Siemens SITOP PSU8200 Manual

Siemens SITOP PSU8200 Manual

1ph
Hide thumbs Also See for SITOP PSU8200:
SITOP PSU8200 1ph
SITOP power supply
SITOP PSU8200 1ph
Manual
SITOP PSU8200 24 V/5 A
6EP3333-8SB00-0AY0
SITOP PSU8200 24 V/10 A
6EP3334-8SB00-0AY0
SITOP PSU8200 24 V/20 A
6EP1336-3BA10
11.2014
C98130-A7633-A1-3-7629
___________________
Overview
___________________
Safety instructions
Description, device design,
___________________
dimension drawing
___________________
Mounting/removal
Mounting position, mounting
___________________
clearances
___________________
Installation
___________________
Technical data
___________________
Safety, approvals, EMC
___________________
Ambient conditions
___________________
Applications
___________________
Environment
___________________
Service & Support
1
2
3
4
5
6
7
8
9
10
11
Table of Contents
loading

Summary of Contents for Siemens SITOP PSU8200

  • Page 1 Installation Manual ___________________ Technical data ___________________ Safety, approvals, EMC ___________________ Ambient conditions ___________________ Applications ___________________ Environment ___________________ Service & Support SITOP PSU8200 24 V/5 A 6EP3333-8SB00-0AY0 SITOP PSU8200 24 V/10 A 6EP3334-8SB00-0AY0 SITOP PSU8200 24 V/20 A 6EP1336-3BA10 11.2014 C98130-A7633-A1-3-7629...
  • Page 2: Legal Information

    Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Overview

    Overview 1-phase SITOP PSU8200 power supplies from the SITOP modular product line are high- performance, regulated technology power supplies for automated systems and machines. In addition to the basic functions required, these low-profile power supply units have an outstanding overload behavior.
  • Page 4 24 V / 10 A output Input, 1 and 2-phase AC or DC, 6EP1336-3BA10 Output 24 V DC / 20 A Accessories Type Order number Device identification labels 20 mm × 7 mm, Ti grey 3RT2900-1SB20 SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 5: Table Of Contents

    Technical data ............................37 Input ............................37 Output ............................. 39 Efficiency ..........................44 Closed-loop control ......................... 45 Protection and monitoring ....................... 46 MTBF ............................46 Mechanical system ......................... 46 Accessories ..........................47 Dimension drawing ......................... 47 SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 6 Series connection for increased voltage ................58 Overload protection in the 24 V output circuit ................ 59 Protection against short-time voltage dips ................60 Protecting against longer power failures ................61 Environment ............................63 Service & Support ..........................65 SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 7: Safety Instructions

    Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 8 Safety instructions SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 9: Description, Device Design, Dimension Drawing

    Description, device design, dimension drawing Device description SITOP PSU8200 1 ph is a primary-clocked power supply for connection to a 1-phase AC line supply. An electronically regulated DC voltage that can be set via a potentiometer is available at the output of the device. The output of the device is isolated, no-load proof and short-circuit proof.
  • Page 10 Description, device design, dimension drawing 2.1 Device description SITOP PSU8200 20A 1ph is a primary-clocked power supply for connection to a 1-phase/2- phase AC line supply or a DC supply. An electronically regulated DC voltage that can be set via a potentiometer is available at the output of the device. The output of the device is isolated, no-load proof and short-circuit proof.
  • Page 11: Connections And Terminal Designation

    One screw terminal each signaling contacts 13, 14 ⑤ One screw terminal each remote contacts 15, 16 Do not subject the end stop to higher loads Figure 2-3 Terminal data for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 12 2 screw terminals output "+" ② 2 screw terminals output "–" ③ One screw terminal each signaling contacts 13, 14 Do not subject the end stop to higher loads Figure 2-4 Terminal data for 6EP1336-3BA10 SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 13: Potentiometer

    It is only permissible to use an insulated screwdriver when actuating the potentiometer. For information on actuating the potentiometer (screwdriver, torque), see Figure 2-4 Terminal data for 6EP1336-3BA10 (Page 12). and Figure 2-3 Terminal data for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 (Page 11) SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 14: Status Displays And Signaling

    Overload, output voltage <20 V ±0.5 V (only in "constant current" mode) Signaling contact, contacts 13-14 open (quiescent position) Red LED lit Latching shut down or remote OFF Signaling contact, contacts 13-14 open (quiescent position) SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 15 Yellow LED (4.2) lit Overload (U <20 V ±0.5 V) Signaling contact (5), contacts 13-14 open (quiescent position) Red LED (4.3) lit Latching shutdown due to overload Signaling contact (5), contacts 13-14 open (quiescent position) SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 16: Change-Over Switch

    10 s after power ON or remote ON. During these first 10 s, the device responds for overload as if the switch is OFF. SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 17 Description, device design, dimension drawing 2.5 Change-over switch Delivery state: A-OFF; B-OFF Note Selector switches may only be activated when the device is switched off. SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 18: Remote Contact

    (R < 8 kΩ). If the power supply is shut down and latched in the "latching shutdown" mode as a result of an overload, then it can be restarted using remote OFF followed by remote Figure 2-9 Remote contact for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 19: Block Diagram

    Description, device design, dimension drawing 2.7 Block diagram Block diagram Figure 2-10 Block diagram for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 20 Description, device design, dimension drawing 2.7 Block diagram Figure 2-11 Block diagram for 6EP1336-3BA10 SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 21: Dimensions And Weight

    Description, device design, dimension drawing 2.8 Dimensions and weight Dimensions and weight Figure 2-12 Dimension drawing 6EP3333-8SB00-0AY0 Figure 2-13 Dimension drawing 6EP3334-8SB00-0AY0 SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 22 (24 V/20 A) Dimensions 45 × 125 × 125 55 × 125 × 125 90 × 125 × 120 (W × H × D) in mm Weight approx. 0.8 kg approx. 1.0 kg approx. 1.2 kg SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 23: Mounting/Removal

    WARNING Installing the device in a housing or a control cabinet The SITOP PSU8200 1ph power supply is a built-in device. It must be installed in a housing or control cabinet, to which only qualified personnel have access. The device can be mounted in a control cabinet on standard mounting rails according to EN 60715.
  • Page 24 If the devices are to be used in hazardous zones (II 3G Ex nA nC IIC T3 Gc or II 3G Ex nA nC IIC T4 Gc), they must be installed in a distribution box with degree of protection IP54 or higher. SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 25: Mounting Position, Mounting Clearances

    50 mm). No space is required at the side. Output current as a function of the ambient temperature and mounting height Figure 4-1 6EP3333-8SB00-0AY0 standard mounting position Figure 4-2 6EP3334-8SB00-0AY0 standard mounting position SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 26 Mounting position, mounting clearances 4.1 Standard mounting position Figure 4-3 6EP1336-3BA10 standard mounting position Figure 4-4 Mounting height derating For details, see Ambient conditions (Page 53) SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 27: Other Mounting Positions

    Particularly when installing on a vertically fastened standard mounting rail, additional measures may be required, e.g. to prevent the device from slipping on the standard mounting rail. 4.2.1 6EP3333-8SB00-0AY0 Figure 4-5 6EP3333-8SB00-0AY0 mounting position (1) Figure 4-6 6EP3333-8SB00-0AY0 mounting position (2) SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 28 Mounting position, mounting clearances 4.2 Other mounting positions Figure 4-7 6EP3333-8SB00-0AY0 mounting position (3) Figure 4-8 6EP3333-8SB00-0AY0 mounting position (4) Figure 4-9 6EP3333-8SB00-0AY0 mounting position (5) SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 29: 6Ep3334-8Sb00-0Ay0

    Mounting position, mounting clearances 4.2 Other mounting positions 4.2.2 6EP3334-8SB00-0AY0 Figure 4-10 6EP3334-8SB00-0AY0 mounting position (1) Figure 4-11 6EP3334-8SB00-0AY0 mounting position (2) Figure 4-12 6EP3334-8SB00-0AY0 mounting position (3) SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 30 Mounting position, mounting clearances 4.2 Other mounting positions Figure 4-13 6EP3334-8SB00-0AY0 mounting position (4) Figure 4-14 6EP3334-8SB00-0AY0 mounting position (5) SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 31: 6Ep1336-3Ba10

    Mounting position, mounting clearances 4.2 Other mounting positions 4.2.3 6EP1336-3BA10 Figure 4-15 6EP1336-3BA10 mounting position (1) Figure 4-16 6EP1336-3BA10 mounting position (2) Figure 4-17 6EP1336-3BA10 mounting position (3) SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 32 Mounting position, mounting clearances 4.2 Other mounting positions Figure 4-18 6EP1336-3BA10 mounting position (4) Figure 4-19 6EP1336-3BA10 mounting position (5) SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 33: Installation

    Figure 5-1 Line connection for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 SITOP PSU8200 1ph (6EP1336-3BA10) power supplies are designed to be connected to a 1-phase AC line voltage or to 2 line conductors of three-phase line supplies (TN, TT or IT system according to VDE 0100 T 300 / IEC 364-3) with a rated voltage of 120-230 V AC, 50/60 Hz or a DC voltage.
  • Page 34 A ground-fault circuit interrupter is not permissible against indirect contact as the only protective measure. This applies for the complete line supply protected by the ground-fault circuit interrupter. Protection SITOP PSU8200 1ph Line-side protection 6EP3333-8SB00-0AY0 Recommended: Miniature circuit breaker (IEC 898) characteristic C, 6 A...
  • Page 35: Output-Side Connection

    5.2 Output-side connection Output-side connection At its output, the SITOP PSU8200 1ph power supply provides an isolated (= non-grounded) SELV output voltage (Safety Extra Low Voltage). The output of the power supply is no-load, overload, and short-circuit proof. If an overload occurs, the electronic current limiting function limits the output current to a maximum value (see Section Technical data (Page 37)).
  • Page 36 Installation 5.2 Output-side connection SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 37: Technical Data

    Input current / at rated value 1.2 A 1.9 A 2.5 A of input voltage 230 V Switch-on current limitation 10 A 10 A 20 A (+ 25° C), max. I²t, max 0.2 A 0.3 A SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 38 C; required for two- phase operation: Miniature circuit breaker, two-pole coupled or circuit breaker (8 or 4 A) according to UL 489: 3RV2711-1HD10 (120 V) or 3RV2711-1ED10 (230 V) Figure 6-1 Power failure buffering SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 39: Output

    240 W 480 W Constant overload current for 12 A 30 A a short circuit when powering up, typical Short-time overload current 15 A 30 A 60 A for a short circuit during operation, typical SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 40 See Figure 6-4 Output char- See Figure 6-5 6EP1336- acteristic curve 6EP3333- acteristic curve 6EP3334- 3BA10 single operation out- 8SB00-0AY0 stand-alone 8SB00-0AY0 stand-alone put characteristic (Page 41) operation (Page 41) operation (Page 41) Figure 6-2 Starting delay/voltage rise SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 41 Figure 6-5 6EP1336-3BA10 single operation output characteristic The device supplies a constant output voltage until the current limit is reached. In the event of an overload, the output current and the output voltage are reduced. SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 42 Selector switch A on (parallel operation): The output voltage falls with increasing output current. Figure 6-6 Output characteristic curve 6EP3333-8SB00-0AY0 parallel operation Figure 6-7 Output characteristic curve 6EP3334-8SB00-0AY0 parallel operation Figure 6-8 6EP1336-3BA10 parallel operation output characteristic SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 43 5 s or remote OFF and ON at the remote contact. 6EP1336-3BA10 is reset by switching off the power supply for longer than 5 s. Figure 6-9 Output characteristic curve 6EP3333-8SB00-0AY0 latching shutdown Figure 6-10 Output characteristic curve 6EP3334-8SB00-0AY0 latching shutdown Figure 6-11 6EP1336-3BA10 latching shutdown output characteristic SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 44: Efficiency

    No-load operation power loss, 1.5 W 1.5 W 10 W approx. Power loss in the "latching shut- down" state 1.2 W 1.2 W 6.5 W Figure 6-12 Power efficiency 6EP3333-8SB00-0AY0 Figure 6-13 Power efficiency 6EP3334-8SB00-0AY0 SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 45: Closed-Loop Control

    1 ms 5 ms Dyn. load regulation (Ia: 10/90/10 %), Ua ± typ. Load step regulation time 10 to 90 %, typ. 1 ms Load step regulation time 90 to 10 %, typ. 1 ms SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 46: Protection And Monitoring

    45 mm 55 mm 90 mm Height of the housing 125 mm 125 mm 125 mm Depth of the housing 125 mm 125 mm 125 mm Mounting width 45 mm 55 mm 90 mm SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 47: Accessories

    Device identification label 20mm × 7mm, Ti grey 3RT2900- 1SB20 Dimension drawing See Section Dimensions and weight (Page 21) CAD data that can be downloaded from the Internet: 6EP3333-8SB00-0AY0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00963) 6EP3334-8SB00-0AY0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00966) 6EP1336-3BA10 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00385) SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 48 Technical data 6.9 Dimension drawing SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 49: Safety, Approvals, Emc

    Degree of protection (EN 60529) IP20 Leakage current, typ. 1 mA Leakage current, max. 3.5 mA Test voltage See Table 7-1 Test voltage for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 (Page 50) and Table 7-2 Test voltage for 6EP1336-3BA10 (Page 51) SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 50: Test Voltage

    3000 VAC 3000 VAC 350 VAC Field test 2200 VDC 2200 VDC 500 VDC 1500 VAC 1500 VAC 350 VAC Note: Tripping current for DC measurement: 0 mA Tripping current for AC measurement: <100 mA SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 51: Approvals

    II 3G Ex nA nC IIC T3 Gc cCSAus HazLoc Class I, Div 2, Group cCSAus HazLoc Class I, Div 2, Group A,B,C,D T4 A,B,C,D T3 CB approval Yes, (IEC 60950-1) SEMI F47 compliance Fulfilled Marine approvals GL, ABS GL, ABS SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 52: Emc

    Voltage interruptions EN 61000-4-11 100 % for 5000 ms Emitted interference EN 55022 Class B Line harmonics limit EN 61000-3-2 Class A Generic standards EN61000-6-2 Noise immunity for industrial environments EN61000-6-3 Emission for residential areas SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 53: Ambient Conditions

    II from 2000 m to 6000 m (EN 50178) II to 2000 m (EN 60950-1) I from 2000 m to 6000 m (EN 60950-1) Storage: 1080 ... 660 hPa (-1000 ... +3500 m) • SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 55: Applications

    Applications Parallel connection to increase power rating To increase the power rating, SITOP PSU8200 power supplies of the same type can be directly connected in parallel. The following must be observed: ● The cables connected to each power supply at terminals "+" and "-" must have identical lengths and the same cable cross-sections (or the same impedance) up to a common external connection point (terminal strip) if possible.
  • Page 56 For this purpose, a suitable protective circuit (e.g. decoupling diode or DC-conform circuit breaker) must be installed between each "+" terminal of the power supply and the common connection point. SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 57: Parallel Connection For Redundancy

    Applications 9.2 Parallel connection for redundancy Parallel connection for redundancy Connecting several SITOP PSU8200 power supplies in parallel for redundancy purposes is required if especially high demands are placed regarding the availability of a reliable 24 V power supply. Using the SITOP PSE202Uredundancy module, two 24 V power supplies of the same type up to 20 A can be decoupled (Figure 9-2 Redundant configuration with two power supplies and SITOP PSE202U redundancy module (Page 57)).
  • Page 58: Series Connection For Increased Voltage

    Series connection for increased voltage To achieve an output voltage of 48 V DC, two 24 V SITOP PSU8200 power supplies of the same type can be connected in series. In this case, connect the "-" terminal of the first power supply to the "+"...
  • Page 59: Overload Protection In The 24 V Output Circuit

    9.4 Overload protection in the 24 V output circuit Overload protection in the 24 V output circuit If an overload occurs, the electronic current limiting function limits the SITOP PSU8200 output current to a maximum value (see Section Technical data (Page 37)). The output...
  • Page 60: Protection Against Short-Time Voltage Dips

    9.5 Protection against short-time voltage dips Protection against short-time voltage dips In the case of a drop in the line-side supply voltage, the SITOP PSU8200 power supply can still maintain the output voltage for a short time in the millisecond range (see section Technical data (Page 37)).
  • Page 61: Protecting Against Longer Power Failures

    Using the free-of-charge SITOP DC-UPS software tool, DC-UPS systems can be simply integrated into PC-based automation solutions. This supports further processing of the status signals and safely running down the PC. You can find additional information at: Manual, DC UPS with capacitors (http://support.automation.siemens.com/WW/view/en/48932766/133300) SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 62 – make it easy to integrate operating and diagnostics information into STEP 7 user programs. Preconfigured UPS faceplates for WinCC visualization can be downloaded at no charge. You can find additional information at: DC UPS SITOP UPS1600/UPS1100 Manual (http://support.automation.siemens.com/WW/view/en/84977415) SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 63: Environment

    The devices are in conformance with RoHS. As a rule, only non-silicon precipitating materials are used. Disposal guidelines Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as domestic refuse. SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 64 Environment SITOP PSU8200 1ph Manual, 11.2014, C98130-A7633-A1-3-7629...
  • Page 65: Service & Support

    ● Phone: + 49 (0) 911 895 7222 ● E-Mail (mailto:[email protected]) ● Internet: Online support request form (http://www.siemens.de/automation/support-request) Technical documentation on the Internet Operating instructions and manuals for SITOP are available in the Internet: Operating instructions/manuals (http://www.siemens.de/sitop/manuals) SITOP power supply homepage General news about our power supplies is available in the Internet at the SITOP homepage: SITOP (http://www.siemens.de/sitop)
  • Page 66 Service & Support Contact persons If you have any questions regarding the use of our products, then contact the Siemens contact person in your regional Siemens sales office. You can find these addresses as follows: ● On the Internet (http://www.siemens.de/automation/partner) ●...