Daikin McQuay AWS210BDS Installation Manual

Daikin McQuay AWS210BDS Installation Manual

Pathfinder aws-b series air cooled chillers (rev 0b) standard, high, & premium efficiencies includes models with vfd and models with remote evaporator 170 to 550 tons, 600 to 1930 kw, r-134a, 60hz
®
Pathfinder
Model AWS-B (Rev 0B) • Standard, High, & Premium Efficiencies
Includes models with VFD and models with Remote Evaporator
170 to 550 tons • 600 to 1930 kW • R-134a • 60Hz
© 2012 McQuay International
Installation Manual
Air Cooled Chillers
IM 1167
Group: Chillers
Part Number: IM 1167
Date: December, 2012
REV
00
Table of Contents
loading

Summary of Contents for Daikin McQuay AWS210BDS

  • Page 1 Installation Manual IM 1167 ® Group: Chillers Pathfinder Air Cooled Chillers Part Number: IM 1167 Date: December, 2012 Model AWS-B (Rev 0B) • Standard, High, & Premium Efficiencies Includes models with VFD and models with Remote Evaporator 170 to 550 tons • 600 to 1930 kW • R-134a • 60Hz ©...
  • Page 2: Table Of Contents

    Introduction....... . 3 Single-point Electrical Data (non-VFD) ..92 Installation and Startup .
  • Page 3: Introduction

    Design Vintage T = Triple Compressor General Description  Daikin McQuay Pathfinder™ air-cooled chillers are complete, Information on the operation of the unit MicroTech self-contained chillers that include the latest in engineered controller is in the OM 1123 manual, available on components arranged to provide a compact and efficient unit.
  • Page 4: Installation And Startup

    Installation and Startup Installation and maintenance are to be performed only by For pad-mounted units, it is recommended that the unit be Installation and Startup qualified personnel who are familiar with local codes and raised a few inches with suitable supports such as neoprene waffle vibration pads, located at least under the mounting regulations, and experienced with this type of equipment.
  • Page 5: Clearance Requirements

    Installation and Startup The right-hand panel contains a circuit breaker. A minimum of Single Point Disconnect Switch four feet of clearance is required in front of the panels. The side clearance required for airflow provides sufficient service clearance. Compressor #2 On all Pathfinder units, the condenser fans and motors can be Compressor #1 Circuit Breaker...
  • Page 6 Installation and Startup Figure 5: Refrigerant Diagram - All Standard Efficiency Models (one circuit shown of two or three possible circuits) AWS PACKAGE CHILLER 331994701 REV. 0D SCHRADER VALVE CONDENSER (HEADER) ASSEMBLY FLOW OIL PRESS. BUTTERFLY DISCHARGE DISCHARGE TRANSDUCER VALVE TRANSDUCER TUBING WITH SCHRADER...
  • Page 7 Installation and Startup Restricted Air Flow Case 1: Building or Wall on One Side of One Unit The clearances required for design operation of Pathfinder air- The existence of a screening wall or the wall of a building in cooled chillers are described in the previous section. close proximity to an air-cooled chiller is common in both Occasionally, these clearances cannot be maintained due to site rooftop and ground level applications.
  • Page 8 Installation and Startup Case 2: Two Units Side By Side Case 3: Three or More Units Side By Side Two or more units sited side by side are common. If spaced When three or more units are side by side, the outside chillers closer than 12 feet (3.7 meters) it is necessary to adjust the (1 and 3 in this case) are influenced by the middle unit only on performance of each unit;...
  • Page 9 Installation and Startup Case 4: Open Screening Walls Case 5, Pit/Solid Wall Installation Decorative screening walls are often used to help conceal a Use care with pit installations as they can cause operating unit either on grade or on a rooftop. Design these walls such problems.
  • Page 10: Chilled Water Piping

    Installation and Startup Chilled Water Piping employed in lieu of ethylene glycol, the added pressure drop and loss of performance could be substantial. IMPORTANT: Piping design must be provided by a Do not use PVC or CPVC piping due to incompatibility qualified Architect or Systems HVAC Design Engineer with POE oil in the event of a refrigerant to water leak.
  • Page 11 Figure 12: Strainer Pressure Drop Variable water flow involves reducing the water flow through the evaporator as the load decreases. Daikin McQuay chillers are designed for this duty, provided that the rate of change in water flow is slow, and the minimum and maximum flow rates for the evaporator are not exceeded.
  • Page 12: Flow Switch

    Installation and Startup will result in decreased capacity and increased pressure Flow Switch drop. Note: Do not use automotive grade antifreezes as A flow switch must be included in the chilled water system to they contain inhibitors harmful to chilled water systems. prove that there is adequate water flow before the unit can Use only glycols specifically designated for use in start.
  • Page 13: Refrigerant Charge

    AWS chiller units are designed to operate with leaving chilled fluid temperatures of 20.0°F to 60.0°F (-6.7°C to 15.6°C). each unit is shown in the Physical Data Tables beginning on Consult the local Daikin McQuay sales office for performance page outside these temperatures. Leaving chilled fluid temperatures Glycol Solutions below 40°F (4.4°C) result in evaporating temperatures at or...
  • Page 14: Electrical Connections

    Installation and Startup Table 5: Ethylene Glycol Correction Factors U.S.A. National Electrical Code. Field-supplied disconnect -3.3 0.996 0.998 1.036 1.097 switches are required if not factory-supplied with the unit. -7.8 0.988 0.994 1.061 1.219 Table 8: Electric Power Connection Option -13.9 0.979 0.991...
  • Page 15: Physical Data (Non-Vfd)

    Physical Data (non-VFD) Table 10: Physical Data (60 Hz, Standard Efficiency, non-VFD models) Physical Data (non-VFD) AWS190BDS AWS210BDS AWS225BDS Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 180.1 (633)
  • Page 16 Physical Data (non-VFD) Table 11: Physical Data (60 Hz, Standard Efficiency, non-VFD models) AWS250BDS AWS260BDS AWS290BDS Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 235.8 (829) 250.5 (881) 282.9 (995) Unit Operating Charge lbs (kg) 185 (84)
  • Page 17 Physical Data (non-VFD) Table 12: Physical Data (60 Hz, Standard Efficiency, non-VFD models) AWS310BDS AWS350BDS AWS375BDS Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 300.4 (1056) 340.6 (1197) 361.4 (1271) Unit Operating Charge lbs (kg) 215 (98)
  • Page 18 Physical Data (non-VFD) Table 13: Physical Data (60 Hz, Standard Efficiency, non-VFD models) AWS400BTS AWS425BTS Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 BASIC DATA Unit Cap. @ AHRI tons (kW) 398.3 (1400) 418.7 (1472) Unit Operating Charge lbs (kg) 185 (84) 185 (84)
  • Page 19 Physical Data (non-VFD) Table 14: Physical Data (60 Hz, Standard Efficiency, non-VFD models) AWS450BTS AWS470BTS Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 BASIC DATA Unit Cap. @ AHRI tons (kW) 441.4 (1552) 459.2 (1615) Unit Operating Charge lbs (kg) 210 (95) 210 (95)
  • Page 20 Physical Data (non-VFD) Table 15: Physical Data (60 Hz, Standard Efficiency, non-VFD models) AWS500BTS AWS525BTS Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 BASIC DATA Unit Cap. @ AHRI tons (kW) 488.3 (1717) 517.7 (1820) Unit Operating Charge lbs (kg) 210 (95) 210 (95)
  • Page 21 Physical Data (non-VFD) Table 16: Physical Data (60 Hz, Standard Efficiency, non-VFD models) AWS550BTS Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 BASIC DATA Unit Cap. @ AHRI tons (kW) 547.3 (1924) Unit Operating Charge lbs (kg) 270 (122) 270 (122) 280 (127) Unit Dimensions 580 x 88 x 100...
  • Page 22 Physical Data (non-VFD) Table 17: Physical Data (60 Hz, High Efficiency, non-VFD models) AWS210BDH AWS230BDH AWS250BDH Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 205.7 (723) 225.2 (792) 240.6 (846) Unit Operating Charge lbs (kg) 160 (73)
  • Page 23 Physical Data (non-VFD) Table 18: Physical Data (60 Hz, High Efficiency, non-VFD models) AWS280BDH AWS300BDH AWS330BDH Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 271.9 (956) 288.7 (1015) 327.3 (1151) Unit Operating Charge lbs (kg) 230 (104)
  • Page 24 Physical Data (non-VFD) Table 19: Physical Data (60 Hz, High Efficiency, non-VFD models) AWS350BDH AWS390BDH AWS410BDH Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 348.1 (1224) 378.7 (1332) 409.8 (1441) Unit Operating Charge lbs (kg) 285 (129)
  • Page 25 Physical Data (non-VFD) Table 20: Physical Data (60 Hz, High Efficiency, non-VFD models) AWS450BTH AWS475BTH Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 BASIC DATA Unit Cap. @ AHRI tons (kW) 446.3 (1569) 470.3 (1654) Unit Operating Charge lbs (kg) 250 (113) 250 (113)
  • Page 26 Physical Data (non-VFD) Table 21: Physical Data (60 Hz, High Efficiency, non-VFD models) AWS500BTH AWS530BTH Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 BASIC DATA Unit Cap. @ AHRI tons (kW) 499.4 (1756) 528.3 (1857) Unit Operating Charge lbs (kg) 295 (134) 295 (134)
  • Page 27 Physical Data (non-VFD) Table 22: Physical Data (60 Hz, Premium Efficiency, non-VFD models) AWS240BDP AWS265BDP AWS290BDP Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 232.8 (818) 256.4 (901) 277.5 (976) Unit Operating Charge lbs (kg) 200 (91)
  • Page 28 Physical Data (non-VFD) Table 23: Physical Data (60 Hz, Premium Efficiency, non-VFD models) AWS310BDP AWS330BDP AWS365BDP Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 303.9 (1068) 324.9 (1142) 355 (1248) Unit Operating Charge lbs (kg) 250 (113)
  • Page 29 Physical Data (non-VFD) Table 24: Physical Data (60 Hz, Premium Efficiency, non-VFD models) AWS400BDP Data CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 385.4 (1355) Unit Operating Charge lbs (kg) 310 (141) 310 (141) Unit Dimensions 473 x 88 x 100 L x W x H, in.
  • Page 30: Physical Data (Vfd)

    Physical Data (VFD) Table 25: Physical Data (60 Hz, Standard Efficiency, VFD models) Physical Data (VFD) AWS170BDS VFD AWS190BDS VFD AWS200BDS VFD Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 162.6 (572) 181.3 (637) 195.1 (686)
  • Page 31 Physical Data (VFD) Table 26: Physical Data (60 Hz, High Efficiency, VFD models) AWS210BDH VFD AWS230BDH VFD AWS250BDH VFD Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 205.2 (721) 224.8 (790) 240.0 (844)
  • Page 32 Physical Data (VFD) Table 27: Physical Data (60 Hz, High Efficiency, VFD models) AWS280BDH VFD AWS300BDH VFD AWS330BDH VFD Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 270.6 (951) 287.7 (1012) 326.3 (1147)
  • Page 33 Physical Data (VFD) Table 28: Physical Data (60 Hz, High Efficiency, VFD models) AWS350BDH VFD AWS390BDH VFD AWS410BDH VFD Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 347.1 (1220) 377.8 (1328) 408.7 (1437)
  • Page 34 Physical Data (VFD) Table 29: Physical Data (60 Hz, High Efficiency, VFD models) AWS450BTH VFD AWS475BTH VFD Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 BASIC DATA Unit Cap. @ AHRI tons (kW) 445.2 (1565) 467.7 (1644) Unit Operating Charge lbs (kg) 210 (95)
  • Page 35 Physical Data (VFD) Table 30: Physical Data (60 Hz, High Efficiency, VFD models) AWS500BTH VFD AWS530BTH VFD Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 BASIC DATA Unit Cap. @ AHRI tons (kW) 497.8 (1750) 524.8 (1845) Unit Operating Charge lbs (kg) 265 (120)
  • Page 36 Physical Data (VFD) Table 31: Physical Data (60 Hz, Premium Efficiency, VFD models) AWS240BDP VFD AWS265BDP VFD AWS290BDP VFD Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 232.7 (818) 256.3 (901) 277.6 (976)
  • Page 37 Physical Data (VFD) Table 32: Physical Data (60 Hz, Premium Efficiency, VFD models) AWS310BDP VFD AWS330BDP VFD AWS365BDP VFD Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 303.8 (1068) 324.7 (1142) 354.8 (1247)
  • Page 38 Physical Data (VFD) Table 33: Physical Data (60 Hz, Premium Efficiency, VFD models) AWS400BDP VFD Data CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 385.4 (1355) Unit Operating Charge lbs (kg) 310 (141) 310 (141) Unit Dimensions 496 x 88 x 100 L x W x H, in.
  • Page 39: Lifting & Mounting Weights (I-P Units)

    600-6. To determine if your unit is Rev 00 or Rev 0A, check Item 62 of the Item Summary Report for your unit. If you have additional questions, contact your Daikin McQuay representative. Table 34: Lifting & Mounting Weights (IP units)
  • Page 40 Lifting & Mounting Weights (I-P Units) Table 35: Lifting & Mounting Weights (IP units) continued LIFTING WEIGHT FOR EACH POINT (LBS) MOUNTING LOADS FOR EACH POINT (LBS) UNIT SIZE # OF FANS M9 M10 M11 M12 AWS240BDP 2699 2686 2268 2258 1736 1728 1294 1288...
  • Page 41: Lifting & Mounting Weights (Si Units)

    LIFTING WEIGHT FOR EACH POINT (KG) MOUNTING LOADS FOR EACH POINT (KG) # OF Unit Size FANS AWS190BDS 1779 1770 1070 1065 1272 1266 1054 1049 645 AWS210BDS 1912 1826 1161 1109 1363 1302 1133 1083 702 1980 1971 1155 1150 1416 1409...
  • Page 42 Lifting & Mounting Weights (SI Units) Table 37: Lifting & Mounting Weights - (SI units) continued LIFTING WEIGHT FOR EACH POINT (KG) MOUNTING LOADS FOR EACH POINT (KG) # OF Unit Size FANS M9 M10 M11 M12 AWS240BDP 1224 1219 1029 1024 787 1327 1321 1158...
  • Page 43: Lifting & Mounting Locations - Index Of Drawings

    Fans Figure & Page AWS170BDS Standard Figure 27, page 50 AWS190BDS Standard page 44 AWS190BDS Standard Figure 28, page 50 AWS210BDS Standard page 44 AWS200BDS Standard Figure 28, page 50 AWS210BDH High page 44 AWS210BDH High Figure 28, page 50...
  • Page 44: Dimensions (Non-Vfd)

    5820 229.1 4791 188.6 17.0 4910 193.3 2100 82.7 23.6 2225 87.6 331426601C020A AWS 10 FAN DIM. DWG Figure 15: AWS210BDS/H, AWS225BDS (non-VFD) 5820 229.1 4791 188.6 17.0 4910 193.3 2100 82.7 23.6 2225 87.6 *3314266020A1* AWS 12 FAN DIM. DWG...
  • Page 45 Lifting & Mounting Dimensions (non-VFD) Figure 16: AWS230BDH, AWS250BDS/H, AWS260BDS (non-VFD) 6720 264.6 4791 188.6 17.0 4910 193.3 6310 248.4 2100 82.7 23.6 2225 87.6 AWS 14 FAN DIM. DWG 331426603C020A Figure 17: AWS240BDP, AWS280BDH, AWS290BDS, AWS300BDH, AWS310BDS (non-VFD) 7620 300.0 6791 267.4...
  • Page 46 Lifting & Mounting Dimensions (non-VFD) Figure 18: AWS265BDP, AWS290BDP (non-VFD) 8520 335.5 7484 294.6 4791 188.6 2381 93.7 17.0 8110 319.3 4910 193.3 2100 82.7 23.6 2225 87.6 331426605C020A AWS 18 FAN DIM. DWG Figure 19: AWS310BDP, AWS330BDH/P, AWS350BDS/H, AWS375BDS (non-VFD) 9421 370.9 8384...
  • Page 47 Lifting & Mounting Dimensions (non-VFD) Figure 20: AWS365BDP, AWS390BDH (non-VFD) 10720 422.0 8384 330.1 5401 212.6 2381 93.7 17.0 9110 358.7 6000 236.2 2100 82.7 23.6 2225 87.6 AWS 22 FAN DIM. DWG 331426607C020A Figure 21: AWS400BTS, AWS425BTS (non-VFD) 10718 422.0 9615 378.6...
  • Page 48 Lifting & Mounting Dimensions (non-VFD) Figure 22: AWS400BDP, AWS410BDH (non-VFD) 11620 457.5 9962 392.2 5401 212.6 2381 93.7 17.0 10499 413.4 8147 320.8 5949 234.2 2100 82.7 23.6 2225 87.6 AWS 24 FAN DIM. DWG 331426608C020A Figure 23: AWS450BTS/H, AWS470BTS (non-VFD) 11620 457.5 9962...
  • Page 49 Lifting & Mounting Dimensions (non-VFD) Figure 24: AWS475BTH, AWS500BTS (non-VFD) 12520 492.9 10564 415.9 6438 253.4 2381 93.7 17.0 10501 413.4 8096 318.8 6000 236.2 2100 82.7 23.6 2225 87.6 AWS 3C-26 FAN DIM. DWG 331426611D020A Figure 25: AWS500BTH, AWS525BTS (non-VFD) 13420 528.4 10761...
  • Page 50: Dimensions (Vfd)

    Lifting & Mounting Dimensions (VFD) Figure 27: AWS170BDS (VFD) Lifting & Mounting Dimensions (VFD) Ø .750 TYP. 2225 87.6 AWS-B-0B WITH VFD 10 FAN DIM. DWG 333687301 3336873 BOTTOM VIEW Figure 28: AWS190BDS, AWS200BDS, AWS210BDH (VFD) Ø .750 TYP. 2225 87.6 AWS-B-0B WITH VFD 12 FAN DIM.
  • Page 51 Lifting & Mounting Dimensions (VFD) Figure 29: AWS230BDH, AWS250BDH (VFD) Ø .750 TYP. 2225 87.6 3336873 AWS-B-0B WITH VFD 14 FAN DIM. DWG BOTTOM VIEW Figure 30: AWS240BDP, AWS280BDH, AWS300BDH (VFD) Ø .750 TYP. 2225 87.6 AWS-B-0B WITH VFD 16 FAN DIM. DWG BOTTOM VIEW 3336873 333687304...
  • Page 52 Lifting & Mounting Dimensions (VFD) Figure 31: AWS265BDP, AWS290BDP (VFD) Ø .750 TYP. 2225 87.6 BOTTOM VIEW 3336873 AWS-B-0B WITH VFD 18 FAN DIM. DWG Figure 32: AWS310BDP, AWS330BDH/P, AWS350BDH (VFD) Figure 33: AWS365BDP, 390BDH (VFD) 11688 10078 6968 3349 1568 460.2 396.8...
  • Page 53 Lifting & Mounting Dimensions (VFD) Figure 34: AWS400BDP, AWS410BDH (VFD) 12589 495.6 11470 6918 3349 451.6 272.3 131.9 34.3 10930 9116 6369 3068 1568 430.3 358.9 250.8 120.8 61.7 16.1 2225 87.6 AWS-B W/VFD 24 2C FAN DIM. DWG 332824801 Figure 35: AWS450BTH (VFD) 12589 495.6...
  • Page 54 Lifting & Mounting Dimensions (VFD) Figure 37: AWS500BTH (VFD) 14388 566.5 11729 461.8 7404 291.5 3349 131.9 34.3 12968 510.6 9968 392.4 6968 274.3 3068 120.8 1568 61.7 16.1 2225 87.6 332825101 AWS-B W/ VFD 28 FAN DIM. DWG Figure 38: AWS530BTH (VFD) 15288 601.9 12714...
  • Page 55: Isolator Locations And Kit Numbers

    Isolator Locations and Kit Numbers Transfer the unit as indicated in the Installation and Figure 39: Spring Isolators - CP-4 Isolator Locations and Kit Numbers Maintenance Manual, IM 1167, available on www.DaikinMcQuay.com. In all cases, set the unit in place and level with a spirit level.
  • Page 56 Isolator Locations and Kit Numbers Table 40: Spring Isolators (for 60Hz non-VFD Units with Aluminum Fin Condensers) # O F UN IT S IZ E Kit P / N M 10 F A N S 332620800 332620800 332620800 332620800 332620500 332620500 A WS1 90B DS 332320828 Dark Green Dark Green Dark Green Dark Green...
  • Page 57 Isolator Locations and Kit Numbers Table 41: Spring Isolators (for 60Hz non-VFD Units with Copper Fin Condensers) # OF UN IT SIZ E Kit P / N M 10 F A N S 332620800 332620800 332620800 332620800 332620600 332620600 AWS1 90BDS 332320851 Dark Green Dark Green Dark Green Dark Green Dark Purple Dark P urple 332620900 332620900 332620800 332620800 332620600 332620600...
  • Page 58 Isolator Locations and Kit Numbers Table 42: RIS Isolators (for 60Hz non-VFD Units with Aluminum Fin Condensers) # O F UN IT S IZ E Kit P / N M 10 F A N S 331 481 404 331 481 404 331 481 403 331 481 403 331 481 402...
  • Page 59 Isolator Locations and Kit Numbers Table 43: RIS Isolators (for 60Hz non-VFD Units with Copper Fin Condensers) # OF UN IT SIZ E Kit P / N M 10 F A N S 331 481 404 331 481 404 331 481 403 331 481 403 331 481 402 331 481 402...
  • Page 60 Isolator Locations and Kit Numbers Table 44: Spring Isolators (for 60Hz Units with optional VFD and Aluminum Fin Condensers) # OF  UNIT SIZE Kit P/N M 10 FANS M 11 M 12 332620800 332620800 332620800 332620800 332620800 332620800 332620800 332620800 AW S1 70BDS *VFD* 10 332320821 Dark Green Dark Green Dark Green Dark Green Dark Green Dark Green Dark Green Dark Green 332620800 332620800 332620800 332620800 332620800 332620800 332620800 332620800...
  • Page 61 Isolator Locations and Kit Numbers Table 45: Spring Isolators (for 60Hz Units with optional VFD and Copper Fin Condensers) # OF  UNIT SIZE Kit P/N M 10 FANS M 11 M 12 332620800 332620800 332620800 332620800 332620800 332620800 332620800 332620800 AW S1 70BDS *VFD* 332320821 Dark G reen Dark G reen Dark G reen Dark G reen Dark G reen Dark G reen Dark G reen Dark G reen 332620800 332620800 332620800 332620800 332620800 332620800 332620800 332620800...
  • Page 62 Isolator Locations and Kit Numbers Table 46: RIS Isolators (for 60Hz Units with optional VFD and Aluminum Fin Condensers) # OF  UNIT SIZE Kit P/N M 10 FANS M 11 M 12 331 481 402 331 481 402 331 481 402 331 481 402 331 481 402 331 481 402 331 481 402...
  • Page 63 Isolator Locations and Kit Numbers Table 47: RIS Isolators (for 60Hz Units with optional VFD and Copper Fin Condensers) # OF  UNIT SIZE Kit P/N M 10 FANS M 11 M 12 331 481 403 331 481 403 331 481 403 331 481 403 331 481 403 331 481 403 331 481 403...
  • Page 64: Electrical Data

    Electrical Data Field Wiring Unit wire size ampacity (MCA) is equal to 125% of the Electrical Data largest compressor-motor RLA plus 100% of RLA of all Wiring must comply with all applicable codes and ordinances. other loads in the circuit including control transformer. Warranty does not cover damage to the equipment caused by Wire size ampacity for separate 115V control circuit wiring not complying with specifications.
  • Page 65: Wiring Diagram

    Wiring Diagram Figure 41: Field Wiring Diagram Wiring Diagram IM 1167...
  • Page 66 Wiring Diagram Figure 42: Field Wiring Diagram (continued) IM 1167...
  • Page 67: Multipoint Electrical Data (Non-Vfd)

    Multipoint Electrical Data (non-VFD) Table 48: Multipoint Electrical Data (60Hz, standard efficiency, non-VFD models) Multipoint Electrical Data (non-VFD) Circuit 1 (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage # of Fans Recommended Fuse Size Maximum Fuse Size # of Leads...
  • Page 68 Multipoint Electrical Data (non-VFD) Table 49: Multipoint Electrical Data (60Hz, standard efficiency, non-VFD models), continued Circuit 1 (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage # of Fans Recommended Fuse Size Maximum Fuse Size # of Leads Wire Size...
  • Page 69 Multipoint Electrical Data (non-VFD) Table 50: Multipoint Electrical Data (60Hz, standard efficiency, non-VFD models), continued Circuit 1 (Wire 75°C f or SP Pow er Block / Disconnect Sw . - 90°C f or SP HSCCR) Model Voltage # of Fans Recommended Fuse Size Maximum Fuse Size # of Leads...
  • Page 70 Multipoint Electrical Data (non-VFD) Table 51: Multipoint Electrical Data (60Hz, standard efficiency, non-VFD models), continued Circuit 1 (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage # of Fans Recommended Fuse Size Maximum Fuse Size # of Leads Wire Size...
  • Page 71 Multipoint Electrical Data (non-VFD) Table 52: Multipoint Electrical Data (60Hz, standard efficiency, non-VFD models), continued Circuit 1 (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage # of Fans Recommended Fuse Size Maximum Fuse Size # of Leads Wire Size...
  • Page 72 Multipoint Electrical Data (non-VFD) Table 53: Multipoint Electrical Data (60Hz, high efficiency, non-VFD models) Circuit 1 (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage # of Fans Recommended Fuse Size Maximum Fuse Size # of Leads Wire Size...
  • Page 73 Multipoint Electrical Data (non-VFD) Table 54: Multipoint Electrical Data (60Hz, high efficiency, non-VFD models), continued Circuit 1 (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage # of Fans Recommended Fuse Size Maximum Fuse Size # of Leads Wire Size...
  • Page 74 Multipoint Electrical Data (non-VFD) Table 55: Multipoint Electrical Data (60Hz, high efficiency, non-VFD models), continued Circuit 1 (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage # of Fans Recommended Fuse Size Maximum Fuse Size # of Leads Wire Size...
  • Page 75 Multipoint Electrical Data (non-VFD) Table 56: Multipoint Electrical Data (60Hz, high efficiency, non-VFD models), continued Circuit 1 (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage # of Fans Recommended Fuse Size Maximum Fuse Size # of Leads Wire Size...
  • Page 76 Multipoint Electrical Data (non-VFD) Table 57: Multipoint Electrical Data (60Hz, premium efficiency, non-VFD models) Circuit 1 (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage # of Fans Recommended Fuse Size Maximum Fuse Size # of Leads Wire Size...
  • Page 77 Multipoint Electrical Data (non-VFD) Table 58: Multipoint Electrical Data (60Hz, premium efficiency, non-VFD models), continued Circuit 1 (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage # of Fans Recommended Fuse Size Maximum Fuse Size # of Leads Wire Size...
  • Page 78: Multipoint Field Wiring Data (Non-Vfd)

    Multipoint Field Wiring Data (non-VFD) Table 59: Multipoint Field Wiring Data (60Hz, Standard efficiency, non-VFD models) Multipoint Field Wiring Data (non-VFD) Circuit 1 # o f High Short Circuit Current Rating Disconnect Sw itch Fans Circuit Breaker (note 1) Model V oltage Size Std Lug Size...
  • Page 79 Multipoint Field Wiring Data (non-VFD) Table 60: Multipoint Field Wiring Data (60Hz, Standard efficiency, non-VFD models), continued Circuit 1 # o f High Short Circuit Current Rating Disconnect Sw itch F ans Model HZ V oltage Circuit Breaker (note 1) Size Std Lug Size Size...
  • Page 80 Multipoint Field Wiring Data (non-VFD) Table 61: Multipoint Field Wiring Data (60Hz, Standard efficiency, non-VFD models), continued Circuit 1 # o f High Short Circuit Current Rating Disconnect Sw itch Fans Model V oltage Circuit Breaker (note 1) Size Std Lug Size Size Std Lug Size C ircuit...
  • Page 81 Multipoint Field Wiring Data (non-VFD) Table 62: Multipoint Field Wiring Data (60Hz, Standard efficiency, non-VFD models), continued Circuit 1 # o f High Short Circuit Current Rating Disconnect Sw itch F ans Model HZ Voltage Circuit Breaker (note 1) Size Std Lug Size Size Std Lug Size...
  • Page 82 Multipoint Field Wiring Data (non-VFD) Table 63: Multipoint Field Wiring Data (60Hz, High efficiency, non-VFD models) Circuit 1 # o f High Short Circuit Current Rating Disconnect Sw itch Fans Model V oltage Circuit Breaker (note 1) Size Std Lug Size Size Std Lug Size Circuit...
  • Page 83 Multipoint Field Wiring Data (non-VFD) Table 65: Multipoint Field Wiring Data (60Hz, High efficiency, non-VFD models), continued Circuit 1 # o f High Short Circuit Current Rating Disconnect Sw itch Fans Model V oltage Circuit Breaker (note 1) Size Std Lug Size Size Std Lug Size Circuit...
  • Page 84 Multipoint Field Wiring Data (non-VFD) Table 66: Multipoint Field Wiring Data (60Hz, High efficiency, non-VFD models), continued Circuit 1 # o f High Short Circuit Current Rating Disconnect Sw itch Fans Model V oltage Circuit Breaker (note 1) Size Std Lug Size Size Std Lug Size C ircuit...
  • Page 85 Multipoint Field Wiring Data (non-VFD) Table 68: Multipoint Field Wiring Data (60Hz, High efficiency, non-VFD models), continued Circuit 1 # o f High Short Circuit Current Rating Disconnect Sw itch Fans Model Voltage Circuit Breaker (note 1) Size Std Lug Size Size Std Lug Size C ircuit...
  • Page 86 Multipoint Field Wiring Data (non-VFD) Table 69: Multipoint Field Wiring Data (60Hz, Premium efficiency, non-VFD models) Circuit 1 # o f Disconnect Sw itch High Short Circuit Current Rating Fans Model V oltage Size Std Lug Size Size Std Lug Size C ircuit 208V 600A...
  • Page 87 Multipoint Field Wiring Data (non-VFD) Table 70: Multipoint Field Wiring Data (60Hz, Premium efficiency, non-VFD models), continued Circuit 1 # o f Disconnect Sw itch High Short Circuit Current Rating Fans Model V oltage Size Std Lug Size Size Std Lug Size C ircuit 208V 800A...
  • Page 88: Terminal Amps (Non-Vfd) (Single/Multi-Point)

    Terminal Amps (non-VFD) (single/multi-point) Table 71: Terminal Amps Electrical Data (60Hz) Terminal Amps (non-VFD) (single/multi-point) Compressor Locked Rotor Amps Inrush Amps Inrush Amps Rated Load Amps Compressor Solid State Starter Y-Delta Starter Model Voltage # of Fans Motor Motor CIR 3 CIR 1 CIR 2 CIR 1 CIR 2 CIR 3 CIR 1...
  • Page 89 Terminal Amps (non-VFD) (single/multi-point) Table 72: Terminal Amps Electrical Data (60Hz), continued Compressor Locked Rotor Amps Inrush Amps Inrush Amps Rated Load Amps Compressor Solid State Starter Y-Delta Starter Model Voltage # of Fans Motor Motor CIR 1 CIR 2 CIR 3 CIR 1 CIR 2...
  • Page 90 Terminal Amps (non-VFD) (single/multi-point) Table 73: Terminal Amps Electrical Data (60Hz), continued Compressor Locked Rotor Amps Inrush Amps Inrush Amps Rated Load Amps Compressor Solid State Starter Y-Delta Starter Model Voltage # of Fans Motor Motor CIR 1 CIR 2 CIR 3 CIR 1 CIR 2...
  • Page 91 Terminal Amps (non-VFD) (single/multi-point) Table 74: Terminal Amps Electrical Data (60Hz), continued Compressor Locked Rotor Amps Inrush Amps Inrush Amps Compressor Solid State Starter Y-Delta Starter Rated Load Amps Model Voltage # of Fans Motor Motor CIR 1 CIR 2 CIR 3 CIR 1 CIR 2 CIR 3...
  • Page 92: Single-Point Electrical Data (Non-Vfd)

    Single-point Electrical Data (non-VFD) Table 75: Single-point Electrical Data (60 Hz, Standard efficiency, non-VFD models) Single-point Electrical Data (non-VFD) # of (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage Fans Recommended Fuse Size Maximum Fuse Size # of Leads Wire Size # of Hubs Hub Size...
  • Page 93 Single-point Electrical Data (non-VFD) Table 76: Single-point Electrical Data (60 Hz, Standard efficiency, non-VFD models) continued # of (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage Fans Recommended Fuse Size Maximum Fuse Size # of Leads Wire Size # of Hubs Hub Size 208V...
  • Page 94 Single-point Electrical Data (non-VFD) Table 77: Single-point Electrical Data (60 Hz, High efficiency, non-VFD models) # of (Wire 75°C for SP Power Block / Disconnect Sw. - 90°C for SP HSCCR) Model HZ Voltage Fans Recommended Fuse Size Maximum Fuse Size # of Leads Wire Size # of Hubs Hub Size 208V...
  • Page 95 Single-point Electrical Data (non-VFD) Table 78: Single-point Electrical Data (60 Hz, High efficiency, non-VFD models) continued # of (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage Fans Recommended Fuse Size Maximum Fuse Size # of Leads Wire Size # of Hubs Hub Size 208V...
  • Page 96 Single-point Electrical Data (non-VFD) Table 79: Single-point Electrical Data (60 Hz, Premium efficiency, non-VFD models) # of (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage Fans Recommended Fuse Size Maximum Fuse Size # of Leads Wire Size # of Hubs Hub Size 208V...
  • Page 97: Single-Point Field Wiring Data (Non-Vfd)

    Single-point Field Wiring Data (non-VFD) Table 80: Single-point Field Wiring Data (60 Hz, Standard efficiency, non-VFD models) Single-point Field Wiring Data (non-VFD) High Short Circuit Current Rating Pow er Block Disconnect Sw itch # of Circuit Breaker (note 1) Model HZ Voltage Fans Size...
  • Page 98 Single-point Field Wiring Data (non-VFD) Table 81: Single-point Field Wiring Data (60 Hz, Standard efficiency, non-VFD models) continued High Short Circuit Current Rating # of Pow er Block Disconnect Sw itch Model HZ Voltage Circuit Breaker (note 1) Fans Size Std Lug Size Size Std Lug Size...
  • Page 99 Single-point Field Wiring Data (non-VFD) Table 83: Single-point Field Wiring Data (60 Hz, High efficiency, non-VFD models) continued High Short Circuit Current Rating # of Pow er Block Disconnect Sw itch Model HZ Voltage Circuit Breaker (note 1) Fans Size Std Lug Size Size Std Lug Size...
  • Page 100 Single-point Field Wiring Data (non-VFD) Table 84: Single-point Field Wiring Data (60 Hz, Premium efficiency, non-VFD models) High Short Circuit Current Rating # of Pow er Block Disconnect Sw itch Model HZ Voltage Circuit Breaker (note 1) Fans Size Std Lug Size Size Std Lug Size Size...
  • Page 101: Multipoint Electrical Data (Vfd)

    Multipoint Electrical Data (VFD) Table 85: Multipoint Electrical Data (60Hz, standard and high efficiency, VFD models) Multipoint Electrical Data (VFD) Circuit 1 (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage # of Fans Recommended Fuse Size Maximum Fuse Size...
  • Page 102 Multipoint Electrical Data (VFD) Table 86: Multipoint Electrical Data (60Hz, standard efficiency, VFD models), continued Circuit 1 # of Fans (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage per Circuit Recommended Fuse Size Maximum Fuse Size # of Leads...
  • Page 103 Multipoint Electrical Data (VFD) Table 87: Multipoint Electrical Data (60Hz, premium efficiency, VFD models), continued Circuit 1 (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage # of Fans Recommended Fuse Size Maximum Fuse Size # of Leads Wire Size...
  • Page 104: Multipoint Field Wiring Data (Vfd)

    Multipoint Field Wiring Data (VFD) Table 88: Multipoint Field Wiring Data (VFD models) Multipoint Field Wiring Data (VFD) Circuit 1 Circuit 2 Circuit 3 # o f Disconnect Sw itch/ Disconnect Sw itch/ Disconnect Sw itch/ Fans Model HZ Voltage Circuit Breaker Circuit Breaker Circuit Breaker...
  • Page 105: Terminal Amps (Vfd) (Single- And Multi-Point)

    Terminal Amps (VFD) (single- and multi-point) Table 89: Terminal Amps Electrical Data (60Hz) Terminal Amps (VFD) (single- and multi-point) Compressor Inrush Amps VFD Rated Load Amps # of Fans Model Voltage Motor Motor per Circuit CIR 1 CIR 2 CIR 3 CIR 1 CIR 2 CIR 3 380V 170BDS VFD...
  • Page 106: Single-Point Electrical Data (Vfd)

    Single-point Electrical Data (VFD) Table 90: Single-point Electrical Data (60 Hz, High and Premium efficiency, VFD models) Single-point Electrical Data (VFD) # of (Wire 75°C for SP Pow er Block / Disconnect Sw . - 90°C for SP HSCCR) Model Voltage Fans Recommended Fuse Size Maximum Fuse Size # of Leads...
  • Page 107: Single-Point Field Wiring Data (Vfd)

    Single-point Field Wiring Data (VFD) Table 91: Single-point Field Wiring Data (VFD models) Single-point Field Wiring Data (VFD) # of Pow erBlock Disconnect Sw itch Model HZ Voltage Fans Size Std Lug Size Size Std Lug Size 380V 620A (2/PH) # 6 - 350 MCM 600A (2/PH) 2/0 - 500 MCM 1 70B DSVFD...
  • Page 108: Pressure Drop Data

    Pressure Drop Data Figure 43: Evaporator Pressure Drop: AWS models 170/190 Standard Efficiency Pressure Drop Data A WS- B E v a por a t or P r e s s ur e D r op C ur v e s E v a por a t or E V 4 0 2 7 1 0 1 0 / 9 N 2 19 0 St an dar d 17 0 St an dar d...
  • Page 109 Pressure Drop Data Figure 45: Evaporator Pressure Drop: AWS models 200/225 Standard Efficiency and 230/250 High Efficiency AWS-B Evapor ator Pr essur e Dr op Cur ves Evapor ator EV40271212/ 7 N2 250 Hi gh 230 High 225 Standar d 200 Standar d (ft) 1 000...
  • Page 110 Pressure Drop Data Figure 47: Evaporator Pressure Drop: AWS models 280/300 High Efficiency A WS- B E v a por a t or P r e s s ur e D r op C ur v e s E v a por a t or E V 5 0 2 7 1 4 1 4 / 7 N 2 300 Hi gh 280 Hi gh ( f t )
  • Page 111 Pressure Drop Data Figure 49: Evaporator Pressure Drop: AWS models 350/375 Standard Efficiency and 330/350/390/410 High Efficiency AWS- B Evapor at or Pr essur e Dr op Cur ves Evapor at or EV6633111111/ 5 N2 410 Hi g h 3 90 Hi g h 375 St an dar d 35 0 Hi g h 35 0 St andar d...
  • Page 112 Pressure Drop Data Figure 50: Evaporator Pressure Drop: AWS models 240/265 Premium Efficiency A WS- B E v a por a t or P r e s s ur e D r op C ur v e s E v a por a t or E V 5 0 3 9 1 3 1 3 / 1 1 N 2 2 6 5 Pr emi u m 2 4 0 Pr emi u m ( f t )
  • Page 113 Pressure Drop Data Figure 52: Evaporator Pressure Drop: AWS models 470/500/525/550 Standard Efficiency & 475/500/530 High Efficiency A WS- B E v a por a t or P r e s s ur e D r op C ur v e s E v a por a t or E V 6 6 3 3 1 1 1 1 1 1 / 5 N 2 5 5 0 St an dar d 5 3 0 Hi g h...
  • Page 114 Pressure Drop Data Figure 53: Evaporator Pressure Drop: AWS models 290/310 Premium Efficiency A WS- B E v a por a t or P r e s s ur e D r op C ur v e s E v a por a t or E V 6 6 3 9 1 4 1 4 / 1 1 N 2 3 10 Pr emi u m 2 9 0 Pr emi u m ( f t )
  • Page 115: Remote Evaporators

    This section contains data specific to AWS-B models with Interpolation is permitted, extrapolation is not. Consult Remote Evaporators remote evaporators. Information includes: the Daikin McQuay Technical Response Center for • Remote Evaporator Field Wiring Notes-this page piping installations outside the published • Refrigerant Piping - page 116 recommendations.
  • Page 116: Remote Evaporator Refrigerant Piping

    Service Form SF99006 and an isometric sketch of the Remote Piping Layout showing pipe size, location of fittings, measured lengths, and elevations MUST BE SUBMITTED TO Daikin McQuay Technical Response Center and reviewed at least two weeks prior to beginning piping installation.
  • Page 117 Remote Evaporators Figure 55: Piping Schematic, Remote Evaporator (One of Two Circuits) AWS Remote Evaporator Models (No Economizer) NOTE : PIPING SHOWN FOR ONE SYSTEM OF UNIT SCHRADER UNIT HAS TWO INDEPENDENT SYSTEMS. CONDENSER VALVE ASSEMBLY (HEADER ) FLOW OIL PRESS . BUTTERFLY DISCHARGE TRANSDUCER...
  • Page 118 4 1/8 3 5/8 1.23 3 5/8 1.84 4 1/8 1.32 4 1/8 1.66 4 1/8 1.99 4 1/8 2.38 AWS210BDS 4 1/8 3 5/8 1.23 3 5/8 1.84 4 1/8 1.32 4 1/8 1.66 4 1/8 1.99 4 1/8 2.38...
  • Page 119 Size AWS190BDS 3 5/8 1.23 3 5/8 1.84 3 5/8 AWS190BDS 3 5/8 1.23 3 5/8 1.84 3 5/8 AWS210BDS 3 5/8 1.23 3 5/8 1.84 3 5/8 AWS210BDS 3 5/8 1.73 3 5/8 2.60 3 5/8 AWS225BDS 3 5/8 1.73...
  • Page 120 Remote Evaporators Table 96 (continued) Recommended Upflow Suction Recom m ended Vertical or Upflow Max. Suct. Nom inal Suction Line Size Riser Line Size Tons Model # Circuit UP TO 50 EQUIV. UP TO 75 EQUIV. for Vertical Upflow to Circuit Com pr.
  • Page 121 Remote Evaporators Table 96 (continued) Recommended Upflow Suction Recom m ended Vertical or Upflow Max. Suct. Nom inal Suction Line Size Riser Line Size Tons Model # Circuit UP TO 50 EQUIV. UP TO 75 EQUIV. for Vertical Upflow to Circuit Com pr.
  • Page 122 2.53 1 5/8 0.70 1 5/8 1.05 1 5/8 1.41 1 5/8 1.76 1 5/8 2.11 1 5/8 2.53 AWS210BDS 1 5/8 0.70 1 5/8 1.05 1 5/8 1.41 1 5/8 1.76 1 5/8 2.11 1 5/8 2.53 1 5/8 0.99 1 5/8 1.49...
  • Page 123: Remote Evaporator Dimensions

    Remote Evaporator Dimensions Figure 56: Evaporator Models Remote Evaporator Dimensions AWS Model Evaporator Model AWS Model Evaporator Model AWS190BDS EV4027 AWS350BDS EV5027 AWS210BDS EV4027 AWS350BDH EV5027 AWS210BDH EV4027 AWS365BDP EV6639 AWS225BDS EV4027 AWS375BDS EV5027 AWS230BDH EV4027 AWS390BDH EV5027 AWS240BDP EV5039...
  • Page 124 Remote Evaporator Dimensions Figure 58: Evaporator Model: EV5027 EVAPORATOR: EV5027 PART NO. 332532200 UNIT MODELS: AWS290BDS AWS310BDS AWS350BDS AWS375BDS AWS280BDH 2360 AWS300BDH 12.2 92.9 16.7 AWS330BDH AWS350BDH AWS390BDH AWS410BDH EVAPORATOR 1.63IN/41.5MM I.D. NAME PLATE 4.13IN/105MM I.D. LIQUID CONNECTION 13.9 SUCTION CONNECTION 219.2 8.63 SCH.
  • Page 125 Remote Evaporator Dimensions Figure 60: Evaporator Model: EV6639 EVAPORATOR: EV6639 PART NO. 332532400 UNIT MODELS: AWS290BDP AWS310BDP AWS330BDP AWS365BDP 3430 AWS400BDP 14.4 135.0 19.3 4.13IN/105MM I.D. 1.63IN/41.5MM I.D. SUCTION CONNECTION LIQUID CONNECTION 105.8 16.9 EVAPORATOR NAME PLATE 105.8 10.75 SCH. 40 PIPE ASME/CRN 105.8 VICTAULIC GROOVED QTY.2...
  • Page 126: Remote Evaporator Unit Dimensions

    Remote Evaporator Unit Dimensions (Non-VFD) Figure 62: AWS190BDS Remote Evaporator (Non-VFD) Remote Evaporator Unit Dimensions (Non-VFD) IM 1167...
  • Page 127 Remote Evaporator Unit Dimensions (Non-VFD) Figure 63: AWS210BDS, AWS225BDS Remote Evaporator (Non-VFD) IM 1167...
  • Page 128 Remote Evaporator Unit Dimensions (Non-VFD) Figure 64: AWS210BDH Remote Evaporator (Non-VFD) IM 1167...
  • Page 129 Remote Evaporator Unit Dimensions (Non-VFD) Figure 65: AWS250BDS, AWS260BDS Remote Evaporator (Non-VFD) IM 1167...
  • Page 130 Remote Evaporator Unit Dimensions (Non-VFD) Figure 66: AWS230BDH, AWS250BDH Remote Evaporator (Non-VFD) IM 1167...
  • Page 131 Remote Evaporator Unit Dimensions (Non-VFD) Figure 67: AWS290BDS, AWS310BDS Remote Evaporator (Non-VFD) IM 1167...
  • Page 132 Remote Evaporator Unit Dimensions (Non-VFD) Figure 68: AWS240BDP, AWS280BDH, AWS300BDH Remote Evaporator (Non-VFD) IM 1167...
  • Page 133 Remote Evaporator Unit Dimensions (Non-VFD) Figure 69: AWS265BDP, AWS290BDP Remote Evaporator (Non-VFD) IM 1167...
  • Page 134 Remote Evaporator Unit Dimensions (Non-VFD) Figure 70: AWS350BDS, AWS375BDS Remote Evaporator (Non-VFD) IM 1167...
  • Page 135 Remote Evaporator Unit Dimensions (Non-VFD) Figure 71: AWS310BDP, AWS330BDP, AWS330BDH, AWS350BDH Remote Evaporator (Non-VFD) IM 1167...
  • Page 136 Remote Evaporator Unit Dimensions (Non-VFD) Figure 72: AWS365BDP, AWS390BDH Remote Evaporator (Non-VFD) IM 1167...
  • Page 137 Remote Evaporator Unit Dimensions (Non-VFD) Figure 73: AWS400BDP, AWS410BDH Remote Evaporator (Non-VFD) IM 1167...
  • Page 138 Remote Evaporator Unit Dimensions (Non-VFD) Figure 74: AWS400BTS, AWS425BTS Remote Evaporator (Non-VFD) (Page 1 of 2) IM 1167...
  • Page 139 Remote Evaporator Unit Dimensions (Non-VFD) Figure 75: AWS400BTS, AWS425BTS Remote Evaporator (Non-VFD) (Page 2 of 2) IM 1167...
  • Page 140 Remote Evaporator Unit Dimensions (Non-VFD) Figure 76: AWS450BTS, AWS450BTH, AWS470BTS Remote Evaporator (Non-VFD) (Page 1 of 3) IM 1167...
  • Page 141 Remote Evaporator Unit Dimensions (Non-VFD) Figure 77: AWS450BTH Remote Evaporator (Non-VFD) (Page 2 of 3, see also Figure IM 1167...
  • Page 142 Remote Evaporator Unit Dimensions (Non-VFD) Figure 78: AWS450BTS, AWS470BTS Remote Evaporator (Non-VFD) (Page 3 of 3, see also Figure IM 1167...
  • Page 143 Remote Evaporator Unit Dimensions (Non-VFD) Figure 79: AWS475BTH, AWS500BTS Remote Evaporator (Non-VFD) (Page 1 of 3) IM 1167...
  • Page 144 Remote Evaporator Unit Dimensions (Non-VFD) Figure 80: AWS475BTH Remote Evaporator (Non-VFD) (Page 2 of 3) IM 1167...
  • Page 145 Remote Evaporator Unit Dimensions (Non-VFD) Figure 81: AWS500BTS Remote Evaporator (Non-VFD) (Page 3 of 3) IM 1167...
  • Page 146 Remote Evaporator Unit Dimensions (Non-VFD) Figure 82: AWS500BTH, AWS525BTS Remote Evaporator (Non-VFD) (Page 1 of 3) IM 1167...
  • Page 147 Remote Evaporator Unit Dimensions (Non-VFD) Figure 83: AWS500BTH Remote Evaporator (Non-VFD) (Page 2 of 3) IM 1167...
  • Page 148 Remote Evaporator Unit Dimensions (Non-VFD) Figure 84: AWS525BTS Remote Evaporator (Non-VFD) (Page 3 of 3) IM 1167...
  • Page 149 Remote Evaporator Unit Dimensions (Non-VFD) Figure 85: AWS530BTH, AWS550BTS Remote Evaporator (Non-VFD) (Page 1 of 3) IM 1167...
  • Page 150 Remote Evaporator Unit Dimensions (Non-VFD) Figure 86: AWS530BTH Remote Evaporator (Non-VFD) (Page 2 of 3) IM 1167...
  • Page 151 Remote Evaporator Unit Dimensions (Non-VFD) Figure 87: AWS550BTS Remote Evaporator (Non-VFD) (Page 3 of 3) IM 1167...
  • Page 152: Remote Evaporator Lifting & Mounting Weights

    Remote Evaporator Unite Dimensions (VFD) Figure 88: AWS170BDS(380-460V) Remote Evaporator (VFD) Remote Evaporator Unite Dimensions (VFD) IM 1167...
  • Page 153 Remote Evaporator Unite Dimensions (VFD) Figure 89: AWS190BDS (380-460V), AWS200BDS(380-460V), AWS210BDH(380-460V) Remote Evaporator (VFD) IM 1167...
  • Page 154: Remote Evaporator Isolators

    Remote Evaporator Unite Dimensions (VFD) Figure 90: AWS230BDH(380-460V), AWS250BDH(380-460V) Remote Evaporator (VFD) IM 1167...
  • Page 155 Remote Evaporator Unite Dimensions (VFD) Figure 91: AWS280BDH (460V), AWS300BDH (460v), AWS240BDP(380-460V) Remote Evaporator (VFD) IM 1167...
  • Page 156 Remote Evaporator Unite Dimensions (VFD) Figure 92: AWS280BDH(380-400V), AWS300BDH (380-400V) Remote Evaporator (VFD) IM 1167...
  • Page 157 Remote Evaporator Unite Dimensions (VFD) Figure 93: AWS265BDP(380-460V), AWS290BDP(380-460V) Remote Evaporator (VFD) IM 1167...
  • Page 158 Remote Evaporator Unite Dimensions (VFD) Figure 94: AWS310BDP, AWS330BDP Remote Evaporator (VFD) IM 1167...
  • Page 159 Remote Evaporator Unite Dimensions (VFD) Figure 95: AWS310BDP, AWS330BDP, AWS330BDH, AWS350BDH Remote Evaporator (VFD) IM 1167...
  • Page 160 Remote Evaporator Unite Dimensions (VFD) Figure 96: AWS365BDP, AWS390BDH Remote Evaporator (VFD) IM 1167...
  • Page 161 Remote Evaporator Unite Dimensions (VFD) Figure 97: AWS400BDP(380-460V), AWS410BDH(380-460V) Remote Evaporator (VFD) IM 1167...
  • Page 162 Remote Evaporator Unite Dimensions (VFD) Figure 98: AWS450BTH(380-460V) Remote Evaporator (VFD) IM 1167...
  • Page 163 Remote Evaporator Unite Dimensions (VFD) Figure 99: AWS475BTH (380-460V)Remote Evaporator (VFD) 4032 4.12 O.D. SUCTION #3 5031 158.8 3819 198.1 1.62 O.D. LIQUID #2 4796 150.4 188.8 4.12 O.D. SUCTION #2 35.1 1.62 O.D. LIQUID #3 1.62 O.D. LIQUID #1 37.8 35.1 4981...
  • Page 164 Remote Evaporator Unite Dimensions (VFD) Figure 100: AWS500BTH (380-460V)Remote Evaporator (VFD) IM 1167...
  • Page 165 Remote Evaporator Unite Dimensions (VFD) Figure 101: AWS530BTH (380-460V)Remote Evaporator (VFD) IM 1167...
  • Page 166: Remote Evaporator Physical Data

    AWS190BDS RE (KG) 1786 1778 831 1255 1249 958 (LBS) 4241 4051 2021 1931 2973 2840 2287 2185 1002 958 AWS210BDS RE (KG) 1924 1838 917 1349 1288 1037 991 (LBS) 4372 4352 2015 2006 3073 3059 2342 2331 972...
  • Page 167 Remote Evaporator Lifting & Mounting Weights Table 99, Lifting and Mounting Weights (continued) LIFTING WT FOR EACH POINT (LBS) MOUNTING LOADS FOR EACH POINT (LBS) Unit of UNIT SIZE Measure (LBS) 3913 3895 2216 2206 2700 2688 2191 2181 1238 1232 AWS210BDH RE (KG) 1775 1767 1005 1001...
  • Page 168 Remote Evaporator Isolators Table 100: Spring Isolators for Aluminum Fin Condensers (Non-VFD) Remote Evaporator Isolators Unit M o del # Kit P / N M 10 332620800 332620800 332620800 332620800 332620400 332620400 A WS190B D S 332320838 Dark Green Dark Green Dark Green Dark Green 332620800...
  • Page 169 Remote Evaporator Isolators Table 101: Spring Isolators for Copper Fin Condensers (Non-VFD) Unit M o del # Kit P / N M 10 332620900 332620900 332620800 332620800 332620500 332620500 A WS190B D S 332320839 Gray Gray Dark Green Dark Green Black Black 332620900...
  • Page 170 Remote Evaporator Isolators Table 102: Neoprene in Shear Isolators for Aluminum Fin Condensers (Non-VFD) Unit M o del # Kit P / N M 10 331 481 403 331 481 403 331 481 402 331 481 402 331 481 401 331 481 401 A WS190B D S 332325836 Green...
  • Page 171 Remote Evaporator Isolators Table 103: Neoprene in Shear Isolators for Copper Fin Condensers (Non-VFD) Unit M o del # Kit P / N M 10 331 481 404 331 481 404 331 481 403 331 481 403 331 481 402 331 481 402 A WS190B D S 332325828 Gray...
  • Page 172 Remote Evaporator Isolators Table 104: Spring Isolators for Aluminum Fin Condensers (VFD) Unit M o del # M 10 M 11 M 12 Kit P/ N 332620800 332620800 332620800 332620800 332620500 332620500 332620400 332620400 A WS170B D S 332320840 R E VF D Dk Green Dk Green Dk Green...
  • Page 173 Remote Evaporator Isolators Table 105: Spring Isolators for Copper Fin Condensers (VFD) Unit M o del # M 10 M 11 M 12 Kit P/ N A WS170B D S 332620800 332620800 332620800 332620800 332620500 332620500 332620500 332620500 332320864 R E VF D Dk Green Dk Green Dk Green...
  • Page 174 Remote Evaporator Isolators Table 106: Neoprene in Shear Isolators for Aluminum Fin Condensers (VFD) Unit M o del # M 10 M 11 M 12 Kit P/ N 331 481 403 331 481 403 331 481 403 331 481 403 331 481 401 331 481 401 331 481 401...
  • Page 175 Remote Evaporator Isolators Table 107: Neoprene in Shear Isolators for Copper Fin Condensers (VFD) Unit M o del # M 10 M 11 M 12 Kit P/ N 331 481 403 331 481 403 331 481 402 331 481 402 331 481 402 331 481 402 331 481 401...
  • Page 176: Remote Evaporator Lifting & Mounting Locations

    4790 188.6 16.9 4910 193.3 2100 82.7 23.6 2225 87.6 AWS-B REMOTE 10 FAN DIM. DWG 334042101C0200 Figure 103: AWS210BDS, AWS225BDS, AWS210BDH Remote Evaporator (Non-VFD) Lifting & Mounting Locations 4910 23.6 193.3 5820 229.1 4790 2100 188.6 82.7 16.9 2225 87.6...
  • Page 177 Remote Evaporator Lifting & Mounting Locations (Non-VFD) Locations 6720 264.6 23.6 6310 4790 2100 16.9 248.4 188.6 82.7 2225 87.6 AWS-B REMOTE 14 FAN DIM. DWG 334042301C0300 Figure 105: AWS240BDP, AWS280BDH, AWS300BDH, AWS290BDS, 310BDS Remote Evaporator (Non-VFD) Lifting & Mounting 7620 300.0 6790...
  • Page 178 Remote Evaporator Lifting & Mounting Locations (Non-VFD) Figure 106: AWS265BDP, AWS290BDP Remote Evaporator (Non-VFD) Lifting & Mounting Locations 8520 335.5 2380 4910 8110 23.6 93.7 193.3 319.3 2100 7483 4790 82.7 294.6 188.6 16.9 2225 87.6 AWS-B REMOTE 18 FAN DIM DWG. 334042501C0200 Figure 107: AWS310BDP, 330BDP, AWS330BDH, 350BDH, AWS350BDS, 375BDS Remote Evaporator (Non-VFD) Lifting &...
  • Page 179 Remote Evaporator Lifting & Mounting Locations (Non-VFD) Figure 109: AWS400BDP, AWS410BDH Remote Evaporator (Non-VFD) Lifting & Mounting Locations 11620 457.5 9961 392.2 5400 212.6 2380 93.7 16.9 10501 413.4 8147 320.8 5949 234.2 2100 82.7 23.6 2225 87.6 334042801 AWS-B REMOTE 24 FAN DIM DWG. Figure 110: AWS400BTS, AWS425BTS Remote Evaporator (Non-VFD) Lifting &...
  • Page 180 Remote Evaporator Lifting & Mounting Locations (Non-VFD) Figure 111: AWS450BTS, AWS450BTH, AWS470BTS Remote Evaporator (Non-VFD) Lifting & Mounting Locations IM 1167...
  • Page 181 Remote Evaporator Lifting & Mounting Locations (Non-VFD) Figure 112: AWS475BTH, AWS500BTS Remote Evaporator (Non-VFD) Lifting & Mounting Locations IM 1167...
  • Page 182 Remote Evaporator Lifting & Mounting Locations (Non-VFD) Figure 113: AWS500BTH, AWS525BTS Remote Evaporator (Non-VFD) Lifting & Mounting Locations IM 1167...
  • Page 183 Remote Evaporator Lifting & Mounting Locations (Non-VFD) Figure 114: AWS530BTH, AWS550BTS Remote Evaporator (Non-VFD) Lifting & Mounting Locations (Page 1 of 3) IM 1167...
  • Page 184 Remote Evaporator Lifting & Mounting Locations (VFD) Figure 115: AWS170BDS(380-460V) Remote Evaporator (VFD) Remote Evaporator Lifting & Mounting Locations (VFD) IM 1167...
  • Page 185 Remote Evaporator Lifting & Mounting Locations (VFD) Figure 116: AWS190BDS (380-460V), AWS200BDS(380-460V), AWS210BDH(380-460V) Remote Evaporator (VFD) IM 1167...
  • Page 186 Remote Evaporator Lifting & Mounting Locations (VFD) Figure 117: AWS230BDH(380-460V), AWS250BDH(380-460V) Remote Evaporator (VFD) IM 1167...
  • Page 187 Remote Evaporator Lifting & Mounting Locations (VFD) Figure 118: AWS280BDH (460V), AWS300BDH (460v), AWS240BDP(380-460V) Remote Evaporator (VFD) IM 1167...
  • Page 188 Remote Evaporator Lifting & Mounting Locations (VFD) Figure 119: AWS280BDH(380-400V), AWS300BDH (380-400V) Remote Evaporator (VFD) IM 1167...
  • Page 189 Remote Evaporator Lifting & Mounting Locations (VFD) Figure 120: AWS265BDP(380-460V), AWS290BDP(380-460V) Remote Evaporator (VFD) IM 1167...
  • Page 190 Remote Evaporator Lifting & Mounting Locations (VFD) Figure 121: AWS310BDP, AWS330BDP Remote Evaporator (VFD) IM 1167...
  • Page 191 Remote Evaporator Lifting & Mounting Locations (VFD) Figure 122: AWS310BDP, AWS330BDP, AWS330BDH, AWS350BDH Remote Evaporator (VFD) IM 1167...
  • Page 192 Remote Evaporator Lifting & Mounting Locations (VFD) Figure 123: AWS365BDP, AWS390BDH Remote Evaporator (VFD) IM 1167...
  • Page 193 Remote Evaporator Lifting & Mounting Locations (VFD) Figure 124: AWS400BDP(380-460V), AWS410BDH(380-460V) Remote Evaporator (VFD) IM 1167...
  • Page 194 Remote Evaporator Lifting & Mounting Locations (VFD) Figure 125: AWS450BTH(380-460V) Remote Evaporator (VFD) IM 1167...
  • Page 195 Remote Evaporator Lifting & Mounting Locations (VFD) Figure 126: AWS475BTH (380-460V)Remote Evaporator (VFD) IM 1167...
  • Page 196 Remote Evaporator Lifting & Mounting Locations (VFD) Figure 127: AWS500BTH (380-460V)Remote Evaporator (VFD) IM 1167...
  • Page 197 Remote Evaporator Lifting & Mounting Locations (VFD) Figure 128: AWS530BTH (380-460V)Remote Evaporator (VFD) IM 1167...
  • Page 198 Remote Evaporator (Non-VFD) Physical Data Table 108: Physical Data, Remote Evaporator (Non-VFD) Models (Standard Efficiency) Remote Evaporator (Non-VFD) Physical Data AWS190BDS Remote Evap AWS210BDS Remote Evap AWS225BDS Remote Evap Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1...
  • Page 199 Remote Evaporator (Non-VFD) Physical Data Table 109: Physical Data, Remote Evaporator (Non-VFD) Models (Standard Efficiency) AWS250BDS Remote Evap AWS260BDS Remote Evap AWS290BDS Remote Evap Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 235.8 (829) 250.5 (881) 282.9 (995)
  • Page 200 Remote Evaporator (Non-VFD) Physical Data Table 110: Physical Data, Remote Evaporator (Non-VFD) Models (Standard Efficiency) AWS310BDS Remote Evap AWS350BDS Remote Evap AWS375BDS Remote Evap Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 300.4 (1056) 340.6 (1197) 361.4 (1271)
  • Page 201 Remote Evaporator (Non-VFD) Physical Data Table 111: Physical Data, Remote Evaporator (Non-VFD) Models (Standard Efficiency) AWS400BTS Remote Evap AWS425BTS Remote Evap Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 BASIC DATA Unit Cap. @ AHRI tons (kW) 398.3 (1400) 418.7 (1472) Unit Operating Charge lbs (kg)
  • Page 202 Remote Evaporator (Non-VFD) Physical Data Table 112: Physical Data, Remote Evaporator (Non-VFD) Models (Standard Efficiency) AWS450BTS Remote Evap AWS470BTS Remote Evap Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 BASIC DATA Unit Cap. @ AHRI tons (kW) 441.4 (1552) 459.2 (1615) Unit Operating Charge lbs (kg)
  • Page 203 Remote Evaporator (Non-VFD) Physical Data Table 113: Physical Data, Remote Evaporator (Non-VFD) Models (Standard Efficiency) AWS500BTS Remote Evap AWS525BTS Remote Evap Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 BASIC DATA Unit Cap. @ AHRI tons (kW) 488.3 (1717) 517.7 (1820) Unit Operating Charge lbs (kg)
  • Page 204 Remote Evaporator (Non-VFD) Physical Data Table 114: Physical Data, Remote Evaporator (Non-VFD) Models (Standard Efficiency) AWS550BTS Remote Evap Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 BASIC DATA Unit Cap. @ AHRI tons (kW) 547.3 (1924) Unit Operating Charge lbs (kg) 270 (122) 270 (122) 280 (127)
  • Page 205 Remote Evaporator (Non-VFD) Physical Data Table 115: Physical Data, Remote Evaporator (Non-VFD) Models (High Efficiency) AWS210BDH Remote Evap AWS230BDH Remote Evap AWS250BDH Remote Evap Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 205.7 (723) 225.2 (792) 240.6 (846)
  • Page 206 Remote Evaporator (Non-VFD) Physical Data Table 116: Physical Data, Remote Evaporator (Non-VFD) Models (High Efficiency) AWS280BDH Remote Evap AWS300BDH Remote Evap AWS330BDH Remote Evap Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 271.9 (956) 288.7 (1015) 327.3 (1151)
  • Page 207 Remote Evaporator (Non-VFD) Physical Data Table 117: Physical Data, Remote Evaporator (Non-VFD) Models (High Efficiency) AWS350BDH Remote Evap AWS390BDH Remote Evap AWS410BDH Remote Evap Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 348.1 (1224) 378.7 (1332) 409.8 (1441)
  • Page 208 Remote Evaporator (Non-VFD) Physical Data Table 118: Physical Data, Remote Evaporator (Non-VFD) Models (High Efficiency) AWS450BTH Remote Evap AWS475BTH Remote Evap Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 BASIC DATA Unit Cap. @ AHRI tons (kW) 446.3 (1569) 470.3 (1654) Unit Operating Charge lbs (kg)
  • Page 209 Remote Evaporator (Non-VFD) Physical Data Table 119: Physical Data, Remote Evaporator (Non-VFD) Models (High Efficiency) AWS500BTH Remote Evap AWS530BTH Remote Evap Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 BASIC DATA Unit Cap. @ AHRI tons (kW) 499.4 (1756) 528.3 (1857) Unit Operating Charge lbs (kg)
  • Page 210 Remote Evaporator (Non-VFD) Physical Data Table 120: Physical Data, Remote Evaporator (Non-VFD) Models (Premium Efficiency) AWS240BDP Remote Evap AWS265BDP Remote Evap AWS290BDP Remote Evap Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 232.8 (818) 256.4 (901) 277.5 (976)
  • Page 211 Remote Evaporator (Non-VFD) Physical Data Table 121: Physical Data, Remote Evaporator (Non-VFD) Models (Premium Efficiency) AWS310BDP Remote Evap AWS330BDP Remote Evap AWS365BDP Remote Evap Data CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 303.9 (1068) 324.9 (1142) 355 (1248)
  • Page 212 Remote Evaporator (Non-VFD) Physical Data Table 122: Physical Data, Remote Evaporator (Non-VFD) Models (Premium Efficiency) AWS400BDP Remote Evap Data CIRCUIT 1 CIRCUIT 2 BASIC DATA Unit Cap. @ AHRI tons (kW) 385.4 (1355) Unit Operating Charge lbs (kg) 310 (141) 310 (141) Unit Dimensions 473 x 88 x 100...
  • Page 213: Troubleshooting Chart

    Troubleshooting Chart Troubleshooting Chart Table 123: Troubleshooting Chart PROBLEM POSSIBLE CAUSES POSSIBLE CORRECTIVE STEPS Main power switch open. Close switch. Unit system switch open. Check unit status on MicroTech III display. Close switch. Circuit switch in pumpdown position. Check circuit status on MicroTech III display. Close switch. Check pump operation for flow.
  • Page 214 Troubleshooting Chart Table 123: Troubleshooting Chart Inadequate refrigerant charge quantity. Check liquid line sight glass. Check unit for leaks. Repair and recharge to clear sight glass at full load, all fans on, 75F min OAT.. Clogged liquid line filter-drier. Check pressure drop across the filter-drier. Replace filter-driers. Expansion valve malfunctioning....
  • Page 216 Daikin McQuay Training and Development Now that you have made an investment in modern, efficient Daikin McQuay equipment, its care should be a high priority. For training information, please visit us at www.daikinmcquay.com/training, or call 540-248-9201 to speak to the Training Department.