Honeywell LCBS Connect Installation Instructions

Honeywell LCBS Connect Installation Instructions

Wall
Hide thumbs Also See for LCBS Connect:

Quick Links

LCBS Connect Wall Module
PRODUCT DESCRIPTION
The LCBS Connect Wall Module is a Sylk bus
communicating device which is exclusively compatible
with the LCBS Connect controller. It contains integral
temperature and humidity sensors to control any given
space's comfort. This device enables local controller
configuration through an easy-to-use touch screen
interface with menu driven selections. The wall module
communicates and is powered by the Sylk bus, so no
additional wiring is necessary.
Dimensions
The TS120 consists of a back plate and a front cover which
contains a circuit board.
INSTALLATION INSTRUCTIONS
4-49/64
(121)
Fig. 1. Dimensions in in. (mm).
INSTALLATION
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check ratings given in instructions and on the prod-
uct to ensure the product is suitable for the applica-
tion.
3. Installer must be a trained, experienced service tech-
nician.
4. After installation is complete, check out product
operation as provided in these instructions.
MOUNTING
Mount the wall module on an inside wall approximately 48
in (1.2m) from the floor (or in the specified location) to
allow for exposure to the average zone temperature. Do
not mount the device on an outside wall, on a wall
containing water pipes or near air ducts. Avoid locations
that are exposed to discharge air from registers or
radiation from appliances, lights or the sun.
53/64
(21)
3-5/16
(84)
M36282
31-00084-01
loading

Summary of Contents for Honeywell LCBS Connect

  • Page 1 4-49/64 (121) PRODUCT DESCRIPTION M36282 The LCBS Connect Wall Module is a Sylk bus communicating device which is exclusively compatible Fig. 1. Dimensions in in. (mm). with the LCBS Connect controller. It contains integral temperature and humidity sensors to control any given space’s comfort.
  • Page 2 LCBS CONNECT WALL MODULE Do not install the wall module where it can be affected by: — drafts or dead spots behind doors and in corners. STANDARD UTILITY CONDUIT BOX — hot or cold air from ducts. — radiant heat from sun or appliances.
  • Page 3 (13MM) FROM address configured. Other Sylk sensors are compatible (13) WALL MODULE WIRES TO BE with the LCBS Connect controller and wall module but TERMINALS ATTACHED AT limitations must be observed. Up to FOUR additional Sylk ONE TERMINAL. sensors can be used unless a TR40-H, TR40-CO2 or TR40- H-CO2 is used.
  • Page 4 By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’...