LG Multi V 5 Data Manual
Show thumbs Also See for Multi V 5:
Table of Contents
Variable Refrigerant Flow Outdoor Units
6.0 to 42.0 Tons
Table of Contents
loading

Summary of Contents for LG Multi V 5

  • Page 1 PERFORMANCE DATA MANUAL Variable Refrigerant Flow Outdoor Units 6.0 to 42.0 Tons...
  • Page 2 A summary list of safety precautions is on page 3. For more technical materials such as submittals, catalogs, installation, owner’s, and service manuals, visit www.lghvac.com. For continual product development, LG Electronics U.S.A., Inc. reserves the right to change specifications without notice. © LG Electronics U.S.A., Inc.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS Performance Data ........................................4-156 Cooling Capacity ........................................5-100 Heating Capacity ....................................... 101-156 Correction Factors ......................................157-160 Defrost Correction Factor for Heating Operation ..............................158 Equivalent Length Calculation ....................................158 Elevation Correction Factors ..................................... 159-160 TABLE OF SYMBOLS This symbol indicates an imminently hazardous situation which, if not avoided, will result in death or DANGER serious injury.
  • Page 4: Performance Data

    PERFORMANCE DATA Cooling Capacity Data on page 5 Heating Capacity Data on page 100...
  • Page 5 COOLING CAPACITY DATA ARUM072BTE5 / ARUM072DTE5 72,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 65.5 1.37 77.8 1.66 90.4 1.97 93.7 2.13 95.1 2.30...
  • Page 6 COOLING CAPACITY DATA ARUM072BTE5 / ARUM072DTE5 72,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 55.2 1.19 65.9 1.43 76.5 1.70 81.8 1.84 87.2 1.97...
  • Page 7 COOLING CAPACITY DATA ARUM072BTE5 / ARUM072DTE5 72,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 43.7 0.93 52.1 1.12 60.8 1.32 64.9 1.42 69.1 1.52...
  • Page 8 COOLING CAPACITY DATA ARUM072BTE5 / ARUM072DTE5 72,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 34.1 0.71 40.5 0.85 47.3 1.00 50.5 1.07 53.7 1.14...
  • Page 9 COOLING CAPACITY DATA ARUM072BTE5 / ARUM072DTE5 72,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 24.3 0.53 28.9 0.63 33.8 0.70 36.0 0.75 38.3 0.81...
  • Page 10 COOLING CAPACITY DATA ARUM096BTE5 / ARUM096DTE5 96,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 87.3 1.71 103.7 2.07 120.5 2.46 125.0 2.65 126.7 2.86...
  • Page 11 COOLING CAPACITY DATA ARUM096BTE5 / ARUM096DTE5 96,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 73.6 1.48 87.8 1.79 102.0 2.12 109.1 2.30 116.2 2.46...
  • Page 12 COOLING CAPACITY DATA ARUM096BTE5 / ARUM096DTE5 96,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 58.3 1.16 69.4 1.39 81.0 1.64 86.6 1.77 92.1 1.89...
  • Page 13 COOLING CAPACITY DATA ARUM096BTE5 / ARUM096DTE5 96,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 45.4 0.89 54.0 1.06 63.0 1.24 67.3 1.33 71.6 1.42...
  • Page 14 COOLING CAPACITY DATA ARUM096BTE5 / ARUM096DTE5 96,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 32.4 0.66 38.6 0.78 45.0 0.87 48.0 0.94 51.0 1.01...
  • Page 15 COOLING CAPACITY DATA ARUM121BTE5 / ARUM121DTE5 120,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 109.1 2.47 129.6 3.00 150.7 3.56 156.2 3.84 158.4 4.15...
  • Page 16 COOLING CAPACITY DATA ARUM121BTE5 / ARUM121DTE5 120,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 92.0 2.14 109.8 2.59 127.5 3.07 136.4 3.32 145.3 3.56...
  • Page 17 COOLING CAPACITY DATA ARUM121BTE5 / ARUM121DTE5 120,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 72.9 1.68 86.8 2.02 101.3 2.38 108.2 2.56 115.2 2.74...
  • Page 18 COOLING CAPACITY DATA ARUM121BTE5 / ARUM121DTE5 120,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 56.8 1.29 67.5 1.53 78.8 1.80 84.1 1.93 89.5 2.05...
  • Page 19 COOLING CAPACITY DATA ARUM121BTE5 / ARUM121DTE5 120,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 40.5 0.96 48.2 1.13 56.3 1.26 60.0 1.36 63.8 1.47...
  • Page 20 COOLING CAPACITY DATA ARUM144BTE5 / ARUM144DTE5 144,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 130.9 2.98 155.5 3.61 180.8 4.29 187.4 4.63 190.1 4.99...
  • Page 21 COOLING CAPACITY DATA ARUM144BTE5 / ARUM144DTE5 144,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 110.4 2.58 131.7 3.12 153.0 3.69 163.7 4.00 174.3 4.29...
  • Page 22 COOLING CAPACITY DATA ARUM144BTE5 / ARUM144DTE5 144,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 87.4 2.03 104.1 2.43 121.5 2.87 129.9 3.09 138.2 3.30...
  • Page 23 COOLING CAPACITY DATA ARUM144BTE5 / ARUM144DTE5 144,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 68.1 1.55 81.0 1.84 94.5 2.17 100.9 2.32 107.4 2.47...
  • Page 24 COOLING CAPACITY DATA ARUM144BTE5 / ARUM144DTE5 144,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 48.6 1.16 57.9 1.36 67.5 1.52 72.0 1.64 76.5 1.77...
  • Page 25 COOLING CAPACITY DATA ARUM168BTE5 / ARUM168DTE5 168,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 152.8 3.92 181.5 4.75 210.9 5.64 218.7 6.09 221.8 6.57...
  • Page 26 COOLING CAPACITY DATA ARUM168BTE5 / ARUM168DTE5 168,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 128.8 3.40 153.7 4.10 178.5 4.86 190.9 5.27 203.4 5.64...
  • Page 27 COOLING CAPACITY DATA ARUM168BTE5 / ARUM168DTE5 168,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor 68/57 73/61 79/64 80/67 85/70 88/73 91/76 Combination air temp. (°F DB) -9.9 102.0 2.67 121.5 3.20 141.8 3.77 151.5 4.06 161.3 4.34...
  • Page 28 COOLING CAPACITY DATA ARUM168BTE5 / ARUM168DTE5 168,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 79.5 2.04 94.5 2.42 110.3 2.85 117.8 3.05 125.3 3.25...
  • Page 29 COOLING CAPACITY DATA ARUM168BTE5 / ARUM168DTE5 168,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 56.7 1.52 67.5 1.79 78.8 2.00 84.0 2.16 89.3 2.32...
  • Page 30 COOLING CAPACITY DATA ARUM192BTE5 / ARUM192DTE5 192,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor 68/57 73/61 79/64 80/67 85/70 88/73 91/76 Combination air temp. (°F DB) -9.9 174.6 4.36 207.4 5.29 241.1 6.28 249.9 6.77 253.5 7.31...
  • Page 31 COOLING CAPACITY DATA ARUM192BTE5 / ARUM192DTE5 192,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor 68/57 73/61 79/64 80/67 85/70 88/73 91/76 Combination air temp. (°F DB) -9.9 147.2 3.78 175.6 4.56 204.0 5.41 218.2 5.86 232.4 6.28...
  • Page 32 COOLING CAPACITY DATA ARUM192BTE5 / ARUM192DTE5 192,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor 68/57 73/61 79/64 80/67 85/70 88/73 91/76 Combination air temp. (°F DB) -9.9 116.6 2.97 138.9 3.56 162.0 4.20 173.1 4.52 184.3 4.83...
  • Page 33 COOLING CAPACITY DATA ARUM192BTE5 / ARUM192DTE5 192,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor 68/57 73/61 79/64 80/67 85/70 88/73 91/76 Combination air temp. (°F DB) -9.9 90.9 2.27 108.0 2.70 126.0 3.17 134.6 3.40 143.1 3.62...
  • Page 34 COOLING CAPACITY DATA ARUM192BTE5 / ARUM192DTE5 192,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor 68/57 73/61 79/64 80/67 85/70 88/73 91/76 Combination air temp. (°F DB) -9.9 64.8 1.69 77.1 1.99 90.0 2.23 96.0 2.40 102.0 2.58...
  • Page 35 COOLING CAPACITY DATA ARUM216BTE5 / ARUM216DTE5 216,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor 68/57 73/61 79/64 80/67 85/70 88/73 91/76 Combination air temp. (°F DB) -9.9 196.4 4.92 233.3 5.97 271.2 7.09 281.2 7.65 285.2 8.25...
  • Page 36 COOLING CAPACITY DATA ARUM216BTE5 / ARUM216DTE5 216,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 165.7 4.27 197.6 5.15 229.5 6.11 245.5 6.62 261.5 7.09...
  • Page 37 COOLING CAPACITY DATA ARUM216BTE5 / ARUM216DTE5 216,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor 68/57 73/61 79/64 80/67 85/70 88/73 91/76 Combination air temp. (°F DB) -9.9 131.1 3.35 156.2 4.02 182.3 4.74 194.8 5.10 207.3 5.45...
  • Page 38 COOLING CAPACITY DATA ARUM216BTE5 / ARUM216DTE5 216,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor 68/57 73/61 79/64 80/67 85/70 88/73 91/76 Combination air temp. (°F DB) -9.9 102.2 2.56 121.5 3.05 141.8 3.58 151.4 3.84 161.0 4.09...
  • Page 39 COOLING CAPACITY DATA ARUM216BTE5 / ARUM216DTE5 216,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor 68/57 73/61 79/64 80/67 85/70 88/73 91/76 Combination air temp. (°F DB) -9.9 72.9 1.91 86.8 2.25 101.3 2.52 108.0 2.71 114.8 2.92...
  • Page 40 COOLING CAPACITY DATA ARUM241BTE5 / ARUM241DTE5 240,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor 68/57 73/61 79/64 80/67 85/70 88/73 91/76 Combination air temp. (°F DB) -9.9 218.2 5.38 259.2 6.53 301.3 7.75 312.4 8.36 316.8 9.02...
  • Page 41 COOLING CAPACITY DATA ARUM241BTE5 / ARUM241DTE5 240,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor 68/57 73/61 79/64 80/67 85/70 88/73 91/76 Combination air temp. (°F DB) -9.9 184.1 4.67 219.5 5.63 255.0 6.67 272.8 7.23 290.5 7.75...
  • Page 42 COOLING CAPACITY DATA ARUM241BTE5 / ARUM241DTE5 240,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 145.7 3.66 173.6 4.39 202.5 5.18 216.4 5.58 230.4 5.96...
  • Page 43 COOLING CAPACITY DATA ARUM241BTE5 / ARUM241DTE5 240,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor 68/57 73/61 79/64 80/67 85/70 88/73 91/76 Combination air temp. (°F DB) -9.9 113.6 2.80 135.0 3.33 157.5 3.92 168.2 4.19 178.9 4.47...
  • Page 44 COOLING CAPACITY DATA ARUM241BTE5 / ARUM241DTE5 240,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor 68/57 73/61 79/64 80/67 85/70 88/73 91/76 Combination air temp. (°F DB) -9.9 81.0 2.09 96.4 2.46 112.5 2.75 120.0 2.96 127.5 3.19...
  • Page 45 COOLING CAPACITY DATA ARUM264BTE5 / ARUM264DTE5 264,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 240.1 5.63 285.2 6.82 331.4 8.10 343.7 8.74 348.5 9.43...
  • Page 46 COOLING CAPACITY DATA ARUM264BTE5 / ARUM264DTE5 264,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 202.4 4.88 241.5 5.89 280.5 6.98 300.0 7.57 319.6 8.10...
  • Page 47 COOLING CAPACITY DATA ARUM264BTE5 / ARUM264DTE5 264,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 160.3 3.83 190.9 4.59 222.8 5.41 238.1 5.83 253.4 6.23...
  • Page 48 COOLING CAPACITY DATA ARUM264BTE5 / ARUM264DTE5 264,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 124.9 2.93 148.5 3.48 173.3 4.09 185.1 4.38 196.9 4.67...
  • Page 49 COOLING CAPACITY DATA ARUM264BTE5 / ARUM264DTE5 264,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 89.1 2.18 106.1 2.57 123.8 2.87 132.0 3.10 140.3 3.33...
  • Page 50 COOLING CAPACITY DATA ARUM288BTE5 / ARUM288DTE5 288,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 261.9 6.07 311.1 7.36 361.6 8.74 374.9 9.42 380.2 10.17...
  • Page 51 COOLING CAPACITY DATA ARUM288BTE5 / ARUM288DTE5 288,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 220.8 5.26 263.4 6.35 306.0 7.53 327.3 8.16 348.6 8.74...
  • Page 52 COOLING CAPACITY DATA ARUM288BTE5 / ARUM288DTE5 288,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 174.9 4.13 208.3 4.95 243.0 5.84 259.7 6.29 276.4 6.72...
  • Page 53 COOLING CAPACITY DATA ARUM288BTE5 / ARUM288DTE5 288,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 136.3 3.16 162.0 3.76 189.0 4.41 201.9 4.73 214.7 5.04...
  • Page 54 COOLING CAPACITY DATA ARUM288BTE5 / ARUM288DTE5 288,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 97.2 2.35 115.7 2.77 135.0 3.10 144.0 3.34 153.0 3.59...
  • Page 55 COOLING CAPACITY DATA ARUM312BTE5 / ARUM312DTE5 312,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 283.7 6.63 337.0 8.04 391.7 9.55 406.2 10.30 411.9 11.11...
  • Page 56 COOLING CAPACITY DATA ARUM312BTE5 / ARUM312DTE5 312,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 239.3 5.75 285.4 6.94 331.5 8.23 354.6 8.92 377.7 9.55...
  • Page 57 COOLING CAPACITY DATA ARUM312BTE5 / ARUM312DTE5 312,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 189.4 4.51 225.6 5.41 263.3 6.38 281.4 6.87 299.4 7.34...
  • Page 58 COOLING CAPACITY DATA ARUM312BTE5 / ARUM312DTE5 312,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 147.6 3.45 175.5 4.11 204.8 4.82 218.7 5.17 232.6 5.51...
  • Page 59 COOLING CAPACITY DATA ARUM312BTE5 / ARUM312DTE5 312,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 105.3 2.57 125.4 3.03 146.3 3.39 156.0 3.65 165.8 3.93...
  • Page 60 COOLING CAPACITY DATA ARUM336BTE5 / ARUM336DTE5 336,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 305.5 7.39 362.9 8.97 421.9 10.65 437.4 11.49 443.6 12.40...
  • Page 61 COOLING CAPACITY DATA ARUM336BTE5 / ARUM336DTE5 336,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 257.7 6.41 307.4 7.74 357.0 9.18 381.9 9.94 406.8 10.65...
  • Page 62 COOLING CAPACITY DATA ARUM336BTE5 / ARUM336DTE5 336,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 204.0 5.03 243.0 6.04 283.6 7.12 303.0 7.66 322.5 8.19...
  • Page 63 COOLING CAPACITY DATA ARUM336BTE5 / ARUM336DTE5 336,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 159.0 3.85 189.0 4.58 220.6 5.38 235.5 5.77 250.5 6.14...
  • Page 64 COOLING CAPACITY DATA ARUM336BTE5 / ARUM336DTE5 336,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor 68/57 73/61 79/64 80/67 85/70 88/73 91/76 Combination air temp. (°F DB) -9.9 113.4 2.87 135.0 3.38 157.6 3.78 168.0 4.07 178.6 4.39...
  • Page 65 COOLING CAPACITY DATA ARUM360BTE5 / ARUM360DTE5 360,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 327.3 7.90 388.8 9.58 452.0 11.38 468.6 12.28 475.3 13.24...
  • Page 66 COOLING CAPACITY DATA ARUM360BTE5 / ARUM360DTE5 360,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 276.1 6.85 329.3 8.27 382.5 9.80 409.2 10.62 435.8 11.38...
  • Page 67 COOLING CAPACITY DATA ARUM360BTE5 / ARUM360DTE5 360,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 218.5 5.38 260.3 6.45 303.8 7.61 324.7 8.19 345.5 8.75...
  • Page 68 COOLING CAPACITY DATA ARUM360BTE5 / ARUM360DTE5 360,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 170.3 4.11 202.5 4.89 236.3 5.75 252.3 6.16 268.4 6.56...
  • Page 69 COOLING CAPACITY DATA ARUM360BTE5 / ARUM360DTE5 360,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 121.5 3.07 144.7 3.61 168.8 4.04 180.0 4.35 191.3 4.69...
  • Page 70 COOLING CAPACITY DATA ARUM384BTE5 / ARUM384DTE5 384,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 349.2 8.84 414.8 10.72 482.1 12.73 499.9 13.74 507.0 14.82...
  • Page 71 COOLING CAPACITY DATA ARUM384BTE5 / ARUM384DTE5 384,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 294.5 7.67 351.3 9.25 408.0 10.97 436.4 11.89 464.9 12.73...
  • Page 72 COOLING CAPACITY DATA ARUM384BTE5 / ARUM384DTE5 384,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 233.1 6.02 277.7 7.22 324.1 8.51 346.3 9.16 368.6 9.79...
  • Page 73 COOLING CAPACITY DATA ARUM384BTE5 / ARUM384DTE5 384,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 181.7 4.60 216.0 5.47 252.1 6.43 269.2 6.89 286.3 7.34...
  • Page 74 COOLING CAPACITY DATA ARUM384BTE5 / ARUM384DTE5 384,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 129.6 3.43 154.3 4.04 180.1 4.52 192.0 4.87 204.1 5.24...
  • Page 75 COOLING CAPACITY DATA ARUM408BTE5 / ARUM408DTE5 408,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 371.0 9.28 440.7 11.26 512.3 13.37 531.1 14.42 538.7 15.56...
  • Page 76 COOLING CAPACITY DATA ARUM408BTE5 / ARUM408DTE5 408,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 312.9 8.05 373.2 9.71 433.5 11.52 463.7 12.48 493.9 13.37...
  • Page 77 COOLING CAPACITY DATA ARUM408BTE5 / ARUM408DTE5 408,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 247.7 6.32 295.1 7.58 344.3 8.94 367.9 9.62 391.6 10.28...
  • Page 78 COOLING CAPACITY DATA ARUM408BTE5 / ARUM408DTE5 408,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 193.1 4.83 229.5 5.75 267.8 6.75 286.0 7.24 304.1 7.71...
  • Page 79 COOLING CAPACITY DATA ARUM408BTE5 / ARUM408DTE5 408,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 137.7 3.60 163.9 4.24 191.3 4.75 204.0 5.11 216.8 5.50...
  • Page 80 COOLING CAPACITY DATA ARUM432BTE5 / ARUM432DTE5 432,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 392.8 9.84 466.6 11.94 542.4 14.18 562.4 15.30 570.4 16.50...
  • Page 81 COOLING CAPACITY DATA ARUM432BTE5 / ARUM432DTE5 432,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 331.4 8.54 395.2 10.30 459.0 12.22 491.0 13.24 523.0 14.18...
  • Page 82 COOLING CAPACITY DATA ARUM432BTE5 / ARUM432DTE5 432,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 262.2 6.70 312.4 8.04 364.6 9.48 389.6 10.20 414.6 10.90...
  • Page 83 COOLING CAPACITY DATA ARUM432BTE5 / ARUM432DTE5 432,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 204.4 5.12 243.0 6.10 283.6 7.16 302.8 7.68 322.0 8.18...
  • Page 84 COOLING CAPACITY DATA ARUM432BTE5 / ARUM432DTE5 432,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 145.8 3.82 173.6 4.50 202.6 5.04 216.0 5.42 229.6 5.84...
  • Page 85 COOLING CAPACITY DATA ARUM456BTE5 / ARUM456DTE5 456,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 414.6 9.86 492.5 11.97 572.6 14.21 593.6 15.33 602.0 16.55...
  • Page 86 COOLING CAPACITY DATA ARUM456BTE5 / ARUM456DTE5 456,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 349.7 8.55 417.2 10.33 484.5 12.25 518.3 13.26 552.1 14.21...
  • Page 87 COOLING CAPACITY DATA ARUM456BTE5 / ARUM456DTE5 456,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 276.9 6.71 329.8 8.06 384.9 9.50 411.2 10.22 437.7 10.93...
  • Page 88 COOLING CAPACITY DATA ARUM456BTE5 / ARUM456DTE5 456,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 215.8 5.14 256.5 6.11 299.4 7.18 319.6 7.70 340.0 8.19...
  • Page 89 COOLING CAPACITY DATA ARUM456BTE5 / ARUM456DTE5 456,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 153.9 3.83 183.2 4.51 213.9 5.04 228.0 5.43 242.4 5.86...
  • Page 90 COOLING CAPACITY DATA ARUM480BTE5 / ARUM480DTE5 480,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 436.4 10.37 518.4 12.58 602.7 14.94 624.8 16.12 633.7 17.39...
  • Page 91 COOLING CAPACITY DATA ARUM480BTE5 / ARUM480DTE5 480,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 368.1 8.99 439.1 10.86 510.0 12.87 545.6 13.94 581.1 14.94...
  • Page 92 COOLING CAPACITY DATA ARUM480BTE5 / ARUM480DTE5 480,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 291.4 7.06 347.1 8.47 405.1 9.99 432.9 10.75 460.7 11.49...
  • Page 93 COOLING CAPACITY DATA ARUM480BTE5 / ARUM480DTE5 480,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 227.1 5.40 270.0 6.42 315.1 7.55 336.4 8.09 357.9 8.61...
  • Page 94 COOLING CAPACITY DATA ARUM480BTE5 / ARUM480DTE5 480,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 162.0 4.03 192.9 4.74 225.1 5.30 240.0 5.71 255.1 6.16...
  • Page 95 COOLING CAPACITY DATA ARUM504BTE5 / ARUM504DTE5 504,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 458.3 11.31 544.4 13.72 632.8 16.29 656.1 17.58 665.4 18.97...
  • Page 96 COOLING CAPACITY DATA ARUM504BTE5 / ARUM504DTE5 504,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 386.5 9.81 461.1 11.84 535.5 14.04 572.8 15.21 610.2 16.29...
  • Page 97 COOLING CAPACITY DATA ARUM504BTE5 / ARUM504DTE5 504,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 306.0 7.70 364.5 9.24 425.4 10.89 454.5 11.72 483.8 12.53...
  • Page 98 COOLING CAPACITY DATA ARUM504BTE5 / ARUM504DTE5 504,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 238.5 5.89 283.5 7.00 330.9 8.23 353.3 8.82 375.8 9.39...
  • Page 99 COOLING CAPACITY DATA ARUM504BTE5 / ARUM504DTE5 504,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor Combination 68/57 73/61 79/64 80/67 85/70 88/73 91/76 air temp. (°F DB) -9.9 170.1 4.39 202.5 5.17 236.4 5.78 252.0 6.23 267.9 6.71...
  • Page 100 HEATING CAPACITY DATA ARUM072BTE5 / ARUM072DTE5 72,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 56.0 3.45 56.0 3.78 56.0 4.28 55.8 4.69 55.6 5.11 55.6 5.53 55.6 5.74...
  • Page 101 HEATING CAPACITY DATA ARUM072BTE5 / ARUM072DTE5 72,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 55.1 4.89 55.1 5.11 55.1 5.44 54.9 5.67 54.7 5.90 54.7 6.35 54.7 6.62...
  • Page 102 HEATING CAPACITY DATA ARUM072BTE5 / ARUM072DTE5 72,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 54.6 4.02 54.6 4.24 54.6 4.57 54.4 4.92 54.3 5.28 53.0 5.97 50.2 6.39...
  • Page 103 HEATING CAPACITY DATA ARUM096BTE5 / ARUM096DTE5 96,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 74.6 4.31 74.6 4.73 74.6 5.35 74.4 5.87 74.2 6.39 74.2 6.92 74.2 7.18...
  • Page 104 HEATING CAPACITY DATA ARUM096BTE5 / ARUM096DTE5 96,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 73.4 6.11 73.4 6.39 73.4 6.80 73.2 7.09 73.0 7.38 73.0 7.95 73.0 8.27...
  • Page 105 HEATING CAPACITY DATA ARUM096BTE5 / ARUM096DTE5 96,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 72.8 5.02 72.8 5.30 72.8 5.71 72.6 6.15 72.4 6.60 70.6 7.47 67.0 7.99...
  • Page 106 HEATING CAPACITY DATA ARUM121BTE5 / ARUM121DTE5 120,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 93.3 5.89 93.3 6.45 93.3 7.30 93.0 8.01 92.7 8.72 92.7 9.45 92.7 9.80...
  • Page 107 HEATING CAPACITY DATA ARUM121BTE5 / ARUM121DTE5 120,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 91.8 8.34 91.8 8.72 91.8 9.28 91.5 9.68 91.2 10.07 91.2 10.85 91.2 11.29...
  • Page 108 HEATING CAPACITY DATA ARUM121BTE5 / ARUM121DTE5 120,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 91.0 6.85 91.0 7.23 91.0 7.80 90.7 8.40 90.4 9.00 88.3 10.20 83.7 10.91...
  • Page 109 HEATING CAPACITY DATA ARUM144BTE5 / ARUM144DTE5 144,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 112.0 6.75 112.0 7.39 112.0 8.37 111.6 9.18 111.3 9.98 111.3 10.82 111.3 11.23...
  • Page 110 HEATING CAPACITY DATA ARUM144BTE5 / ARUM144DTE5 144,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 110.1 9.55 110.1 9.98 110.1 10.63 109.8 11.09 109.4 11.54 109.4 12.43 109.4 12.94...
  • Page 111 HEATING CAPACITY DATA ARUM144BTE5 / ARUM144DTE5 144,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 109.2 7.85 109.2 8.28 109.2 8.93 108.9 9.62 108.5 10.32 106.0 11.68 100.5 12.50...
  • Page 112 HEATING CAPACITY DATA ARUM168BTE5 / ARUM168DTE5 168,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 130.6 8.95 130.6 9.81 130.6 11.10 130.2 12.17 129.8 13.24 129.8 14.35 129.8 14.89...
  • Page 113 HEATING CAPACITY DATA ARUM168BTE5 / ARUM168DTE5 168,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 128.5 12.67 128.5 13.24 128.5 14.10 128.1 14.70 127.7 15.31 127.7 16.48 127.7 17.16...
  • Page 114 HEATING CAPACITY DATA ARUM168BTE5 / ARUM168DTE5 168,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 127.4 10.41 127.4 10.99 127.4 11.85 127.0 12.76 126.6 13.68 123.6 15.49 117.2 16.58...
  • Page 115 HEATING CAPACITY DATA ARUM192BTE5 / ARUM192DTE5 192,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 149.3 9.90 149.3 10.85 149.3 12.27 148.8 13.46 148.4 14.65 148.4 15.87 148.4 16.47...
  • Page 116 HEATING CAPACITY DATA ARUM192BTE5 / ARUM192DTE5 192,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 146.8 14.01 146.8 14.65 146.8 15.60 146.4 16.26 145.9 16.93 145.9 18.23 145.9 18.98...
  • Page 117 HEATING CAPACITY DATA ARUM192BTE5 / ARUM192DTE5 192,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 145.6 11.52 145.6 12.15 145.6 13.10 145.2 14.12 144.7 15.13 141.3 17.13 134.0 18.34...
  • Page 118 HEATING CAPACITY DATA ARUM216BTE5 / ARUM216DTE5 216,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 168.0 11.36 168.0 12.45 168.0 14.09 167.4 15.45 166.9 16.82 166.9 18.22 166.9 18.91...
  • Page 119 HEATING CAPACITY DATA ARUM216BTE5 / ARUM216DTE5 216,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor air temp. Combination °F DB °F WB -12.6 -13.0 165.2 16.09 165.2 16.82 165.2 17.91 164.7 18.67 164.1 19.43 164.1 20.93 164.1 21.79...
  • Page 120 HEATING CAPACITY DATA ARUM216BTE5 / ARUM216DTE5 216,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 163.8 13.22 163.8 13.95 163.8 15.04 163.3 16.21 162.8 17.37 159.0 19.67 150.7 21.05...
  • Page 121 HEATING CAPACITY DATA ARUM241BTE5 / ARUM241DTE5 240,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 168.0 11.36 168.0 12.45 168.0 14.09 167.4 15.45 166.9 16.82 166.9 18.22 166.9 18.91...
  • Page 122 HEATING CAPACITY DATA ARUM241BTE5 / ARUM241DTE5 240,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor air temp. Combination °F DB °F WB -12.6 -13.0 165.2 16.09 165.2 16.82 165.2 17.91 164.7 18.67 164.1 19.43 164.1 20.93 164.1 21.79...
  • Page 123 HEATING CAPACITY DATA ARUM241BTE5 / ARUM241DTE5 240,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 163.8 13.22 163.8 13.95 163.8 15.04 163.3 16.21 162.8 17.37 159.0 19.67 150.7 21.05...
  • Page 124 HEATING CAPACITY DATA ARUM264BTE5 / ARUM264DTE5 264,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 205.2 13.26 205.2 14.54 205.2 16.45 204.6 18.04 19.63 21.27 22.07 23.13 -7.0 -7.6...
  • Page 125 HEATING CAPACITY DATA ARUM264BTE5 / ARUM264DTE5 264,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 201.9 18.78 201.9 19.63 201.9 20.9 201.3 21.79 200.7 22.69 200.7 24.43 200.7 25.43...
  • Page 126 HEATING CAPACITY DATA ARUM264BTE5 / ARUM264DTE5 264,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB temp. Combination °F DB °F WB -12.6 -13.0 200.2 15.43 200.2 16.29 200.2 17.56 199.6 18.91 20.28 194.2 22.96 184.2 24.57 170.8...
  • Page 127 HEATING CAPACITY DATA ARUM288BTE5 / ARUM288DTE5 288,000 Btu/h 208-230V / 460V Outdoor Units Indoor Air Temp. °F DB/°F WB Outdoor air temp. Combination °F DB °F WB -12.6 -13.0 223.9 14.21 223.9 15.58 223.9 17.62 223.2 19.33 222.6 21.04 222.6 22.79 222.6 23.65...
  • Page 128 HEATING CAPACITY DATA ARUM288BTE5 / ARUM288DTE5 288,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB temp. Combination °F DB °F WB -12.6 -13.0 220.2 20.12 220.2 21.04 220.2 22.4 219.6 23.35 218.9 24.31 218.9 26.18 218.9 27.25...
  • Page 129 HEATING CAPACITY DATA ARUM288BTE5 / ARUM288DTE5 288,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 218.4 16.54 218.4 17.45 218.4 18.81 217.8 20.27 217.1 21.73 211.9 24.6 26.33 186.3...
  • Page 130 HEATING CAPACITY DATA ARUM312BTE5 / ARUM312DTE5 312,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 242.6 15.67 242.6 17.18 242.6 19.44 241.8 21.32 241.1 23.21 241.1 25.14 241.1 26.09...
  • Page 131 HEATING CAPACITY DATA ARUM312BTE5 / ARUM312DTE5 312,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 238.6 22.2 238.6 23.21 238.6 24.71 237.9 25.76 237.1 26.81 237.1 28.88 237.1 30.06...
  • Page 132 HEATING CAPACITY DATA ARUM312BTE5 / ARUM312DTE5 312,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB temp. Combination °F DB °F WB -12.6 -13.0 236.6 18.24 236.6 19.25 236.6 20.75 235.9 22.36 235.2 23.97 229.6 27.14 217.7 29.04...
  • Page 133 HEATING CAPACITY DATA ARUM336BTE5 / ARUM336DTE5 336,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 261.3 17.25 261.3 18.90 261.3 21.39 260.4 23.46 259.6 25.54 259.6 27.67 259.6 28.71...
  • Page 134 HEATING CAPACITY DATA ARUM336BTE5 / ARUM336DTE5 336,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 24.43 25.54 27.19 256.2 28.35 255.3 29.5 255.3 31.78 255.3 33.08 255.3 34.83 -7.0...
  • Page 135 HEATING CAPACITY DATA ARUM336BTE5 / ARUM336DTE5 336,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 254.8 20.07 254.8 21.18 254.8 22.84 24.61 253.2 26.37 247.3 29.87 234.4 31.96 217.3...
  • Page 136 HEATING CAPACITY DATA ARUM360BTE5 / ARUM360DTE5 360,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 280.0 18.11 280.0 19.84 280.0 22.46 279.0 24.63 278.2 26.8 278.2 29.04 278.2 30.14...
  • Page 137 HEATING CAPACITY DATA ARUM360BTE5 / ARUM360DTE5 360,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 275.3 25.64 275.3 26.8 275.3 28.54 274.5 29.76 273.5 30.97 273.5 33.36 273.5 34.73...
  • Page 138 HEATING CAPACITY DATA ARUM360BTE5 / ARUM360DTE5 360,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 21.07 22.23 23.97 272.2 25.83 271.3 27.69 31.35 251.2 33.55 232.9 36.48 -7.0 -7.6...
  • Page 139 HEATING CAPACITY DATA ARUM384BTE5 / ARUM384DTE5 384,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 298.6 20.31 298.6 22.26 298.6 25.19 297.6 27.62 296.7 30.06 296.7 32.57 296.7 33.8...
  • Page 140 HEATING CAPACITY DATA ARUM384BTE5 / ARUM384DTE5 384,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 293.7 28.76 293.7 30.06 293.7 32.01 292.8 33.37 291.8 34.74 291.8 37.41 291.8 38.95...
  • Page 141 HEATING CAPACITY DATA ARUM384BTE5 / ARUM384DTE5 384,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 291.2 23.63 291.2 24.94 291.2 26.89 290.3 28.97 289.4 31.05 282.6 35.16 267.9 37.63...
  • Page 142 HEATING CAPACITY DATA ARUM408BTE5 / ARUM408DTE5 408,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 317.3 21.26 317.3 23.3 317.3 26.36 316.2 28.91 315.3 31.47 315.3 34.09 315.3 35.38...
  • Page 143 HEATING CAPACITY DATA ARUM408BTE5 / ARUM408DTE5 408,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 30.1 31.47 33.51 311.1 34.93 36.36 39.16 40.77 42.92 -7.0 -7.6 339.8 33.16 339.8...
  • Page 144 HEATING CAPACITY DATA ARUM408BTE5 / ARUM408DTE5 408,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 309.4 24.74 309.4 26.1 309.4 28.14 308.5 30.33 307.5 32.5 300.3 36.8 284.7 39.39...
  • Page 145 HEATING CAPACITY DATA ARUM432BTE5 / ARUM432DTE5 432,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 336.0 22.72 336.0 24.9 336.0 28.18 334.8 30.9 333.8 33.64 333.8 36.44 333.8 37.82...
  • Page 146 HEATING CAPACITY DATA ARUM432BTE5 / ARUM432DTE5 432,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 330.4 32.18 330.4 33.64 330.4 35.82 329.4 37.34 328.2 38.86 328.2 41.86 328.2 43.58...
  • Page 147 HEATING CAPACITY DATA ARUM432BTE5 / ARUM432DTE5 432,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB temp. Combination °F DB °F WB -12.6 -13.0 327.6 26.44 327.6 27.9 327.6 30.08 326.6 32.42 325.6 34.74 39.34 301.4 42.1 279.4...
  • Page 148 HEATING CAPACITY DATA ARUM456BTE5 / ARUM456DTE5 456,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 354.6 23.14 354.6 25.35 354.6 28.69 353.4 31.47 352.3 34.26 352.3 37.12 352.3 38.51...
  • Page 149 HEATING CAPACITY DATA ARUM456BTE5 / ARUM456DTE5 456,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 348.8 32.77 348.8 34.26 348.8 36.47 347.7 38.03 346.5 39.57 346.5 42.63 346.5 44.37...
  • Page 150 HEATING CAPACITY DATA ARUM456BTE5 / ARUM456DTE5 456,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 345.8 26.92 345.8 28.41 345.8 30.64 344.7 33.01 343.6 35.37 335.6 40.07 318.1 42.87...
  • Page 151 HEATING CAPACITY DATA ARUM480BTE5 / ARUM480DTE5 480,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 373.3 24.00 373.3 26.29 373.3 29.76 372.0 32.64 370.9 35.52 370.9 38.49 370.9 39.94...
  • Page 152 HEATING CAPACITY DATA ARUM480BTE5 / ARUM480DTE5 480,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 367.1 33.98 367.1 35.52 367.1 37.82 39.44 364.7 41.04 364.7 44.21 364.7 46.02 364.7...
  • Page 153 HEATING CAPACITY DATA ARUM480BTE5 / ARUM480DTE5 480,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 27.92 29.46 31.77 362.9 34.23 361.7 36.69 353.3 41.55 334.9 44.46 310.5 48.35 -7.0...
  • Page 154 HEATING CAPACITY DATA ARUM504BTE5 / ARUM504DTE5 504,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 391.9 26.20 391.9 28.71 391.9 32.49 390.6 35.63 389.4 38.78 389.4 42.02 389.4 43.60...
  • Page 155 HEATING CAPACITY DATA ARUM504BTE5 / ARUM504DTE5 504,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 385.5 37.1 385.5 38.78 385.5 41.29 384.3 43.05 44.81 48.26 50.24 52.9 -7.0 -7.6...
  • Page 156 HEATING CAPACITY DATA ARUM504BTE5 / ARUM504DTE5 504,000 Btu/h 208-230V / 460V Outdoor Units Outdoor air Indoor Air Temp. °F DB/°F WB Combination temp. °F DB °F WB -12.6 -13.0 382.2 30.48 382.2 32.17 382.2 34.69 37.37 379.8 40.05 370.9 45.36 351.6 48.54 52.79...
  • Page 157: Correction Factors

    CORRECTION FACTORS Defrost Correction Factor for Heating Operation on page 158 Equivalent Length Calculation on page 158 Elevation Correction Factors on page 159...
  • Page 158: Defrost Correction Factor For Heating Operation

    CORRECTION FACTORS The correction factors shown below are calculated in the LATS software programs. Defrost Correction Factor for Heating Operation Capacity tables do not take into consideration capacity reduction Table 1: Outdoor Unit Frost Accumulation Factor (Heating) when frost has accumulated on the condenser coil, nor during Entering DB (ºF) 19.4 23.0 26.6 32.0 37.4 41.0 44.6 defrost operation.
  • Page 159: Elevation Correction Factors

    CORRECTION FACTORS Elevation Correction Factors For each outdoor unit, calculate the equivalent length of the liquid line from the outdoor unit to the farthest indoor unit. Also, determine the elevation difference of farthest indoor unit above or below the outdoor unit. Find corresponding cooling capacity correction factor in tables below and on the next page.
  • Page 160 CORRECTION FACTORS The correction factors shown below are calculated in the LATS software programs. Table 4: ARUM Outdoor Unit Cooling Correction Factors (360BTE5 / 360DTE5 to 504BTE5 / 504DTE5). Equivalent Length (ELF) Elevation Differences 98 131 164 197 230 262 295 328 361 394 427 459 492 525 558 591 623 656 689 738 (ft.) HU—Indoor units above heat pump unit (ft.) 1.0 0.99 0.97 0.95 0.94 0.92 0.90 0.89 0.88 0.86 0.85 0.84 0.83 0.82 0.81 0.81 0.80 0.79 0.78 0.77 0.77 0.76 0.75...
  • Page 161 To access additional technical documentation such as submittals, engineering, installation, service, general best practice, and building ventilation manuals, as well as white papers, catalogs, LATS software programs, and more, log in to www.lghvac.com.
  • Page 162 20001747 ISO 9001: 2008 LG ELECTRONICS INC. LG Electronics, U.S.A., Inc. Commercial Air Conditioning Division 4300 North Point Parkway Alpharetta, Georgia 30022 New Issue: PD_MultiV_5_All_01_17 www.lghvac.com LG Electronics Commercial Products Support 1-888-865-3026 USA Follow the prompts for commercial A/C products.

Table of Contents