Functions can be individually set from each of the digital
input terminals X1 to X9.
Function
Value
0,1,2,3 Multi-step frequency selection (1 to 15 steps)
Acceleration and deceleration time selection (3 steps)
4,5
Self-hold selection (HLD)
6
Coast-to-stop command (BX)
7
Alarm reset (RST)
8
External alarm (THR)
9
Jogging (JOG)
10
Frequency setting 2 / Frequency setting 1 (Hz 2 / Hz1)
11
Motor 2 / Motor 1 (M2 / M1)
12
DC injection brake command (DCBRK)
13
Torque limit 2 / Torque limit 1 (TL2 / TL1)
14
Switching operation from line to drive (50 Hz) (SW50)
15
Switching operation from line to drive (60 Hz) (SW60)
16
UP command (UP)
17
DOWN command (DOWN)
18
Edit permission command (WE-KP)
19
PID control cancellation (Hz / PID)
20
Normal/Inverse switching (Terminals 12 and C1) (IVS)
21
Interlock (52-2) (IL)
22
Torque control cancellation (Hz/TRQ)
23
Link communication selection (LE)
24
Universal DI (U-DI)
25
Pick up start mode (STM)
26
Timed alarm stop command (STOP1)
30
Timed alarm stop command with
31
Deceleration time 4 (STOP2)
Note: Values which are not set in the functions from E01
to E09 are assumed to be inactive.
Multi-step frequency selection
Value 0,1, 2, 3: The frequency can be switched to a
preset frequency in function codes C05 to C19 by
switching the external digital input signal. Assign values
0 to 3 to the target digital input terminal. The combina-
tion of input signals determines the frequency.
Combination of
Input Signals
3
2
1
(SS8)
(SS4)
(SS2)
off
off
off
off
off
on
off
off
on
off
on
off
off
on
off
off
on
on
off
on
on
on
off
off
on
off
off
on
off
on
on
off
on
on
on
off
on
on
off
on
on
on
on
on
on
Acceleration and Deceleration time selection
Value 4, 5: The acceleration and deceleration time can
be switched to a preset time in function codes E10 to
E15 by switching the external digital input signal. Assign
values 4 and 5 to the target digital input terminal. The
combination of input signals determines the acceleration
and deceleration times.
Combination
of Input Signals
5
4
(RT2)
(RT1)
off
off
off
on
on
off
on
on
5-18
Selected Frequency
0
(SS1)
on
C05 MULTI Hz-1
off
C06 MULTI Hz-2
Related
on
C07 MULTI Hz-3
Functions:
off
C08 MULTI Hz-4
C05-C19
on
C09 MULTI Hz-5
off
C10 MULTI Hz-6
Setting
on
C11 MULTI Hz-7
Setting
off
C12 MULTI Hz-8
0.00 to
on
C13 MULTI Hz-9
- 120.00 Hz
off
C14 MULTI Hz-10
on
C15 MULTI Hz-11
off
C16 MULTI Hz-12
on
C17 MULTI Hz-13
off
C18 MULTI Hz-14
on
C19 MULTI Hz-15
Selected Acceleration /
Deceleration Times
F07 ACC TIME1
F08 DEC TIME1
Related
E10 ACC TIME2
Functions
E11 DEC TIME2
E10-E15
E12 ACC TIME3
Setting Range
E13 DEC TIME3
0.01 to 3600s
E14 ACC TIME4
E15 DEC TIME4

Hide quick links: