SPECIFICATIONS
Operate time:
Timer accuracy:
NEUTRAL OVERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Pickup delay:
2
Reset delay:
Curve timing accuracy at >1.1 pickup: ±3.5% of operate time or ±1 cycle (whichever is greater) from pickup to operate
Operate time:
AUXILIARY OVERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Pickup delay:
Reset delay:
Timer accuracy:
Operate time:
UNDERFREQUENCY
Minimum signal:
Pickup level:
Dropout level:
Level accuracy:
Time delay:
Timer accuracy:
Operate time:
Typical times are average operate times including variables such as frequency change instance, test method, and so on, and can vary by
±0.5 cycles.
BREAKER ARCING CURRENT
Principle:
Initiation:
Compensation for auxiliary relays:
Alarm threshold:
Fault duration accuracy:
Availability:
BREAKER FLASHOVER
Operating quantity:
Pickup level voltage:
Dropout level voltage:
Pickup level current:
Dropout level current:
Level accuracy:
Pickup delay:
Timer accuracy:
Operate time:
BREAKER RESTRIKE
Principle:
Availability:
Pickup level:
2-20
<30 ms at 1.10 × pickup at 60 Hz
±3% of operate time or ±1/4 cycle (whichever is greater)
0.004 to 3.000 pu in steps of 0.001
97 to 98% of pickup
±0.5% of reading from 10 to 208 V
0.00 to 600.00 s in steps of 0.01 (definite time) or user-defined curve
0.00 to 600.00 s in steps of 0.01
<30 ms at 1.10 pickup at 60 Hz
0.004 to 3.000 pu in steps of 0.001
97 to 98% of pickup
±0.5% of reading from 10 to 208 V
0 to 600.00 s in steps of 0.01
0 to 600.00 s in steps of 0.01
±3% of operate time or ±1/4 cycle (whichever is greater)
<30 ms at 1.10 × pickup at 60 Hz
0.10 to 1.25 pu in steps of 0.01
20.00 to 65.00 Hz in steps of 0.01
pickup + 0.03 Hz
±0.001 Hz
0 to 65.535 s in steps of 0.001
±3% of operate time or ±1/4 cycle (whichever is greater)
typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
2
accumulates breaker duty (I
t) and measures fault duration
programmable per phase from any FlexLogic operand
0 to 65.535 s in steps of 0.001
2
0 to 50000 kA
-cycle in steps of 1
0.25 of a power cycle
1 per CT bank with a minimum of 2
phase current, voltage, and voltage difference
0.004 to 1.500 pu in steps of 0.001
97 to 98% of pickup
0.020 to 1.500 pu in steps of 0.001
97 to 98% of pickup
±0.5% or ±0.1% of rated, whichever is greater
0 to 65.535 s in steps of 0.001
±3% of operate time or ±42 ms, whichever is greater
<42 ms at 1.10 × pickup at 60 Hz
detection of high-frequency overcurrent condition ¼ cycle after breaker opens
one per digital signal processor (DSP)
0.1 to 2.00 pu in steps of 0.01
F35 MULTIPLE FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL