Siemens LMV3 series Technical Instructions page 50

Hide thumbs Also See for LMV3 series:
Table of Contents
LMV Series
Parameter #
Fuel 0
Fuel 1
Parameter Name
Gas Oil Gas Oil
041
Service Level PW
042
OEM Level PW
050
Backup / Restore
055
Burner ID AZL
AZL Parameter Set
056
Associated ASN
AZL Parameter Set
057
Associated SW
102
Production Date
103
Serial Number
Default Parameter
104
Set Code
Default Parameter
105
Set Version
107
LMV3 SW Version
108
LMV3 SW Variant
Parameter Set Code
111
LMV3
113
Burner ID LMV3
SCC Inc.
LEGEND - Password Access: U = User, S = Service, O = OEM, U/S = View - User, Write - Service, S/O = View - Service, Write - OEM
Shaded Parameters = Frequently Used. ** Parameters = Must Set. Fuel 1 parameters for LMV36 only.
U/S/O
Default
Range
000 Level: Parameter Backup / Restore / Change Passwords
Any 4
9876
characters
O
Any 5
EntrY
characters
Backup - 0
-99-50
Restore - 0
S
Read only
100 Level: General Information / Configuration / Modbus
U
Read only
S
U/S
Not set
0-99999999
The service level password can be changed here. It must be exactly 4 characters in length. Enter the same
password twice to change it (n = new, r = repeat).
The OEM level password can be changed here. It must be exactly 5 characters in length. Enter the same
password twice to change it (n = new, r = repeat).
Used to perform parameter backups and restores.
Backup: LMV3 transfer to AZL. Restore: AZL transfer to LMV3.
Set parameter to 1 and press Enter to begin the backup or restore. When the value changes back to 0, the
backup or restore was completed successfully. If the value changes to any other number besides 0, see
error code 137 for the cause of the failure.
Burner ID of the LMV3 parameter set currently stored in the AZL.
Coded LMV3 part number (ASN) associated with the parameter set currently stored in the AZL.
Code example for an LMV37.420A1:
056.00 = 3, 056.01 = 7, 056.02 = 4, 056.03 = 2, 056.04 = 0, 056.05 = 1.
Software version of the LMV3 associated with the parameter set stored in the AZL.
Date that the LMV3 was produced in the DD.MM.YY format.
Serial number of the LMV3.
Parameter set code for the default parameters.
Version (revision) of the default parameter set.
Factory loaded LMV3 software version.
Factory loaded LMV3 software variant.
Coded LMV3 part number (ASN). For comparison to parameter 056.
Code example for an LMV37.420A1:
056.00 = 3, 056.01 = 7, 056.02 = 4, 056.03 = 2, 056.04 = 0, 056.05 = 1.
The burner ID is set here. The burner ID must be all digits (no letters), from 1-8 digits in length. Typically
the burner / boiler serial number is used. This serves as an identifier for the parameter set. The burner ID
must be set in order to perform a parameter backup.
Page 2
Description
Technical Instructions
LV3-1000