C09-7

Default value load

All values per function group are changed to the default values.
9: All default values load (excluding maintenance)
10: Parameter A
11: Parameters B, C basic functions
12: Parameters B, C extended functions
13: Parameter B software option function
Parameter C hardware option function
14: Parameters B basic functions
15: Parameters B extended functions
16: Parameter B software option function
17: Parameters C basic functions
18: Parameters C extended functions
19: Parameter C hardware option function
Nothing will occur when values other than the above are set.
This parameter setting value will not be registered in the internal memory.
(Note)
C10-0~7

Custom parameter register

Set the No. of Block B, C parameter to be displayed on A04-0~7.
To set block B parameter B10-1, set as 0.10.1.
To set block C parameter C14-0, set as 1.14.0.
Refer to section 4-7 for details.
C12-0
FSV terminal input mode
C12-1
FS1 terminal input mode
C12-2
AUX terminal input mode
C12-3

Filter time constant for FSV/FSI and AUX input

As an example, the analog input value through FSV, FSI and AUX (C07-0 = 2 to 4) and
speed setting ratio is shown below. Refer to section 5-7-1 for additional details
6. Control Functions and Parameter Settings
The setting values exceeding 2000 are codes for maker maintenance, so do not
set. Otherwise, the internal factory adjustments may be lost and consequently the
drive will become unadjusted.
C12-0 = 1: 0~10V
= 2: 0~5V
= 3: 1~5V
S etting freq ue ncy/S etting spe ed
M ax . frequen cy
M ax . sp ee d
0
6-61
C 12 -0 =1, 2
C 12 -0 =3
5V
1V
10 V
F SV inp ut voltage