Transmission Format Of Block Communication - Toshiba TOSVERT VF-nC3 Instruction Manual

Hide thumbs Also See for TOSVERT VF-nC3:
Table of Contents
efesotomasyon.com -Toshiba inverter,drive,servo,plc

4.1.3. Transmission format of Block Communication

What is block communication?
Data can be written in and read from several data groups set in one communication by setting the
type of data desired for communication in the block communication parameters (f870, f871,
f875 to f879) in advance. Block communication can save the communication time.
Data is transmitted hexadecimal using the binary (HEX) code transmission characters. "Computer
→ inverter" is for writing only, while "Inverter → computer" for reply is for reading only.
Computer → Inverter (Block Communication)
Omissible
(3.5bytes
Start
INV-NO
Blank)
Code
"/"
1. 2FH("/") (1 byte) : Start code of binary mode
2. INV-NO (1 byte) : Inverter number. (Can be omitted in 1:1 communication): 00H to 3FH, FFH
3. CMD (1 byte)
: 'X' (Block communication command)
4. Number of write data groups (1 byte)
: Specify the number of data groups to be written (00H to 02H).
If specified outside of the range, data will be treated as a format error and data will not be
returned.
5. Number of read data groups (1 byte)
: Specify the number of data groups to be read (00H to 05H).
If specified outside of the range, data will be returned as "Number of read data groups = 0"
when returned by the inverter.
6. Write data1 (2 bytes)
: Needed when the number of write data groups is larger than 1.
Data to be written to the specified parameter selected by f870.
Dummy data is needed if the number of write data groups is larger than 1 even
though(none) is selected for f870.
7. Write data2 (2 bytes)
: Needed when the number of write data groups is 2.
Data to be written to the specified parameter selected by f871.
Dummy data is needed if the number of write data groups is 2 even though(none) is se-
lected for f871.
8. SUM (1 byte)
: Checksum (Cannot be omitted) 00H to FFH
Num-
Num-
CMD
ber of
ber of
"X"
write
data
groups
groups
Executed only when the inverter number matches the inverter number. Set on the panel,
except in FFH (broadcast communication).
Communication data will be invalidated and data will not be returned either if the inverter
number. Does not match.
Lower two digits (1 byte) of total sum from start code (SUM value not included)
Number of writing data groups x 2 bytes
Write
Write
data1
data1
data2
read
High
Low
data
Checksum Area
13
E6581657
(3.5bytes
Write
Write
SUM
Blank)
data2
High
Low