4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE
Once the template has been applied, users are limited to edit the settings specified by the template, but all settings are
shown. The effect of applying the template to the phase time overcurrent settings is shown below.
4
Phase time overcurrent settings window without template applied.
Figure 4–6: APPLYING TEMPLATES VIA THE VIEW ALL SETTINGS COMMAND
e) REMOVING THE SETTINGS TEMPLATE
It can be necessary at some point to remove a settings template. Once a template is removed, it cannot be reapplied and it
is necessary to define a new settings template.
1.
Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2.
Select the Template Mode > Remove Settings Template option.
3.
Enter the template password and click OK to continue.
4.
Verify one more time that you want to remove the template by clicking Yes.
The EnerVista software removes all template information and all settings are available.
The UR allows users to secure parts or all of a FlexLogic equation, preventing unauthorized viewing or modification of criti-
cal FlexLogic applications. This is accomplished using the settings template feature to lock individual entries within Flex-
Logic equations.
Secured FlexLogic equations remain secure when files are sent to and retrieved from any UR-series device.
a) LOCKING FLEXLOGIC EQUATION ENTRIES
The following procedure describes how to lock individual entries of a FlexLogic equation.
1.
Right-click the settings file or online device and select the Template Mode > Create Template item to enable the set-
tings template feature.
2.
Select the FlexLogic > FlexLogic Equation Editor settings menu item.
4-8
Phase time overcurrent window with template applied via
the
Template Mode > View All Settings
The template specifies that only the
settings be available.

4.1.6 SECURING AND LOCKING FLEXLOGIC EQUATIONS

F60 Feeder Protection System
4 HUMAN INTERFACES
command.