SiBE041525F 1. Safety Cautions..................vi 1.1 Warnings and Cautions Regarding Safety of Workers......vi 1.2 Warnings and Cautions Regarding Safety of Users......viii 2. Icons Used ....................x Part 1 - List of Functions..............1 1. Functions....................2 Part 2 - Specifications..............4 1.
Page 5
SiBE041525F Part 5 - Remote Controller ............40 1. Remote Controller .................41 Part 6 - Service Diagnosis ............43 1. General Problem Symptoms and Check Items ........44 2. Troubleshooting with LED ..............45 2.1 Indoor Unit....................45 2.2 Outdoor Unit ...................45 3. Service Diagnosis .................46 4.
Page 6
SiBE041525F Part 7 - Trial Operation and Field Settings ........90 1. Tips for Servicing ..................91 1.1 Pump Down Operation ................91 1.2 Forced Cooling Operation ..............91 2. Trial Operation ..................92 3. Field Settings ..................93 3.1 Temperature Display Switch ..............93 3.2 When 2 Units are installed in 1 Room ............93 4.
SiBE041525F Safety Cautions 1. Safety Cautions Be sure to read the following safety cautions before conducting repair work. After the repair work is complete, be sure to conduct a test operation to ensure that the equipment operates normally, and explain the cautions for operating the product to the customer.
Page 8
Safety Cautions SiBE041525F Warning Do not turn the air conditioner on or off by plugging in or unplugging the power cable. Plugging in or unplugging the power cable to operate the equipment may cause an electrical shock or fire. Be sure to wear a safety helmet, gloves, and a safety belt when working in a high place (more than 2 m).
SiBE041525F Safety Cautions Caution Conduct welding work in a well-ventilated place. Using a welder in an enclosed room may cause oxygen deficiency. Warnings and Cautions Regarding Safety of Users Warning Do not store the equipment in a room with fire sources (e.g., naked flames, gas appliances, electric heaters).
Page 10
Safety Cautions SiBE041525F Warning Do not mix air or gas other than the specified refrigerant (R-32 / R-410A / R-22) in the refrigerant system. If air enters the refrigerant system, an excessively high pressure results, causing equipment damage and injury. If the refrigerant gas leaks, be sure to locate the leaking point and repair it before charging the refrigerant.
SiBE041525F Icons Used Caution Check the earth / grounding, and repair it if the equipment is not properly earthed / grounded. Improper earth / grounding may cause an electrical shock. Be sure to measure insulation resistance after the repair, and make sure that the resistance is 1 MΩ...
Indoor Unit SiBE041525F 1. Indoor Unit 20/25/35 Class Control PCB (PCB1) 1) S6 Connector for swing motor (horizontal blade) 2) S26 Connector for display PCB 3) S32 Connector for indoor heat exchanger thermistor 4) S200 Connector for DC fan motor 5) H1, H2, H3, FG Connector for terminal board 6) FU1 Fuse (3.15 A, 250 V)
Page 19
SiBE041525F Indoor Unit Display PCB (PCB2) 1) S27 Connector for control PCB 2) SW1 (S1W) Forced cooling operation ON/OFF button * Refer to page 91 for details. 3) LED1 (H1P) LED for operation (green) 4) LED2 (H2P) LED for timer (yellow) 5) RTH1 (R1T) Room temperature thermistor LED2 LED1...
Indoor Unit SiBE041525F 50/60/71 Class Control PCB (PCB2) 1) S6 Connector for swing motor (horizontal blade) 2) S26 Connector for display PCB 3) S32 Connector for indoor heat exchanger thermistor 4) S200 Connector for DC fan motor 5) S900 Connector for filter PCB S200 S900 3P380931-1...
Page 21
SiBE041525F Indoor Unit Filter PCB (PCB1) 1) S100 Connector for terminal board 2) S800 Connector for control PCB 3) FG, HE Connector for ground 4) FU1 Fuse (3.15 A, 250 V) 5) V2 Varistor S800 S100 3P380932-1 Display PCB (PCB3) 1) S27 Connector for control PCB 2) SW1 (S1W)
Page 22
Indoor Unit SiBE041525F Remote Control PCB (BR069) S602 S601 To optional wired remote controller BRC073 and BRP069 To connector S403 of control PCB (PCB1) Printed Circuit Board Connector Wiring Diagram...
SiBE041525F Outdoor Unit 2. Outdoor Unit 20/25/35 Class Main PCB (PCB1) 1) S20 Connector for electronic expansion valve coil 2) S30 Connector for compressor motor 3) S40 Connector for overload protector 4) S71 Connector for DC fan motor 5) S80 Connector for four way valve coil 6) S90 Connector for thermistors...
Outdoor Unit SiBE041525F 50/60/71 class Main PCB 1) S20 Connector for electronic expansion valve coil 2) S40 Connector for overload protector 3) S70 Connector for DC fan motor 4) S80 Connector for four way valve coil (heat pump model only) 5) S90 Connector for thermistors (outdoor temperature, outdoor heat exchanger, discharge pipe)
SiBE041525F Part 4 Functions and Control 1. Main Functions..................15 1.1 Temperature Control ................15 1.2 Frequency Principle................15 1.3 Airflow Direction Control.................17 1.4 Fan Speed Control for Indoor Unit ............18 1.5 Program Dry Operation ................19 1.6 Automatic Operation................20 1.7 Thermostat Control.................21 1.8 NIGHT SET Mode ..................22 1.9 ECONO Operation .................22 1.10 Inverter POWERFUL Operation .............23 1.11 Other Functions..................24...
Main Functions SiBE041525F 1. Main Functions Temperature Control The definitions of temperatures are classified as following. Definitions of Temperatures Room temperature: temperature of lower part of the room Set temperature: temperature set by remote controller Room thermistor temperature: temperature detected by room temperature thermistor ...
Page 27
SiBE041525F Main Functions The following drawing shows a schematic view of the inverter principle: Refrigerant circulation rate (high) high speed Amount of heat Amount of heat exchanged air (large) exchanged air (large) high f low f Amount of heat Amount of heat exchanged air (small) exchanged air (small) low speed...
Main Functions SiBE041525F Airflow Direction Control The large flap sends a large volume of air downward to the floor and provides an optimum Power-Airflow control in cooling, dry, and heating operation. Flap Cooling / Dry During cooling or dry operation, the flap retracts into the indoor unit. Then, cool air can be blown far and distributed all over the room.
SiBE041525F Main Functions Fan Speed Control for Indoor Unit Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H, and HH. Outline The airflow rate can be automatically controlled depending on the difference between the room thermistor temperature and the target temperature.
Main Functions SiBE041525F Program Dry Operation Program dry operation removes humidity while preventing the room temperature from lowering. Outline Since the microcomputer controls both the temperature and airflow rate, the temperature adjustment and FAN setting buttons are inoperable. The microcomputer automatically sets the temperature and airflow rate. The difference between Detail the room thermistor temperature at start-up and the target temperature is divided into two zones.
SiBE041525F Main Functions Automatic Operation Outline Automatic Cooling / Heating Function When the automatic operation is selected with the remote controller, the microcomputer automatically determines the operation mode as cooling or heating according to the room temperature and the set temperature at start-up. The unit automatically switches the operation mode to maintain the room temperature at the set temperature.
Main Functions SiBE041525F Thermostat Control Thermostat control is based on the difference between the room thermistor temperature and the Outline target temperature. Detail Thermostat OFF Condition The temperature difference is in the zone A. Thermostat ON Conditions The temperature difference returns to the zone C after being in the zone A. ...
SiBE041525F Main Functions NIGHT SET Mode When the OFF TIMER is set, NIGHT SET Mode is automatically activated. NIGHT SET Mode Outline keeps the airflow rate setting. NIGHT SET Mode continues operation at the target temperature for the first one hour, then Detail automatically raises the target temperature slightly in cooling, or lowers it slightly in heating.
Main Functions SiBE041525F 1.10 Inverter POWERFUL Operation In order to exploit the cooling and heating capacity to full extent, the air conditioner can be Outline operated by increasing the indoor fan rotating speed and the compressor frequency. When the POWERFUL button is pressed, the fan speed and target temperature are converted Detail to the following states for 20 minutes.
SiBE041525F Main Functions 1.11 Other Functions 1.11.1 Hot-Start Function In order to prevent the cold air blast that normally occurs when heating operation is started, the temperature of the indoor heat exchanger is detected, and the airflow is either stopped or significantly weakened resulting in comfortable heating.
Thermistor Functions SiBE041525F 2. Thermistor Functions Electronic expansion valve Four way valve Compressor (R14247) 1. The outdoor heat exchanger thermistor is used for controlling the target discharge pipe (1) Outdoor Heat temperature. The system sets the target discharge pipe temperature according to the Exchanger outdoor and indoor heat exchanger temperature, and controls the electronic expansion valve Thermistor...
SiBE041525F Control Specification 3. Control Specification Mode Hierarchy The air conditioner control has normal operation mode, forced operation mode, and power Outline transistor test mode for installation and servicing. Detail Air conditioner control mode Forced operation mode Forced cooling operation (for pump down operation) Power transistor test mode Normal operation mode Cooling (includes drying)
Control Specification SiBE041525F Frequency Control The compressor frequency is determined according to the difference between the room Outline thermistor temperature and the target temperature. When the shift of the frequency is less than zero (ΔF<0) by PI control, the target frequency is used as the command frequency. Dropping function Input current control, etc.
Page 39
SiBE041525F Control Specification When starting the compressor, the frequency is initialized according to the ∆D value of the Initial Frequency indoor unit. ∆D signal: Indoor Frequency Command The difference between the room thermistor temperature and the target temperature is taken as the ∆D value and is used for ∆D signal of frequency command.
Control Specification SiBE041525F Controls at Mode Changing / Start-up 3.3.1 Preheating Control The inverter operation in open phase starts with the conditions of the outdoor temperature, the Outline discharge pipe temperature, the radiation fin temperature, and the preheating command from the indoor unit.
SiBE041525F Control Specification 3.3.3 Four Way Valve Operation Compensation At the beginning of operation as the four way valve is switched, the pressure difference to Outline activate the four way valve is acquired when the output frequency is higher than a certain fixed frequency, for a certain fixed time.
Control Specification SiBE041525F Discharge Pipe Temperature Control The discharge pipe temperature is used as the internal temperature of the compressor. If the Outline discharge pipe temperature rises above a certain level, the upper limit of frequency is set to keep the discharge pipe temperature from rising further. Detail Stop zone A˚C...
SiBE041525F Control Specification Input Current Control The microcomputer calculates the input current while the compressor is running, and sets the Outline frequency upper limit based on the input current. In case of heat pump models, this control is the upper limit control of frequency and takes priority over the lower limit control of four way valve operation compensation.
Control Specification SiBE041525F Freeze-up Protection Control During cooling operation, the signal sent from the indoor unit determines the frequency upper limit and prevents freezing of the indoor heat exchanger. (The signal from the indoor unit is divided into zones.) The operating frequency limitation is judged with the indoor heat exchanger temperature. Indoor heat exchanger thermistor temperature 13˚C...
SiBE041525F Control Specification Outdoor Fan Control 1. Fan ON control to cool down the electrical box The outdoor fan is turned ON when the electrical box temperature is high while the compressor is OFF. 2. Fan OFF control during defrosting The outdoor fan is turned OFF during defrosting.
Control Specification SiBE041525F 3.10 Defrost Control Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor Outline heat exchanger temperature must be more than a certain value to finish defrosting. Detail Conditions for Starting Defrost ...
SiBE041525F Control Specification 3.11 Electronic Expansion Valve Control The following items are included in the electronic expansion valve control. Outline Electronic expansion valve is fully closed 1. Electronic expansion valve is fully closed when turning on the power. 2. Pressure equalizing control Open Control 1.
Control Specification SiBE041525F 3.11.1 Fully Closing with Power ON The electronic expansion valve is initialized when turning on the power. The opening position is set and the pressure is equalized. 3.11.2 Pressure Equalizing Control When the compressor is stopped, the pressure equalizing control is activated. The electronic expansion valve opens and the pressure is equalized.
Page 49
SiBE041525F Control Specification 3.11.7 Discharge Pipe Thermistor Disconnection Control The disconnection of the discharge pipe thermistor is detected by comparing the discharge pipe Outline temperature with the condensation temperature. If the discharge pipe thermistor is disconnected, the electronic expansion valve opens according to the outdoor temperature and the operation frequency, operates for a specified time, and then stops.
Control Specification SiBE041525F 3.12 Malfunctions 3.12.1 Sensor Malfunction Detection Sensor malfunction can be detected in the following thermistors: 1. Outdoor heat exchanger thermistor 2. Discharge pipe thermistor 3. Radiation fin thermistor 4. Outdoor temperature thermistor 3.12.2 Detection of Overcurrent and Overload An excessive output current is detected and the OL temperature is observed to protect the Outline compressor.
1 Automatic operation P.20 Refer to the operation manual of applicable model for details. You can download operation Note: manuals from Daikin Business Portal: Daikin Business Portal → Document Search → Item Category → Installation/Operation Manual (URL: https://global1d.daikin.com/business_portal/login/) Remote Controller...
Page 53
P.23 5 Auto-swing P.17 Refer to the operation manual of applicable model for details. You can download operation Note: manuals from Daikin Business Portal: Daikin Business Portal → Document Search → Item Category → Installation/Operation Manual (URL: https://global1d.daikin.com/business_portal/login/) Remote Controller...
SiBE041525F Part 6 Service Diagnosis 1. General Problem Symptoms and Check Items ........44 2. Troubleshooting with LED ..............45 2.1 Indoor Unit....................45 2.2 Outdoor Unit ...................45 3. Service Diagnosis .................46 4. Troubleshooting ..................49 4.1 Error Codes and Descriptions ..............49 4.2 Indoor Unit PCB Abnormality ..............50 4.3 Freeze-up Protection Control / Heating Peak-cut Control ......51 4.4 Fan Motor (DC Motor) or Related Abnormality........52 4.5 Thermistor or Related Abnormality (Indoor Unit)........54...
SiBE041525F General Problem Symptoms and Check Items 1. General Problem Symptoms and Check Items Symptom Check Item Measures Reference Page The unit does not operate. Check the power supply. Check if the rated voltage is supplied. — Check the type of the indoor unit. Check if the indoor unit type is compatible with —...
Troubleshooting with LED SiBE041525F 2. Troubleshooting with LED Indoor Unit The operation lamp blinks when any of the following errors is detected. Operation Lamp 1. When a protection device of the indoor or outdoor unit is activated, or when the thermistor malfunctions.
SiBE041525F Service Diagnosis 3. Service Diagnosis 1. When the TIMER CANCEL button is held down for 5 seconds, 00 is displayed on the Method 1 temperature display screen. TIMER CANCEL button (R21665) 2. Press the TIMER CANCEL button repeatedly until a long beep sounds. ...
Page 58
Service Diagnosis SiBE041525F Method 2 1. Press the center of the TEMP button and the OFF button at the same time. (R21666) 5C is displayed on the LCD. (R21059) 2. Select 5C (service check) with the TEMP or TEMP button. 3.
Page 59
SiBE041525F Service Diagnosis 5. Diagnose by the sound. beep: The left-side number does not correspond with the error code. two consecutive beeps: The left-side number corresponds with the error code but the right-side number does not. long beep: Both the left-side and right-side numbers correspond with the error code. (The numbers indicated when you hear the long beep are the error code.
Troubleshooting SiBE041525F 4. Troubleshooting Error Codes and Descriptions Reference Error Codes Description Page System Normal — Low-voltage detection or over-voltage detection Signal transmission error (between indoor unit and outdoor unit) Unspecified voltage (between indoor unit and outdoor unit) Indoor Indoor unit PCB abnormality Unit Freeze-up protection control / heating peak-cut control Fan motor (DC motor) or related abnormality...
SiBE041525F Troubleshooting Indoor Unit PCB Abnormality Error Code The system checks if the circuit works properly within the microcomputer of the indoor unit. Method of Error Detection The system cannot set the internal settings. Error Decision Conditions Wrong models interconnected Supposed ...
Troubleshooting SiBE041525F Freeze-up Protection Control / Heating Peak-cut Control Error Code Freeze-up protection control Method of Error During cooling operation, the freeze-up protection control (operation halt) is activated Detection according to the temperature detected by the indoor heat exchanger thermistor. ...
SiBE041525F Troubleshooting Fan Motor (DC Motor) or Related Abnormality Error Code The rotation speed detected by the Hall IC during fan motor operation is used to determine Method of Error abnormal fan motor operation. Detection The detected rotation speed does not reach the demanded rotation speed of the target tap, and Error Decision is less than 50% of the maximum fan motor rotation speed.
Page 64
Troubleshooting SiBE041525F Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Note: The motor may break when the Turn off the power supply. motor connector is disconnected Check No.03 (Unplug the power cable or turn with the power supply on.
SiBE041525F Troubleshooting Thermistor or Related Abnormality (Indoor Unit) C4, C9 Error Code The temperatures detected by the thermistors determine thermistor errors. Method of Error Detection The voltage between the both ends of the thermistor is 4.96 V and more or 0.04 V and less Error Decision during compressor operation.
Troubleshooting SiBE041525F Low-voltage Detection or Over-voltage Detection Error Code Method of Error Low-voltage detection: An abnormal voltage drop is detected by the DC voltage detection circuit. Detection Over-voltage detection: An abnormal voltage rise is detected by the over-voltage detection circuit. Error Decision Low-voltage detection: ...
Page 67
SiBE041525F Troubleshooting Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check the power supply voltage. Is the voltage fluctuation Correct the power supply. within ±10% from the rated value? Check the connection of the compressor harness.
Troubleshooting SiBE041525F Signal Transmission Error (Between Indoor Unit and Outdoor Unit) Error Code The data received from the outdoor unit in signal transmission is checked whether it is normal. Method of Error Detection The data sent from the outdoor unit cannot be received normally, or the content of the data is Error Decision abnormal.
Page 69
SiBE041525F Troubleshooting Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.11 Check the power supply voltage. Refer to P.81 Is the Is the voltage fluctuation voltage fluctuation Correct the power supply.
Troubleshooting SiBE041525F Unspecified Voltage (Between Indoor Unit and Outdoor Unit) Error Code The supply power is detected for its requirements (pair type is different from multi type) by the Method of Error indoor / outdoor transmission signal. Detection The pair type and multi type are interconnected. Error Decision Conditions ...
SiBE041525F Troubleshooting Outdoor Unit PCB Abnormality Error Code The system checks if the microprocessor is working in order. Method of Error The system checks if the zero-cross signal comes in properly. Detection The microprocessor program runs out of control. Error Decision ...
Troubleshooting SiBE041525F 4.10 OL Activation (Compressor Overload) Error Code A compressor overload is detected through compressor OL. Method of Error Detection If the error repeats, the system is shut down. Error Decision Reset condition: Continuous run for about 60 minutes without any other error Conditions ...
Page 73
SiBE041525F Troubleshooting Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.01 Refer to P.79 Discharge pipe thermistor Insert the thermistor in disconnected? position. Check No.12 Refer to P.81 Check No.
Troubleshooting SiBE041525F 4.11 Compressor Lock Error Code A compressor lock is detected by the current waveform generated when applying high- Method of Error frequency voltage to the motor. Detection If the error repeats, the system is shut down. Error Decision ...
SiBE041525F Troubleshooting 4.12 DC Fan Lock Error Code An error is determined with the high-voltage fan motor rotation speed detected by the Hall IC. Method of Error Detection The fan does not start in 15 ~ 30 seconds (depending on the model) even when the fan Error Decision motor is running.
Troubleshooting SiBE041525F 4.13 Input Overcurrent Detection Error Code An input overcurrent is detected by checking the input current value with the compressor Method of Error running. Detection The current exceeds about 14 ~ 18 A (depending on the model and operation mode) for 2.5 Error Decision seconds with the compressor running.
SiBE041525F Troubleshooting 4.14 Four Way Valve Abnormality Error Code The room temperature thermistor and the indoor heat exchanger thermistor are checked if they Method of Error function within their normal ranges in each operation mode. Detection A following condition continues over 10 minute after operating for 5 minutes. Error Decision Conditions Cooling / Dry...
Page 78
Troubleshooting SiBE041525F Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.01 Four way valve coil Refer to P.79 Correct the four way valve disconnected (loose)? coil. Check No.13 Refer to P.82 Harness disconnected? Reconnect the harness.
SiBE041525F Troubleshooting 4.15 Discharge Pipe Temperature Control Error Code An error is determined with the temperature detected by the discharge pipe thermistor. Method of Error Detection If the temperature detected by the discharge pipe thermistor rises above A°C, the Error Decision compressor stops.
Troubleshooting SiBE041525F 4.16 High Pressure Control in Cooling Error Code High-pressure control (operation halt, frequency drop, etc.) is activated in cooling operation if Method of Error the temperature sensed by the outdoor heat exchanger thermistor exceeds the limit. Detection The temperature sensed by the outdoor heat exchanger thermistor rise above 61°C Error Decision (depending on the model).
SiBE041525F Troubleshooting 4.17 Compressor System Sensor Abnormality Error Code The system checks the DC current before the compressor starts. Method of Error Detection The voltage converted from the DC current before compressor start-up is out of the range Error Decision 0.5 ~ 4.5 V.
Troubleshooting SiBE041525F 4.18 Position Sensor Abnormality Error Code A compressor start-up failure is detected by checking the compressor running condition through Method of Error the position detection circuit. Detection If the error repeats, the system is shut down. Error Decision ...
Page 83
SiBE041525F Troubleshooting Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.15 Refer to P.83 Turn off the power. Check No.18 Check the power supply voltage. Refer to P.86 Is the power supply Check No.20...
Troubleshooting SiBE041525F 4.19 Thermistor or Related Abnormality (Outdoor Unit) H9, J3, J6, P4 Error Code This fault is identified based on the thermistor input voltage to the microcomputer. Method of Error A thermistor fault is identified based on the temperature sensed by each thermistor. Detection ...
Page 85
SiBE041525F Troubleshooting In case of H9, J3, J6 Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.01 Refer to P.79 Turn on the power again. Error displayed Reconnect the connectors again on remote or thermistors.
Troubleshooting SiBE041525F 4.20 Electrical Box Temperature Rise Error Code An electrical box temperature rise is detected by checking the radiation fin thermistor with the Method of Error compressor off. Detection With the compressor off, the radiation fin temperature is above A°C. Error Decision ...
SiBE041525F Troubleshooting 4.21 Radiation Fin Temperature Rise Error Code A radiation fin temperature rise is detected by checking the radiation fin thermistor with the Method of Error compressor on. Detection If the radiation fin temperature with the compressor on is above A°C. Error Decision ...
Troubleshooting SiBE041525F 4.22 Output Overcurrent Detection Error Code An output overcurrent is detected by checking the current that flows in the inverter DC section. Method of Error Detection A position signal error occurs while the compressor is running. Error Decision ...
Page 89
SiBE041525F Troubleshooting Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.15 ∗ An output overcurrent may result from wrong internal wiring. If the system is interrupted by an output Refer to P.83 overcurrent after the wires have been disconnected and reconnected for part replacement, check the wiring again.
Check SiBE041525F 5. Check Thermistor Resistance Check Disconnect the connectors of the thermistors from the PCB, and measure the resistance of Check No.01 each thermistor using a multimeter. The data is for reference purpose only. Resistance (kΩ) Thermistor temperature (°C) Room temperature thermistor Other thermistors –20...
SiBE041525F Check Indoor Fan Motor Connector Output Check Fan motor wire breakdown / short circuit check Check No.03 1. Check the connector for connection. 2. Turn the power off. 3. Check if each resistance at the phases U - V and V - W is 90 Ω ~ 100 Ω (between the pins 12 - 9, and between 9 - 6).
Check SiBE041525F Power Supply Waveforms Check Measure the power supply waveform between No. 1 and No. 2 on the terminal board, and check Check No.11 the waveform disturbance. Check if the power supply waveform is a sine wave (Fig.1). ...
SiBE041525F Check Four Way Valve Performance Check Check No.13 Turn off the power. Then, turn on the power to restart the system. ∗ Four way valve coil Start heating operation. Cooling / Dry: Not energized Heating: Energized voltage at 220 - 240 Replace the outdoor unit VAC with compressor PCB (main PCB).
Check SiBE041525F Inverter Analyzer Check Characteristics Check No.15 Inverter analyzer: RSUK0917C If an abnormal stop occurs due to compressor startup failure or overcurrent output when using an inverter unit, it is difficult to judge whether the stop is caused by the compressor failure or some other failure (main PCB, power module, etc.).
Page 95
SiBE041525F Check Step 3 Activate power transistor test operation from the indoor unit. (1) Turn the power on. (2) Press the center of the TEMP button and the OFF button on the remote controller at the same time. (3) Select T with the TEMP or TEMP button.
Check SiBE041525F Rotation Pulse Check on the Outdoor Unit PCB Make sure that the voltage of 320 + 100 V ~ 320 - 50 V is applied. Check No.16 1. Set operation off and power off. Disconnect the connector S70 or S71. 2.
SiBE041525F Check Installation Condition Check Check No.17 Installation condition check Check the allowable dimensions of the air Change the installation suction and location or direction. discharge area. Is the discharged air Change the installation short-circuited? location or direction. Is the outdoor heat Clean the outdoor heat exchanger very dirty? exchanger.
Check SiBE041525F 5.11 Outdoor Fan System Check Check No.19 DC motor Check the outdoor fan system. Fan motor Is the lead wire connector outdoor fan running? Go to Check No. 16. disconnected? Reconnect the connector. Outdoor fan system is functioning. (R21195) 5.12 Main Circuit Short Check Check to make sure that the voltage between (+) and (–) of the diode bridge (DB1) is about 0 V...
SiBE041525F Check 50/60/71 class Multimeter (R20701) 5.13 Power Module Check Check to make sure that the voltage between (+) and (–) of the power module is about 0 V Check No.22 before checking. Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the connector, press the protrusion on the connector.
Page 100
Check SiBE041525F 20/25/35 class Pin 24: + Pin 23: U Pin 22: V Pin 21: W Pin 20: – (R20703) 50/60/71 class DC_P1: + (R20704) DC_N1: – Service Diagnosis...
SiBE041525F Part 7 Trial Operation and Field Settings 1. Tips for Servicing ..................91 1.1 Pump Down Operation ................91 1.2 Forced Cooling Operation ..............91 2. Trial Operation ..................92 3. Field Settings ..................93 3.1 Temperature Display Switch ..............93 3.2 When 2 Units are installed in 1 Room ............93 4.
Tips for Servicing SiBE041525F 1. Tips for Servicing Pump Down Operation In order to protect the environment, be sure to conduct pump down operation when relocating or Outline disposing of the unit. 1) Remove the valve caps from the liquid stop valve and the gas stop valve. Detail 2) Carry out forced cooling operation.
SiBE041525F Trial Operation 2. Trial Operation Carry out the trial operation in accordance with the operation manual to ensure that all functions Outline and parts, such as flap movement, are working properly. Trial operation should be carried out in either cooling or heating operation. 1.
Field Settings SiBE041525F 3. Field Settings Temperature Display Switch You can select Celsius or Fahrenheit for temperature display. ARC466A6 Press the TEMP and ON TIMER buttons at the same time for 5 seconds to change the unit of temperature display.
SiBE041525F Silicone Grease on Power Transistor / Diode Bridge 4. Silicone Grease on Power Transistor / Diode Bridge Apply the specified silicone grease to the heat radiation part of a power transistor / diode bridge Outline when you replace an outdoor unit PCB. The silicone grease encourages the heat radiation of a power transistor / diode bridge.
Wiring Diagrams SiBE041525F 2. Wiring Diagrams Indoor Unit FTX20/25/35K(2)V1B, ATX20/25/35K(2)V1B PCB1: Control PCB Note: PCB2: Display PCB Refer to Part 3 for Printed Circuit Board Connector Wiring Diagram. PCB3: Remote Control PCB BR069 (only available on A/FTX20~35K2V1B) Appendix...
Page 111
SiBE041525F Wiring Diagrams FTX50/60/71K(M/2)V1B PCB A1P: Filter PCB Note: PCB A2P: Control PCB PCB A3P: Display PCB Refer to Part 3 for Printed Circuit Board Connector Wiring Diagram. PCB A4P: Remote Control PCB BR069 (only available on FTX50~71KM) Appendix...
Page 113
SiBE041525F Wiring Diagrams RX50/60/71K(2)V1B WIRING DIAGRAM FIELD WIRING INDOOR MRM20 IPM1 TO INDOOR UNIT 1 BLK MRM10 3.15A MR30 3.15A W V U POWER SUPPLY MRCW X11A OUTDOOR NOTE 1. REFER TO THE NAMEPLATE FOR THE POWER REQUIREMENTS. : CAPACITOR t˚...
Page 114
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.