates system images for you with the corresponding navigation.
4. Switch to the connection view in the network view.
5. Click on WinCC RT Advanced.
6. Drag (with mouse button pressed) from the WinCC RT Advanced software to the S7-1500
software controller (for example, CPU 1505SP).
A network connection is established between the two devices.
Downloading the project to the target system
The complete PC station is downloaded the first time you download the configuration.
1. Select the complete PC system in the device view.
2. Click the "Download to device" button.
3. Make the following settings:
– Type of connection
– Specify the interface of the programming device
– Specify the X2 interface on the Open Controller
Note
The first TIA Portal download must be via the "X2" interface.
Only ASCII characters are permitted in the name of the interface X2 PN/IE (LAN) in the
TIA Portal, e.g. PROFINET_2.
Download and compile the project. The hardware configuration and the first download are
now completed.
WinCC RT Advanced
WinCC Runtime Advanced contains all the essential functions for operator control and
monitoring of machinery or plants.
Reference
For more information on WinCC RT Advanced, refer to the WinCC Advanced V14
(http://support.automation.siemens.com/WW/view/en/109742297) system manual.