Check Rotation - Emerson Bettis EHO Installation And Operation Manual

Table of Contents
Section 4: Set-up/Start-up Procedure
May 2015
4.5.5
4.5.6
4.6

Check Rotation

4.6.1
4.6.2
NOTE:
On Spring-Return units, Fail-safe Close units OPEN with the Power Cylinder and Spring-
Return CLOSE. Fail-safe Open units CLOSE with the Power Cylinder and Spring-Return
OPEN.
4.6.3
4.6.4
Figure 15
4.6.5
4.6.6
NOTE:
If the EHO Actuator is supplied with optional ESD, before operating a motor-powered
stroke, a customer supplied ESD signal must be present and Solenoid Valve (17)
energized.
24
Open the Hand Pump Isolation valves (8). ((See NOTE: IMPORTANT above.))
Check Reservoir (4) to see the hydraulic fluid is at the proper level.
Turn on the electrical supply to the unit. If an ((optional)) Circuit Breaker Module
is supplied, turn the Circuit Breaker to ON.
Turn the LOCAL-OFF-REMOTE selector switch to LOCAL.
Ensure Flow Control Valves (7) are adjusted fully counterclockwise for maximum
flow.
Open inspection port on side of unit to observe the rotation of the motor/pump
shaft.
Inspection Port for Motor Rotation
While observing the inspection port, for motor rotation, push and release the
OPEN/CLOSE PUSHBUTTON to Power Stroke the actuator and immediately push
the STOP Pushbutton. Motor rotation should be counterclockwise when looking
at the back of the motor.
If needed, correct motor rotation.
Installation and Operation Manual
Part Number: VA001-507-32, Rev. 0
Set-up/Start-up Procedure