CV10 Quick Start Guide Table of Contents Step 1 – Before Starting the Drive..............2 Wiring Diagram...................3 Description of Main Circuit Terminals ............4 Description of Control Circuit Terminals............4 Keypad and Display Description ..............5 Step 2 – Apply Power to the Drive..............5 Parameter Groups ..................6...
Step 1 Before Starting the Drive Please review Preface and Safety Precautions (page 13 through 16) of the CV10 Instruction Manual. Verify drive was installed in accordance with the procedures as described in CV10 Ambient Environment and Installation on pages 18 through 32.
Common contact for S1~S5 in PNP (source) input. (refer to CV10 wiring diagram) of SW1 when PNP input is used. Common contact for S1~S5 in NPN (sink) input. (refer to CV10 wiring diagram) of SW1 when NPN input is used.
Frequency when running. To display RPM or Engineering units it must be selected in the program. See parameters 4-04 and 4-05 page 61 of the CV10 Instruction Manual. 2. VOLTS LED Indicates Output Voltage when running and also DC Bus Voltage.
CV10 Quick Start Guide CV10 PARAMETER GROUPS Each parameter group branches off into individual parameters. See pages 41 through 50 for more detailed information about each parameter number. Parameter Description Group No. Drive Operation Mode Start/Stop and Frequency Control Modes...
CV10 Quick Start Guide Press the key to move to the next digit to be changed with the keys. Press the key to save the edited parameter value to memory. Display will read “END” indicating it saved the information then the parameter edited will be displayed in the keypad.
CV10 Quick Start Guide Step-by-Step Procedure for Step 3 Enter the drive Operating Mode in parameter 0-00. 0-00 = 0000 Vector (General Purpose) “Default Setting”. 0-00 = 0001 Vector (Variable Torque). 0-00 = 0002 Volts / Hz. If a value of 0002 (Volts/Hz) was entered for parameter 0-00, then skip to step K.
CV10 Quick Start Guide Step 5 Check Full Speed at 50Hz/60Hz • Frequency/Speed can be changed by pressing the keys. To move left for next digit, press key. Press the key to set the speed. • Set frequency to 50Hz/60Hz as applicable.
Page 11
CV10 Quick Start Guide External 0-10V or 100% 0 - 2 0 mA Signal Potentiometer External Signal Input Input Figure 1 Set SW2 switch per Table 1 based on the type of analog signal connected to the drive (use 0 - 10 VDC position for potentiometer input).
Page 12
After setting parameters 1-00 and 1-01, remove AC input power, wait for the "Charged" LED to extinguish, and connect the switches or pushbuttons as shown in Figures 3-A, 3-B, and 3-C. Reference page 52 of the CV10 instruction manual for more detailed information.
Page 13
CV10 Quick Start Guide 1. Parameter 1-01 = 0000: Forward/Stop - Reverse/Stop a. Input signal is NPN (Active Low) b. Input Signal is PNP (Active High) S1 Forward S1 Forward S1 Forward S2 Reverse S2 Reverse S2 Reverse COM Common...