Interrupt Module; Installation And Wiring - Mitsubishi QX10 User Manual

I/o module type building block. melsec q series
Table of Contents
1
GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

1.2.5 Interrupt module

1.2.6 Installation and wiring

1 - 16
(1) If setting the response time during the interrupt input operation of QI60 or QX40H,
QX70H, QX80H, and QX90H, use the module whose contents are shown below.
The response time cannot be set with other contents (fixed at 0.2ms.).
Product
CPU module
GX Developer
For how to check product information of the CPU module, refer to the QCPU User's
Manual (Hardware Design, Maintenance and Inspection).
(1) Solderless terminal with insulation sleeve
A solderless terminal with insulation sleeve cannot be used for a terminal block.
It is recommended that the junction of a solderless terminal and a cable should be
covered up with a cable tag or an insulation tube.
(2) Applicable wire
Use wires of 0.3 to 0.75mm
block. When using a wire whose core is 0.75mm or more, it is preferable to use the
spring clamp terminal block (Q6TE-18S, Q6TE-18SN).
(3) Tightening torque range
Tighten screws (such as a module fixing screw) within the following torque range.
Screw location
Module fixing screw (M3 12 screw)
Terminal block screw (M3 screw)
Terminal block mounting screw (M3.5 screw)
Connector screw (M2.6 screw)
Description
Product information "021120000000000-B" or later
SW6D5C-GPPW or later
2
core and 2.8mm OD max. to connect to the terminal
MELSEC-Q
Tightening torque range
0.36 to 0.48 N•m
0.42 to 0.58 N•m
0.66 to 0.89 N•m
0.20 to 0.29 N•m
1 - 16