Planning; General Information - Bosch FPA-5000 System Description

Modular fire panel
Hide thumbs Also See for FPA-5000:
Table of Contents
Modular Fire Panel
3

Planning

3.1

General Information

NOTICE!
The simple, straightforward Fire System Designer (FSD) planning software can be used to
plan fire alarm systems that conform to the relevant limits (e.g. in terms of cable length,
power supply and energy requirement).
Bosch Sicherheitssysteme GmbH
Country-specific standards and guidelines must be considered during planning.
The regulations issued by regional authorities and institutions (e.g. fire service) must be
adhered to.
Please note that standards and guidelines may require that a maximum of one function in
more than one zone may fail.
For example, if the auxiliary power fails, only the fire detectors and/or manual call points
of one zone may fail.
We recommend the use of loops wherever possible, as they offer far greater security than
stub lines.
Terminating each stub and each T-tap with EOL modules is essential to set up a complete
fire alarm system complying with EN 54-13.
Conventional detectors approved for the FPA-5000 can be connected using one of the
following methods:
Using the CZM 0004 A 4 Zone Conventional Module
The module provides four DC primary lines (zones).
Using an FLM-420/4-CON GLT interface module on the LSN bus for two zones
When selecting the address cards, please note:
Each element or input that can trigger an alarm after programming requires its own
detection point. The inputs are classed as detection points if they are configured
accordingly using the FSP-5000-RPS panel software.
Refer to the information starting on Page 32.
In accordance with EN54-2, no more than 512 detectors and their functions may fail if a
system component fails. The corresponding measures are described under
Section 3.10 Redundancy, page 47 .
12 V/45 Ah batteries can only be used with the frame installation housings.
Use fuses complying with national regulations to protect the power lines.
Recommended fire detector cable: J--Y (St) Y 2 x 2 x 0.8 mm, red.
System Description
Planning | en
25